Toshiba MMY-MAP0804HT8-E „Resetting the address, Resetting to the factory, Method

Page 29

SMMS-i

3 Push the SET button.

Installation Manual

„Resetting the address

SMMS-i

Installation Manual

The address of one of the indoor units connected to the selected refrigerant line is indicated on the LCD display and the fan and louvers of the unit are activated.

At first, the current indoor unit address is displayed in SET DATA.

(No system address is indicated.)

 

CODE No.

SET DATA SETTING

 

UNIT

No.

R.C.

No.

TEMP.

ON / OFF

(Resetting to the factory

default (address undecided))

Method 1

Clearing each address separately using a wired remote controller.

Set the system address, indoor unit address and group address to “0099” using a wired remote controller. (For the setting procedure, refer to the address setting procedures using the wired remote controller on the previous pages.)

Method 2

Clearing all the indoor unit addresses on a refrigerate line at

Header

 

Follower unit

unit

 

U3 U4

U3 U4

U1 U2

U5 U6

U1 U2

U5 U6

Header unit

U3 U4

U1

U2

 

U5

U6

 

 

 

 

 

Follower unit

U3 U4

U1 U2

U5 U6

 

 

 

 

 

 

 

 

Central control

 

 

 

 

 

 

 

 

controller

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

U1

U2

 

Header

 

 

 

 

 

U3

U4

 

 

 

 

 

 

 

 

 

 

unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

U3

U4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

U1

U2

 

 

U5

U6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TIMER SET

4

 

TIME

FILTER

 

 

RESET TEST

SET CL

8

 

 

Finish

 

 

6

once from the outdoor unit.

1 Turn off the refrigerant line to reset to the factory default and set the header outdoor unit of the line as below.

1) Disconnect the relay connectors between the

[U1, U2] and [U3, U4] terminals.

U1

U2

 

 

 

U1

U2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

B

 

 

 

A

B

 

Remote

 

Remote

controller

 

controller

U1 U2

A B

Remote controller

U1 U2

A B

U1 U2

A B

Remote controller

5, 7

Press to finish setting.

(Leave them as they are if they have already

been disconnected.)

2) Turn on dip switch 2 of SW30 on the interface

Indoor units to have their addresses initialized

4 Push the TIME / buttons repeatedly to change the value of the indoor unit address in SET DATA.

Change the value in SET DATA to that of a new address.

5 Push the SET button to confirm the new address on SET DATA.

6 Push the button (left side of the button) repeatedly to select another address to change. Each time you push the button, the indoor unit numbers in a refrigerant line are indicated one after another. Only the fan and louvers of the selected indoor unit are activated.

Repeat steps 4 to 6 to change the indoor unit addresses so as to make each of them unique.

7 Push the SET button.

(All the segments on the LCD display light up.)

8 Push the TEST button to finish the procedure.

P.C. board of the header outdoor unit if the

switch is OFF.

(Leave it as it is if it has already been set to

ON.)

2 Turn on the indoor and outdoor units of the refrigerant line for which you want to initialize the addresses. About one minute after turning on the power, confirm that the 7-segment display on the header outdoor unit indicates “U.1. - - -” and operate the interface P.C. board on the header outdoor unit of the refrigerant line as follows.

SW01

SW02

SW03

SW04

Clearable addresses

2

1

2

Confirm that the 7-segment display indicates

System/indoor unit/group address

“A.d.buS” and turn SW04 ON for more than five

 

 

 

seconds.

 

2

2

2

Confirm that the 7-segment display indicates

Central control address

“A.d.nEt” and turn SW04 ON for more than five

 

 

 

seconds.

 

3 Confirm that the 7-segment display indicates “A.d. c.L.” and set SW01, SW02 and SW03 to 1, 1, 1 respectively.

4 After a time “U.1.L08” appears on the 7-segment display if the address clearing has been completed successfully.

If the 7-segment display indicates “A.d. n.G.”, the outdoor unit may still connected with other refrigerant lines. Check the connection of the relay connectors between [U1, U2] and [U3, U4].

NOTE

Take care to carry out the procedure above correctly; otherwise, addresses in other refrigerate lines may also be cleared.

