Electrical supply / cable specifications

Wiring specifications (power line)

Description

 

POWER

Maximum

Installation

 

SUPPLY

current

fuse rating

 

 

 

 

 

 

 

 

14 kW

230 V ~ 50 Hz

22.8 A

25 A

Outdoor unit power

11 kW

230 V ~ 50 Hz

22.8 A

25 A

 

8 kW

230 V ~ 50 Hz

20.8 A

25 A

Outdoor-Hydro

 

 

Hydro inlet heater

3 kW

230 V ~ 50 Hz

13 A

16 A

6 kW

400 V 3N ~ 50 Hz

15 A (13 A x 2P)

25 A

power

9 kW

400 V 3N ~ 50 Hz

23 A (13 A x 3P)

25 A

 

Hydro cylinder heater power

230 V ~ 50 Hz

12 A

16 A

Hydro - cylinder

 

12 A

Cable size

Connection

destination

 

 

 

 

 

 

 

2.5 mm² or more

 

 

 

 

 

2.5 mm² or more

L

,

N

 

 

2.5 mm² or more

 

 

 

 

 

1.5 mm² or more

1

,

2

,

3

1.5 mm² or more

L

,

N

 

(TB02)

2.5 mm² or more

L1

,

L2

,

L3

2.5 mm² or more

N

(TB02)

1.5 mm² or more

L

,

N

(TB03)

1.5 mm² or more

1

,

2

(TB03)

Wiring specification (control line)

Description

Line spec

Maximum

current

 

 

3-way valve control

2 line or 3 line

100 mA

 

 

 

Mixing valve control

3 line

100 mA

 

 

 

2-zone thermo sensor

2 line

100 mA

Cylinder thermo sensor

2+GND (shield

100 mA

wire)

 

 

Second remote controller

2 line

50 mA

Maximum length

12 m

12 m

5m

5m

50m

Cable Size

0.75mm² or more

0.75mm² or more

0.75mm² or more

0.75mm² or more

0.75mm² or more

Connection destination

7

,

8

,

9

(TB05)

 

1

,

2

,

3

or

,

 

,

 

2

3

4

(TB04)

C , D (TB06)

A , B (TB06)

1 , 2 (TB07)

Control parts specifications

Description

Power

Maximum

Type

 

 

current

 

Motorized 3-way valve (for

AC 230 V

100 mA

Spring return type Note: 3-wire SPST and SPDT type can be

hot water)

used by changing the function code.

 

 

 

 

 

 

Motorized 2-way valve (for

AC 230 V

100 mA

spring return type (normally open )

cooling)

 

 

 

Motorized mixing valve type

AC 230 V

100 mA

60 sec 90º. SPDT type Note: SPST and 20 to 240 sec type

1 (for 2-zone)

 

 

can be used by changing the function code.

Output line specifications

Description

Output

Maximum

Max

Maximum

current

voltage

length

 

 

External pump No. 1

AC230V

1 A

12 m

 

 

 

 

 

External booster heater

AC230V

1 A

12 m

 

 

 

 

 

Boiler control

Non-

0.5 A

AC230 V

12 m

voltage

 

 

 

1 A

DC24 V

12 m

 

contacts

ALARM Output

Non-

0.5 A

AC230 V

12 m

voltage

 

 

 

1 A

DC24 V

12 m

 

contacts

Operation Output

Non-

0.5 A

AC230 V

12 m

voltage

 

 

 

1 A

DC24 V

12 m

 

contacts

Defrost Output

Non-

0.5 A

AC230 V

12 m

voltage

 

 

 

1 A

DC24 V

12 m

 

contacts

 

 

 

 

