Toshiba A09-01P Refrigerant Piping, Refrigerant Pipe Lengths and Height, Minimum Pipe Length

Page 7

Quick Reference Guide - Page 7

Refrigerant Piping

Refrigerant Pipe Lengths and Height

The length and height of the refrigeration pipe must be within the following values.

Minimum Pipe Length

HWS-802H-E : 5 m

HWS-1102H-E : 3 m

HWS-1402H-E : 3 m

Maximum Pipe Length and Height

H:Max. ±30 m (above or below)

L:Max. 30 m

Note

The maximum pipe length cannot be increased using additional refrigerant.

Refrigeration and Water Cycle Diagrams Hydro Unit

 

Pressure

Air vent valve

relief

valve

Expansion vessel

 

Pressure

Gauge

Refrigerant pipe at gas side (Outer ø15.88)

Thermal

Protector

Hi_P_Switch

TWO

Sensor

THO Sensor

Pump

Water Out (1 1/4")

P_Sensor

Backup heater

Refrigerant pipe at liquid side (Outer ø9.52)

TC Sensor

Flow_Switch

TWI

Sensor

Water IN (1 1/4")

Water Heat exchanger

Image 7
Contents AIR to Water Heat Pump Estia Hot Water Cylinder EU Estia SystemEstia Hot Water Cylinder UK Procure locally Options required for each function14 kW Purpose Toshiba Supply Part name Model codeSpace Cooling and Space Heating with Domestic Hot Water Installation ExamplesZone Space Heating with Domestic Hot Water Hydro Unit Exploded View Minimum Pipe Length Refrigeration and Water Cycle Diagrams Hydro UnitRefrigerant Piping Refrigerant Pipe Lengths and HeightOutdoor Unit HWS-802H-E HWS-1102H-E, 1402H-E Piping to hot water tank option Water PipingWater Connections Water Piping LimitationsAction ExamplePiping insulation Pump operation / configurationWater charging Water qualityBox layout Terminal Block Connections Electrical ConnectionsPower Lines Schematic Control Lines Schematic Control parts specifications Electrical supply / cable specificationsWiring specifications power line Wiring specification control lineOutdoor unit to hydro unit electrical connection Input line specificationsEarthing arrangements Electrical connection to hydro unitElectrical connection for external additional pump P2 Electrical connection for external booster heaterDiverter Valve Description SW13-1 Required Valve SpecificationWay valve for cooling connection Way valve diverter connectionHot water cylinder connection optional Required Actuator SpecificationElectrical Connection Hot Water Cylinder temperature Sensor Way mixing valve connectionSetting DIP Switches on the Board in the Hydro Unit Buttons and Functions Hydro Unit Remote ControlDisplay HOT Water Description Display ExplanationZONE1, ZONE2 Display DescriptionDisplay Explanation Function Code AccessSetting procedure for Hydro Unit function code Setting procedure for Remote Controller function codeMain setting items Function Code List Main setting itemFunction Settings for hot water supply Settings by PurposeSettings when hot water supply function is not used Setting for coolingTest Run Settings for 2-zone temperature controlCode No Location Indication Sensor Temperature Monitoring FunctionFault Symptoms Symptom Possible causeAlarm Indications Alarm Indications Outdoor Alarm indicationAlarm Main failure part Description Indication Check of the current abnormal status Outdoor Fault Diagnosis

A09-01P specifications

The Toshiba A09-01P is a cutting-edge air conditioning unit that has garnered attention for its sleek design and advanced technology. This model is well-suited for both residential and commercial spaces, providing efficient cooling and heating, which makes it a versatile choice for year-round comfort.

One of the standout features of the A09-01P is its energy efficiency, marked by its high SEER (Seasonal Energy Efficiency Ratio) rating. This means that it uses less electricity compared to traditional models, which is beneficial not only for the environment but also for reducing utility bills. The unit employs inverter technology, which allows the compressor to adjust its output based on the cooling demand. This results in more consistent temperatures and minimizes energy waste.

The Toshiba A09-01P is also equipped with a multi-stage air purification system. This advanced filtration process includes a pre-filter, a HEPA filter, and an activated carbon filter. The pre-filter captures larger particles, while the HEPA filter can remove up to 99.97% of microscopic allergens and pollutants. The activated carbon filter helps to eliminate odors, ensuring that the air quality remains fresh and clean.

In terms of user convenience, the device comes with a smart remote control that allows users to adjust settings without getting up. It features programmable timers and multiple modes, including auto, cool, and dry modes, aiding users in customizing their experience according to specific needs.

The unit's compact design allows for installation in tighter spaces, making it ideal for urban environments where real estate is at a premium. The quiet operation of the A09-01P is another significant advantage, ensuring that it runs unobtrusively in the background, making it perfect for bedrooms or offices.

Furthermore, Toshiba has integrated smart technology into the A09-01P, allowing it to be controlled via smartphone apps. This feature adds an extra layer of convenience, enabling users to manage their indoor climate even when they are away from home.

Overall, the Toshiba A09-01P stands out in the air conditioning market due to its combination of energy efficiency, advanced filtration, and user-friendly features, making it a wise investment for any space requiring climate control.