Toshiba A09-01P manual Main setting item, Function Code List

Page 24

Quick Reference Guide - Page 24

Main setting item (cont.)

(11)Setting 2-Way Valve (for Cooling) Operation (function code 3C)

When using both cooling and heating operations and there is an indoor unit only for heating (such as floor heating), install the 2-way valve and set this function code.

(12)Setting 3-Way Valve Operation (function code 54)

This setting is not necessary for normal installation. Make this setting to invert the logic circuit in case ports A and B of the 3-way valve are wrongly attached and it cannot be rectified on site.

(13)Mixing valve types and setting

Set the time period from full close to full open of the 2-zone control mixing valve. Set a value that is 1/10 of the actual time.

(14)Setting Heating/Hot Water Switching when Boiler Is Used (function code 3E)

• When boiler is used, make this setting to operate the Hydro Unit by the instruction from the boiler.

(15)Setting Heat Pump Operating Time for Hot Water Supply Operation

Set the time period from the start of heat pump run to the start of heater energization at the beginning of hot water supply operation. If a long period is set, it takes long time for heating water.

(16)Setting Cooling ON/OFF

• Set this function when performing cooling operation.

(17)Remote controller time indication

24-hour or 12-hour notation is selected for the timer.

(18)Setting Nighttimes Quiet Operation

Issue an instruction for low-noise mode operation to the outdoor unit. Enabling/disabling of this function, start time, and end time can be set.

(19)Setting Alarm Tone

• The remote controller alarm tone can be set.

Function Code List

Function Code

 

 

 

 

Number

 

 

 

Function

Hydro

Remote

Range

Default

 

Unit

Controller

 

 

 

 

 

Zone 1 - heating upper temperature limit °C

1A

-

37 ~55

55

 

Zone 1 - heating lower temperature limit °C

1B

-

20 ~ 37

20

Setting

Zone 2 - heating upper limit temperature °C

1C

-

37 ~55

55

Zone 2 - heating lower limit temperature °C

1D

-

20 ~ 37

20

Temperature

Cooling mode - upper temperature limit °C

18

-

18 ~ 30

25

Range

Cooling mode - lower temperature limit °C

19

-

10 ~ 18

10

 

 

Hot water - upper temperature limit °C

1E

-

50 ~ 75

75

 

Hot water - lower temperature limit °C

1F

-

40 ~ 60

40

Hot Water

Heat pump start temperature °C

20

-

20 ~ 45

38

Operation

Heat pump stop temperature °C

21

-

40 ~ 50

45

Hot Water

Temperature compensation - start outside air

24

-

-20 ~ 10

0

Temperature

temperature °C

 

 

 

 

Compensation

 

 

 

 

 

Compensation temperature °C

25

-

0 ~ 15

3

Hot Water Boost

Operation time x 10 min

08

-

3 ~ 18

6

Setting temperature °C

09

-

40 ~ 75

75

 

 

Setting temperature °C

0A

-

70 ~ 75

75

Anti - Bacteria

Start cycle (day)

-

0D

0 ~ 10

7

Start time (hour)

-

0C

0 ~ 23

22

 

 

Operation time (min)

0B

-

0 ~ 60

30

 

Hot water and heating switching

22

-

-20 ~ 20

0

Priority Mode

temperature °C

 

 

 

 

Boiler and heat pump switching

23

-

-20 ~ 20

-10

 

 

temperature °C

 

 

 

 

 

Image 24
Contents AIR to Water Heat Pump Estia System Estia Hot Water Cylinder EUEstia Hot Water Cylinder UK Options required for each function 14 kWPurpose Toshiba Supply Part name Model code Procure locallyInstallation Examples Space Cooling and Space Heating with Domestic Hot WaterZone Space Heating with Domestic Hot Water Hydro Unit Exploded View Refrigeration and Water Cycle Diagrams Hydro Unit Refrigerant PipingRefrigerant Pipe Lengths and Height Minimum Pipe LengthOutdoor Unit HWS-802H-E HWS-1102H-E, 1402H-E Water Piping Water ConnectionsWater Piping Limitations Piping to hot water tank optionExample ActionPump operation / configuration Water chargingWater quality Piping insulationElectrical Connections Box layout Terminal Block ConnectionsPower Lines Schematic Control Lines Schematic Electrical supply / cable specifications Wiring specifications power lineWiring specification control line Control parts specificationsInput line specifications Earthing arrangementsElectrical connection to hydro unit Outdoor unit to hydro unit electrical connectionElectrical connection for external booster heater Electrical connection for external additional pump P2Required Valve Specification Way valve for cooling connectionWay valve diverter connection Diverter Valve Description SW13-1Required Actuator Specification Electrical Connection Hot Water Cylinder temperature SensorWay mixing valve connection Hot water cylinder connection optionalSetting DIP Switches on the Board in the Hydro Unit Hydro Unit Remote Control Buttons and FunctionsDisplay Explanation ZONE1, ZONE2Display Description Display HOT Water DescriptionFunction Code Access Setting procedure for Hydro Unit function codeSetting procedure for Remote Controller function code Display ExplanationMain setting items Main setting item Function Code ListFunction Settings by Purpose Settings when hot water supply function is not usedSetting for cooling Settings for hot water supplySettings for 2-zone temperature control Test RunSensor Temperature Monitoring Function Fault SymptomsSymptom Possible cause Code No Location IndicationAlarm Indications Outdoor Alarm indication Alarm IndicationsAlarm Main failure part Description Indication Outdoor Fault Diagnosis Check of the current abnormal status

A09-01P specifications

The Toshiba A09-01P is a cutting-edge air conditioning unit that has garnered attention for its sleek design and advanced technology. This model is well-suited for both residential and commercial spaces, providing efficient cooling and heating, which makes it a versatile choice for year-round comfort.

One of the standout features of the A09-01P is its energy efficiency, marked by its high SEER (Seasonal Energy Efficiency Ratio) rating. This means that it uses less electricity compared to traditional models, which is beneficial not only for the environment but also for reducing utility bills. The unit employs inverter technology, which allows the compressor to adjust its output based on the cooling demand. This results in more consistent temperatures and minimizes energy waste.

The Toshiba A09-01P is also equipped with a multi-stage air purification system. This advanced filtration process includes a pre-filter, a HEPA filter, and an activated carbon filter. The pre-filter captures larger particles, while the HEPA filter can remove up to 99.97% of microscopic allergens and pollutants. The activated carbon filter helps to eliminate odors, ensuring that the air quality remains fresh and clean.

In terms of user convenience, the device comes with a smart remote control that allows users to adjust settings without getting up. It features programmable timers and multiple modes, including auto, cool, and dry modes, aiding users in customizing their experience according to specific needs.

The unit's compact design allows for installation in tighter spaces, making it ideal for urban environments where real estate is at a premium. The quiet operation of the A09-01P is another significant advantage, ensuring that it runs unobtrusively in the background, making it perfect for bedrooms or offices.

Furthermore, Toshiba has integrated smart technology into the A09-01P, allowing it to be controlled via smartphone apps. This feature adds an extra layer of convenience, enabling users to manage their indoor climate even when they are away from home.

Overall, the Toshiba A09-01P stands out in the air conditioning market due to its combination of energy efficiency, advanced filtration, and user-friendly features, making it a wise investment for any space requiring climate control.