5 Set the addresses again after finishing the clearance.

EN

55-EN

– 28 –

56-EN

 

 

Image 29
Contents Non accessibile a clienti generici Not accessible to the general publicFor commercial use Vente interdite au grand publicContents Selection of installation location Precautions for SafetyInstallation „ Warning Indications on the Air Conditioner UnitSMMS-i Installation Manual Relocation Electrical wiringNew Refrigerant Air Conditioner Installation To Disconnect the Appliance from Main Power SupplyInstallation of NEW Refrigerant AIR Conditioner Accessory PartsExplanation of symbols „ Required Tools and Cautions on handlingAvoid the following places Selection of Installation Place„ Installation space Combination of outdoor units Carrying in the Outdoor UnitSide Front /Back„ Weight centre and weight Installation of the Outdoor UnitWeight centre of an outdoor unit Installation in a snowfall areaGas piping Liquid pipingAt a level position Model typeSMMS-iInstallation Manual When drawing pipes downwardRefrigerant Piping „ Connection of refrigerant pipePipe connection method of valve at the gas side Example Extruding margin of copper pipe with flare tools a Unit mmCapacity code of indoor and outdoor units „ Selection of pipe sizeCoupling size of brazed pipe Selection of pipe materialType Gas side Liquid side Pipe size for connecting piping between outdoor unitsCapacity Size of main piping26-EN System restriction „ Airtightness testPacked valve details Able to detect a serious leakage„ Vacuum drying Calculation of additional refrigerant charge amount „ Adding refrigerantCharging of refrigerant MAP080 MAP100 MAP120 MAP140 MAP160 Type„ Full opening of the valve „ Finishing after connecting pipes„ F-GAS label „ Heat insulation for pipe„ Power supply specifications Electric WiringPower wiring selection Pipe holding bracketDesign of communication wiring „ Specifications for communication wiringSummary of communication wiring Model Phase and frequency Nominal VoltageGroup control through a Remote Controller „ Connection of power wires and communication wiresCommunication wiring between outdoor units L5 Remote controller wiring L6, L7SMMS-i Installation Manual Screw size and tightening torque Power supply wire connectionCommunication wire connection „ Regulation of high frequency wave Address Setting„ Automatic address setting Address setting procedure Set the central control address Remains lit on the display, the setting isBoard of the header outdoor unit indicates 7-segment display indicatesWiring example of 2 refrigerant lines „ Manual address setting using the remote controllerOutdoor units setting manually Installation Manual SMMS-i Installation Manual Relay connector connectionRemote controller An indoor unit using„Confirming the indoor unit Addresses and the positionWired remote controller Address using a remote„Changing the indoor unit ControllerResetting to the factory „Resetting the addressDefault address undecided Set the addresses again after finishing the clearance10TEST RUN When executing a test run using a Remote controller„ Before test run „ Methods of test runInterface PC board Corrective trialPush and hold SW04 for more than 2 seconds Rotary switch setting value 11TROUBLESHOOTINGSegment display and check code SW01 SW02 SW03 Indication„ Machine card 12MACHINE Card and Logbook„ Logbook Describe the following items on the machine cardEH99871699 Check of Concentration Limit Standards for minimum room volume are as follows

MMY-MAP0804HT8-E, MMY-MAP1604HT8Z-E, MMY-MAP1404HT8-E, MMY-MAP0804HT8Z-E, MMY-MAP1204HT8Z-E specifications

The Toshiba MMY-MAP0804HT8Z-E, MMY-MAP1404HT8-E, MMY-MAP1604HT8Z-E, MMY-MAP0804HT8-E, and MMY-MAP1604HT8-E are part of Toshiba's advanced air conditioning line-up, designed for both residential and commercial applications. These models are engineered to offer high efficiency, comfort, and reliability, making them an excellent choice for modern HVAC solutions.

One of the standout features of these models is their high Seasonal Energy Efficiency Ratio (SEER), which indicates their superior energy performance. They are built to reduce energy consumption while providing optimal cooling and heating capabilities. This is particularly beneficial for users looking to lower their energy bills without sacrificing comfort.

In terms of technology, Toshiba incorporates inverter technology in these air conditioning units. The inverter system adjusts the compressor's speed according to the cooling demand, ensuring consistent temperatures and enhanced energy savings. This feature is especially useful during peak usage periods, as it minimizes energy spikes associated with traditional on/off systems.

Additionally, the MMY-MAP series includes sophisticated air filtration systems that improve indoor air quality. These filters capture dust, allergens, and other pollutants, creating a healthier living or working environment. The units also come equipped with a quiet operation mode, allowing them to function with minimal noise – a crucial aspect for residential settings and quiet commercial spaces.

These models boast a sleek and compact design, making them easy to install in various configurations. Their aesthetic appeal ensures they blend seamlessly with any interior decor. Furthermore, they are built to withstand diverse environmental conditions, with robust materials that ensure durability and longevity.

User-friendly controls are another hallmark of the Toshiba MMY-MAP series. Many of these models support smart technology, allowing for remote operation via smartphones or tablets. This capability enhances convenience, enabling users to monitor and adjust settings in real-time.

In summary, the Toshiba MMY-MAP0804HT8Z-E, MMY-MAP1404HT8-E, MMY-MAP1604HT8Z-E, MMY-MAP0804HT8-E, and MMY-MAP1604HT8-E models epitomize efficiency and comfort. With their energy-saving features, advanced inverter technology, effective air filtration, and smart connectivity, these air conditioning units are designed to meet the demands of modern users, ensuring a comfortable and healthy indoor environment all year round.