Toshiba A09-01P manual Alarm Indications

Page 29

Quick Reference Guide - Page 29

Alarm Indications

Alarm

Alarm description and generation/reset conditions

indication

 

 

Regular communication error between hydro unit and remote controller (system controller) If there is no

E03

regular communication from the remote controller for three minutes, the hydro unit regards it as no

remote controller. If there is no communication from both sides, alarm E03 occurs. Auto-reset: When

 

 

successful regular communication is made

 

Regular communication error between hydro unit and outdoor unit When serial signal from the outdoor

 

unit cannot be received though normal serial signal is sent to the outdoor unit 1) When serial signal

E04

cannot be received continuously for 60 seconds (S code communication) 2) Communication is still not

successful for 80 seconds through three retries if serial signal cannot be received for 20 seconds after

 

new communication (f code) starts When the remote controller starts operation, serial transmission

 

starts with the new communication format. Auto-reset: When successful regular communication is

 

made

 

Condensing temperature TC sensor defect

F03

If short-circuit or open-circuit state continues for two seconds, an alarm occurs.

 

Auto-reset: When normal value is confirmed

 

Hydraulic heat exchanger inlet temperature TWI sensor defect

F10

If short-circuit or open-circuit state continues for two seconds, an alarm occurs.

 

Auto-reset: When normal value is confirmed

 

Hydraulic heat exchanger outlet temperature TWO sensor defect

F11

If short-circuit or open-circuit state continues for two seconds, an alarm occurs.

 

Auto-reset: When normal value is confirmed

 

Hot water cylinder temperature TTW sensor defect

F14

If short-circuit or open-circuit state continues for two seconds, an alarm occurs.

 

Auto-reset: When normal value is confirmed

 

Floor inlet temperature TFI sensor defect

F17

If short-circuit or open-circuit state continues for two seconds, an alarm occurs.

 

Auto-reset: When normal value is confirmed

 

Internal heater outlet temperature TWO sensor defect

F18

If short-circuit or open-circuit state continues for two seconds, an alarm occurs.

 

Auto-reset: When normal value is confirmed

 

Low-pressure sensor defect

F23

If open-circuit state continues for two seconds, an alarm occurs.

 

Auto-reset: When normal value is confirmed

 

Hydraulic heat exchanger EEPROM defect

F29

One mismatch is detected if there is no verification ACK after data write to the EEPROM Reset

condition: This alarm is inhibited while the unit is not working.

 

 

(When EEPROM1K is mounted, this alarm cannot be reset.)

F20

Floor inlet temperature TFI sensor disconnection or wrong installation (This alarm is reset by stopping

operation and is checked again.)

 

F30

Onboard expansion IC defect This alarm is not reset automatically.

 

 

 

Group line in an hydro unit

 

This alarm is checked during initial communication immediately after power-on. This alarm occurs

L07

immediately after operation start.

 

This alarm is not reset automatically. (This alarm is inhibited while the unit is not working, but occurs

 

again after the unit operates.)

L09

Hydro unit capacity has not been set.

This alarm is checked immediately after power-on. This alarm is not reset automatically. (This alarm is

 

inhibited while the unit is not working, but occurs again after the unit operates.)

A01

Pump defect or abnormal flow rate This alarm is not reset automatically.

 

 

A02

Excessive water temperature increase by the heating heater Auto-reset:

 

 

A03

Excessive water temperature increase in the hot water cylinder

 

 

A04

Freezing is detected. Auto-reset:

 

 

A07

High-pressure switch malfunction This alarm is not reset automatically.

 

 

A08

Low-pressure sensor malfunction This alarm is not reset automatically.

 

 

Image 29
Contents AIR to Water Heat Pump Estia Hot Water Cylinder UK Estia SystemEstia Hot Water Cylinder EU 14 kW Options required for each functionPurpose Toshiba Supply Part name Model code Procure locallySpace Cooling and Space Heating with Domestic Hot Water Installation ExamplesZone Space Heating with Domestic Hot Water Hydro Unit Exploded View Refrigerant Piping Refrigeration and Water Cycle Diagrams Hydro UnitRefrigerant Pipe Lengths and Height Minimum Pipe LengthOutdoor Unit HWS-802H-E HWS-1102H-E, 1402H-E Water Connections Water PipingWater Piping Limitations Piping to hot water tank optionAction ExampleWater charging Pump operation / configurationWater quality Piping insulationBox layout Terminal Block Connections Electrical ConnectionsPower Lines Schematic Control Lines Schematic Wiring specifications power line Electrical supply / cable specificationsWiring specification control line Control parts specificationsEarthing arrangements Input line specificationsElectrical connection to hydro unit Outdoor unit to hydro unit electrical connectionElectrical connection for external additional pump P2 Electrical connection for external booster heaterWay valve for cooling connection Required Valve SpecificationWay valve diverter connection Diverter Valve Description SW13-1Electrical Connection Hot Water Cylinder temperature Sensor Required Actuator SpecificationWay mixing valve connection Hot water cylinder connection optionalSetting DIP Switches on the Board in the Hydro Unit Buttons and Functions Hydro Unit Remote ControlZONE1, ZONE2 Display ExplanationDisplay Description Display HOT Water DescriptionSetting procedure for Hydro Unit function code Function Code AccessSetting procedure for Remote Controller function code Display ExplanationMain setting items Function Code List Main setting itemFunction Settings when hot water supply function is not used Settings by PurposeSetting for cooling Settings for hot water supplyTest Run Settings for 2-zone temperature controlFault Symptoms Sensor Temperature Monitoring FunctionSymptom Possible cause Code No Location IndicationAlarm Indications Alarm Main failure part Description Indication Outdoor Alarm indicationAlarm Indications Check of the current abnormal status Outdoor Fault Diagnosis

A09-01P specifications

The Toshiba A09-01P is a cutting-edge air conditioning unit that has garnered attention for its sleek design and advanced technology. This model is well-suited for both residential and commercial spaces, providing efficient cooling and heating, which makes it a versatile choice for year-round comfort.

One of the standout features of the A09-01P is its energy efficiency, marked by its high SEER (Seasonal Energy Efficiency Ratio) rating. This means that it uses less electricity compared to traditional models, which is beneficial not only for the environment but also for reducing utility bills. The unit employs inverter technology, which allows the compressor to adjust its output based on the cooling demand. This results in more consistent temperatures and minimizes energy waste.

The Toshiba A09-01P is also equipped with a multi-stage air purification system. This advanced filtration process includes a pre-filter, a HEPA filter, and an activated carbon filter. The pre-filter captures larger particles, while the HEPA filter can remove up to 99.97% of microscopic allergens and pollutants. The activated carbon filter helps to eliminate odors, ensuring that the air quality remains fresh and clean.

In terms of user convenience, the device comes with a smart remote control that allows users to adjust settings without getting up. It features programmable timers and multiple modes, including auto, cool, and dry modes, aiding users in customizing their experience according to specific needs.

The unit's compact design allows for installation in tighter spaces, making it ideal for urban environments where real estate is at a premium. The quiet operation of the A09-01P is another significant advantage, ensuring that it runs unobtrusively in the background, making it perfect for bedrooms or offices.

Furthermore, Toshiba has integrated smart technology into the A09-01P, allowing it to be controlled via smartphone apps. This feature adds an extra layer of convenience, enabling users to manage their indoor climate even when they are away from home.

Overall, the Toshiba A09-01P stands out in the air conditioning market due to its combination of energy efficiency, advanced filtration, and user-friendly features, making it a wise investment for any space requiring climate control.