Physical and Electrical Data - 1 Phase
MODEL |
|
| H1RA018S06 | H1RA024S06 | H2RA030S06 |
| H2RA036S06 |
| H1RA042S06 | H1RA048S06 | H3RA060S06 | |
Unit Supply Voltage |
|
|
|
|
| 208/230 – 1 – 60 |
|
|
|
| ||
|
|
|
|
|
|
|
|
| ||||
Normal Voltage Range 1 |
|
|
|
| 187 to 252 |
|
|
| ||||
Minimum Circuit Ampacity | 12.5 | 15.6 | 17.5 |
| 21.5 |
| 26.1 | 30.1 | 37.3 | |||
|
|
|
|
|
|
|
|
|
| |||
Max. Overcurrent Device Amps 2 | 20 | 25 | 30 |
| 35 |
| 40 | 45 | 60 | |||
Compressor Type 3 |
| Recip | Recip | Recip |
| Recip |
| Recip | Recip | Scroll B | ||
Compressor Amps | Rated Load | 9.6 | 12.1 | 13.6 |
| 16.1 |
| 19.8 | 23 | 28.8 | ||
Locked Rotor | 54 | 57 | 73 |
| 82 |
| 97 | 110 | 160 | |||
|
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
| ||
Crankcase Heater |
| No | No | No |
| No |
| No | No | No | ||
|
|
|
|
|
|
|
|
|
|
| ||
Fan Motor Amps | Rated Load | 0.5 | 0.5 | 0.5 |
| 1.4 |
| 1.4 | 1.3 | 1.3 | ||
|
|
|
|
|
|
|
|
|
|
| ||
Fan Diameter Inches |
| 18 | 18 | 18 |
| 18 |
| 18 | 22 | 22 | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Rated HP | 1/12 | 1/12 | 1/12 |
| 1/4 |
| 1/4 | 1/4 | 1/4 |
Fan Motor |
|
|
|
|
|
|
|
|
|
|
| |
| Nominal RPM | 1,100 | 1,100 | 1,100 |
| 1,100 |
| 1,100 | 850 | 850 | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Nominal CFM | 1,850 | 1,850 | 1,900 |
| 2,750 |
| 2,750 | 3,250 | 3,300 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Face Area Sq. Ft. | 8.00 | 8.00 | 9.15 |
| 9.15 |
| 12.58 | 15.72 | 15.72 | |
Coil |
|
|
|
|
|
|
|
|
|
|
| |
| Rows Deep | 1 | 1 | 1 |
| 1 |
| 1 | 1 | 1 | ||
|
|
|
|
|
|
|
|
|
|
|
| |
|
| Fin / Inches | 14 | 14 | 18 |
| 18 |
| 18 | 18 | 22 | |
|
|
|
|
|
|
|
|
|
|
|
| |
Liquid Line | OD |
| 3/8 | 3/8 | 3/8 |
| 3/8 |
| 3/8 | 3/8 | 3/8 | |
|
|
|
|
|
|
|
|
|
|
| ||
Vapor Line OD |
| 5/8 | 5/8 | 3/4 |
| 3/4 |
| 3/4 | 7/8 | 7/8 | ||
|
|
|
|
|
|
|
|
|
| |||
Unit Charge (Lbs. - Oz.) 4 | 3 - 6 | 3 - 11 | 3 - 14 |
| 3 - 15 |
| 5 - 4 | 7 - 5 | 6 - 2 | |||
Charge Per Foot, Oz. 4 | 0.66 | 0.66 | 0.68 |
| 0.68 |
| 0.68 | 0.70 | .070 | |||
Operating Weight Lbs. | 118 | 123 | 135 |
| 137 |
| 161 | 176 | 188 | |||
|
|
|
|
|
|
|
|
|
|
|
|
|
Physical and Electrical Data - 3 Phase
MODEL |
|
|
| H1RA | H1RA | H1RA | H1RA | H1RA | H1RA | H1RA | H1RA | H1RA | H1RA | H1RA | H1RA |
|
|
| 036S25 | 042S25 | 048S25 | 060S25 | 076S25 | 090S25 | 036S25 | 042S46 | 048S46 | 060S46 | 076S46 | 090S46 | |
|
|
|
| ||||||||||||
Unit Supply Voltage |
|
|
| 208/230 – 3 – 60 |
|
|
|
| 460 - | 3 - 60 |
|
| |||
Normal Voltage Range 1 |
|
| 187 to 252 |
|
|
|
| 432 to 504 |
|
| |||||
Minimum Circuit Ampacity | 15.0 | 17.4 | 17.3 | 21.3 | 25.8 | 37.7 | 8.0 | 8.4 | 8.3 | 10.8 | 13.0 | 18.1 | |||
|
|
|
|
|
|
|
|
|
|
|
|
| |||
Max. Overcurrent Device Amps 2 | 25 | 30 | 30 | 35 | 40 | 50 | 15 | 15 | 15 | 15 | 20 | 25 | |||