Interlocked with the Hydro Unit pump

Output as required when outdoor air temperature is -20°C or less

Output as required when outdoor air temperature is -10°C or less

Image 14
Contents AIR to Water Heat Pump Estia Hot Water Cylinder UK Estia SystemEstia Hot Water Cylinder EU Purpose Toshiba Supply Part name Model code Options required for each function14 kW Procure locallyInstallation Examples Space Cooling and Space Heating with Domestic Hot WaterZone Space Heating with Domestic Hot Water Hydro Unit Exploded View Refrigerant Pipe Lengths and Height Refrigeration and Water Cycle Diagrams Hydro UnitRefrigerant Piping Minimum Pipe LengthOutdoor Unit HWS-802H-E HWS-1102H-E, 1402H-E Water Piping Limitations Water PipingWater Connections Piping to hot water tank optionExample ActionWater quality Pump operation / configurationWater charging Piping insulationElectrical Connections Box layout Terminal Block ConnectionsPower Lines Schematic Control Lines Schematic Wiring specification control line Electrical supply / cable specificationsWiring specifications power line Control parts specificationsElectrical connection to hydro unit Input line specificationsEarthing arrangements Outdoor unit to hydro unit electrical connectionElectrical connection for external booster heater Electrical connection for external additional pump P2Way valve diverter connection Required Valve SpecificationWay valve for cooling connection Diverter Valve Description SW13-1Way mixing valve connection Required Actuator SpecificationElectrical Connection Hot Water Cylinder temperature Sensor Hot water cylinder connection optionalSetting DIP Switches on the Board in the Hydro Unit Hydro Unit Remote Control Buttons and FunctionsDisplay Description Display ExplanationZONE1, ZONE2 Display HOT Water DescriptionSetting procedure for Remote Controller function code Function Code AccessSetting procedure for Hydro Unit function code Display ExplanationMain setting items Main setting item Function Code ListFunction Setting for cooling Settings by PurposeSettings when hot water supply function is not used Settings for hot water supplySettings for 2-zone temperature control Test RunSymptom Possible cause Sensor Temperature Monitoring FunctionFault Symptoms Code No Location IndicationAlarm Indications Alarm Main failure part Description Indication Outdoor Alarm indicationAlarm Indications Outdoor Fault Diagnosis Check of the current abnormal status

A09-01P specifications

The Toshiba A09-01P is a cutting-edge air conditioning unit that has garnered attention for its sleek design and advanced technology. This model is well-suited for both residential and commercial spaces, providing efficient cooling and heating, which makes it a versatile choice for year-round comfort.

One of the standout features of the A09-01P is its energy efficiency, marked by its high SEER (Seasonal Energy Efficiency Ratio) rating. This means that it uses less electricity compared to traditional models, which is beneficial not only for the environment but also for reducing utility bills. The unit employs inverter technology, which allows the compressor to adjust its output based on the cooling demand. This results in more consistent temperatures and minimizes energy waste.

The Toshiba A09-01P is also equipped with a multi-stage air purification system. This advanced filtration process includes a pre-filter, a HEPA filter, and an activated carbon filter. The pre-filter captures larger particles, while the HEPA filter can remove up to 99.97% of microscopic allergens and pollutants. The activated carbon filter helps to eliminate odors, ensuring that the air quality remains fresh and clean.

In terms of user convenience, the device comes with a smart remote control that allows users to adjust settings without getting up. It features programmable timers and multiple modes, including auto, cool, and dry modes, aiding users in customizing their experience according to specific needs.

The unit's compact design allows for installation in tighter spaces, making it ideal for urban environments where real estate is at a premium. The quiet operation of the A09-01P is another significant advantage, ensuring that it runs unobtrusively in the background, making it perfect for bedrooms or offices.

Furthermore, Toshiba has integrated smart technology into the A09-01P, allowing it to be controlled via smartphone apps. This feature adds an extra layer of convenience, enabling users to manage their indoor climate even when they are away from home.

Overall, the Toshiba A09-01P stands out in the air conditioning market due to its combination of energy efficiency, advanced filtration, and user-friendly features, making it a wise investment for any space requiring climate control.