4 SELECTION OF INSTALLATION PLACE

Upon customer’s approval, install the air conditioner in a place which satisfies the following conditions:

Place where it can be installed horizontally.

Place which can reserve a sufficient service space for safe maintenance or checks.

Place where there is no problem even if the drained water overflows.

Avoid the following places:

Salty places (seaside area) or places with much gas sulfide (hot spring area) (If selecting such a place, special maintenance is required.)

Places where oil (including machine oil), steam, oil smoke or corrosive gas is generated.

Places where an organic solvent is used.

Chemical plants with a cooling system using liquid carbon dioxide.

Places where a device generating high frequency (inverter, non-utility generator, medical apparatus, or communication equipment) is set. (Malfunction or abnormal control of the air conditioner, or interference to devices listed above may occur.)

Places where discharged air from the outdoor unit blows against the windows of a neighbour's house.

Places unable to bear the weight of the unit.

Places with poor ventilation.

SMMS-i

Installation Manual

„Installation space

Leave space necessary for running, installation and servicing.

Air discharge

Air intake

Air intake

Air intake

Air intake

Installation/servicing surface

Square hole for handling

Outdoor unit top view

500mm or more

 

 

(Rear side)

 

 

10mm or more

 

 

500mm or more

 

 

(Front side)

20mm or more

20mm or more

10mm or more

NOTE

If there is an obstacle above the outdoor unit, leave a space of 2000mm or more to the top end of the outdoor unit.

If there is a wall around the outdoor unit, make sure that its height does not exceed 800mm.

Image 6
Contents For commercial use Not accessible to the general publicNon accessibile a clienti generici Vente interdite au grand publicContents Installation Precautions for SafetySelection of installation location „ Warning Indications on the Air Conditioner UnitNew Refrigerant Air Conditioner Installation Electrical wiringSMMS-i Installation Manual Relocation To Disconnect the Appliance from Main Power SupplyExplanation of symbols Accessory PartsInstallation of NEW Refrigerant AIR Conditioner „ Required Tools and Cautions on handlingSelection of Installation Place „ Installation spaceAvoid the following places Side Carrying in the Outdoor UnitCombination of outdoor units Front /BackWeight centre of an outdoor unit Installation of the Outdoor Unit„ Weight centre and weight Installation in a snowfall areaAt a level position Liquid pipingGas piping Model typeRefrigerant Piping When drawing pipes downwardSMMS-iInstallation Manual „ Connection of refrigerant pipeExtruding margin of copper pipe with flare tools a Unit mm Pipe connection method of valve at the gas side ExampleCoupling size of brazed pipe „ Selection of pipe sizeCapacity code of indoor and outdoor units Selection of pipe materialCapacity Pipe size for connecting piping between outdoor unitsType Gas side Liquid side Size of main piping26-EN Packed valve details „ Airtightness testSystem restriction Able to detect a serious leakage„ Vacuum drying Charging of refrigerant „ Adding refrigerantCalculation of additional refrigerant charge amount MAP080 MAP100 MAP120 MAP140 MAP160 Type„ F-GAS label „ Finishing after connecting pipes„ Full opening of the valve „ Heat insulation for pipePower wiring selection Electric Wiring„ Power supply specifications Pipe holding bracketSummary of communication wiring „ Specifications for communication wiringDesign of communication wiring Model Phase and frequency Nominal VoltageCommunication wiring between outdoor units L5 „ Connection of power wires and communication wiresGroup control through a Remote Controller Remote controller wiring L6, L7Power supply wire connection Communication wire connectionSMMS-i Installation Manual Screw size and tightening torque Address Setting „ Automatic address setting„ Regulation of high frequency wave Address setting procedure Board of the header outdoor unit indicates Remains lit on the display, the setting isSet the central control address 7-segment display indicatesOutdoor units setting manually Installation Manual „ Manual address setting using the remote controllerWiring example of 2 refrigerant lines SMMS-i Installation Manual Relay connector connection„Confirming the indoor unit An indoor unit usingRemote controller Addresses and the position„Changing the indoor unit Address using a remoteWired remote controller ControllerDefault address undecided „Resetting the addressResetting to the factory Set the addresses again after finishing the clearance„ Before test run When executing a test run using a Remote controller10TEST RUN „ Methods of test runCorrective trial Push and hold SW04 for more than 2 secondsInterface PC board Segment display and check code 11TROUBLESHOOTINGRotary switch setting value SW01 SW02 SW03 Indication„ Logbook 12MACHINE Card and Logbook„ Machine card Describe the following items on the machine cardStandards for minimum room volume are as follows EH99871699 Check of Concentration Limit

MMY-MAP0804HT8-E, MMY-MAP1604HT8Z-E, MMY-MAP1404HT8-E, MMY-MAP0804HT8Z-E, MMY-MAP1204HT8Z-E specifications

The Toshiba MMY-MAP0804HT8Z-E, MMY-MAP1404HT8-E, MMY-MAP1604HT8Z-E, MMY-MAP0804HT8-E, and MMY-MAP1604HT8-E are part of Toshiba's advanced air conditioning line-up, designed for both residential and commercial applications. These models are engineered to offer high efficiency, comfort, and reliability, making them an excellent choice for modern HVAC solutions.

One of the standout features of these models is their high Seasonal Energy Efficiency Ratio (SEER), which indicates their superior energy performance. They are built to reduce energy consumption while providing optimal cooling and heating capabilities. This is particularly beneficial for users looking to lower their energy bills without sacrificing comfort.

In terms of technology, Toshiba incorporates inverter technology in these air conditioning units. The inverter system adjusts the compressor's speed according to the cooling demand, ensuring consistent temperatures and enhanced energy savings. This feature is especially useful during peak usage periods, as it minimizes energy spikes associated with traditional on/off systems.

Additionally, the MMY-MAP series includes sophisticated air filtration systems that improve indoor air quality. These filters capture dust, allergens, and other pollutants, creating a healthier living or working environment. The units also come equipped with a quiet operation mode, allowing them to function with minimal noise – a crucial aspect for residential settings and quiet commercial spaces.

These models boast a sleek and compact design, making them easy to install in various configurations. Their aesthetic appeal ensures they blend seamlessly with any interior decor. Furthermore, they are built to withstand diverse environmental conditions, with robust materials that ensure durability and longevity.

User-friendly controls are another hallmark of the Toshiba MMY-MAP series. Many of these models support smart technology, allowing for remote operation via smartphones or tablets. This capability enhances convenience, enabling users to monitor and adjust settings in real-time.

In summary, the Toshiba MMY-MAP0804HT8Z-E, MMY-MAP1404HT8-E, MMY-MAP1604HT8Z-E, MMY-MAP0804HT8-E, and MMY-MAP1604HT8-E models epitomize efficiency and comfort. With their energy-saving features, advanced inverter technology, effective air filtration, and smart connectivity, these air conditioning units are designed to meet the demands of modern users, ensuring a comfortable and healthy indoor environment all year round.