Compressor Type 3 |
| Recip | Recip | Recip | ScrollB | ScrollB | Dual | Recip | Recip | Recip | ScrollB | ScrollB | Dual | ||
Compressor Amps |
| Rated Load | 10.9 | 12.8 | 11.7 | 16.0 | 18.9 | 29.4 | 5.8 | 6.1 | 6.1 | 8.0 | 9.5 | 14.0 | |
| Locked Rotor | 78 | 78 | 78 | 125 | 146 | 260 | 40 | 39 | 39 | 67 | 73 | 128 | ||
|
|
| |||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Crankcase Heater |
|
| No | No | No | No | No | Yes | No | No | No | No | No | Yes | |
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
Fan Motor Amps |
| Rated Load | 1.4 | 1.4 | 1.3 | 1.3 | 2.2 | 4.6 | .8 | .8 | .7 | .8 | 1.2 | 2.3 | |
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
Fan Diameter Inches |
| 18 | 18 | 22 | 22 | 24 | 24 | 18 | 18 | 22 | 22 | 24 | 24 | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Rated HP | 1/4 | 1/4 | 1/4 | 1/4 | 1/3 | 3/4 | 1/4 | 1/4 | 1/5 | 1/4 | 1/3 | 3/4 |
Fan Motor |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
| Nominal RPM | 1,100 | 1,100 | 850 | 850 | 1100 | 1100 | 1,100 | 1,100 | 850 | 850 | 1100 | 1100 | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Nominal CFM | 2,750 | 2,750 | 3,250 | 3,450 | 4000 | 5000 | 2,750 | 2,750 | 3,250 | 3,450 | 4000 | 5000 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
| Face Area Sq. Ft. | 9.15 | 12.58 | 15.72 | 23.58 | 18.0 | 22.5 | 9.15 | 12.58 | 15.72 | 23.58 | 18.0 | 22.5 | ||
Coil |
|
|
|
|
|
|
|
|
|
|
|
|
| ||
Rows Deep | 1 | 1 | 1 | 1 | 2 | 2 | 1 | 1 | 1 | 1 | 2 | 2 | |||
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
| Fin / Inches | 18 | 18 | 18 | 18 | 16 | 16 | 18 | 18 | 18 | 18 | 16 | 16 | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Liquid Line OD |
| 3/8 | 3/8 | 3/8 | 3/8 | 1/2 | 1/2 | 3/8 | 3/8 | 3/8 | 3/8 | 1/2 | 1/2 | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
Vapor Line OD |
| 3/4 | 3/4 | 7/8 | 7/8 | 3/4 | 3/4 | 7/8 | 7/8 | ||||||
|
|
|
|
|
|
|
|
|
|
|
|
| |||
Unit Charge (Lbs. - Oz.) 4 | 3 - 15 | 5 - 4 | 7 - 5 | 9 - 7 | 3 - 15 | 5 - 4 | 7 - 5 | 9 - 7 | |||||||
Charge Per Foot, Oz.4 | .68 | .68 | .70 | .70 | 1.26 | 1.26 | .68 | .68 | .70 | .70 | 1.26 | 1.26 | |||
Operating Weight Lbs. | 170 | 176 | 206 | 228 | 219 | 368 | 170 | 176 | 206 | 228 | 219 | 368 | |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1.Rated in accordance with ARI Standard 110, utilization range “A”.
2.Dual element fuses or HACR circuit breaker.
3.All scrolls listed with a superscript “B” are Bristol scrolls. All scrolls listed with a superscript “C” are Copeland scrolls.
4.The Unit Charge is correct for the outdoor unit, matched indoor coil and 15 feet of refrigerant tubing. For tubing lengths other than 15 feet, add or sub- tract the amount of refrigerant, using the difference in length multiplied by the per foot valve.
2 | Unitary Products Group |