Toshiba A09-01P manual Settings by Purpose, Settings when hot water supply function is not used

Page 26

Function Code List (cont.)

 

 

 

Function

 

 

 

 

Remote Controller

24 hour or 12 hour remote control display.

 

 

Indication

0=24hr; 1=12hr

 

 

 

 

 

Outdoor Night Time

0

= Function invalid

 

1

= Function valid

 

Low Noise

 

 

Start time (hour)

 

Operation

 

End time (hour)

 

 

 

 

 

 

Alarm Tone

Tone Switching 0: OFF, 1: ON

 

 

 

 

 

Pump P2 remote

0

= Not Shown;

 

controller Display

1

= Shown

 

 

 

 

 

Outdoor Forced

0

= Forced Defrost OFF;

 

Defrost Mode

1

= Forced Defrost ON

 

 

 

 

 

Optional ON/OFF

0

= a contact “ON” = Forced stop

 

1

= b contact “OFF” = Forced stop

 

Command

2

= ON/OFF = Start / Stop

 

 

3= HA Specification

 

Outdoor Night Time

0

= Symbol displayed when mode is valid

 

(controlled by Function Code Only);

 

Mode Button

1

= Symbol displayed when mode is activated

 

 

(controlled by Function Code and Button)

 

Control Logic for

0

= Cooling thermo on – contact open;

 

Room Thermostat

1

= Cooling thermo on – contact close

Quick Reference Guide - Page 26

Function Code Number

 

 

 

 

 

 

Hydro Unit

Remote

Range

Default

Controller

 

 

 

 

 

 

 

-

05

0 ~ 1

0

 

 

 

 

-

09

0 ~ 1

0

 

 

 

 

-

0A

0 ~ 23

22

-

0B

0 ~ 23

06

 

 

 

 

 

11

0 ~ 1

1

 

 

 

 

42

-

0 ~ 1

0

 

 

 

 

46

-

0 ~ 1

0

 

 

 

 

52

-

0 ~ 3

0

 

 

 

 

56

-

0 ~ 1

0

 

 

 

 

57

-

0 ~ 1

0

 

 

 

 

Settings by Purpose

Settings when hot water supply function is not used

• When the hot water supply function is not used, set DIP SW12-1 on the Hydro Unit board to ON.

Setting for cooling

For Space Conditioning Units that do not perform cooling (radiators and Under floor heating, etc.), procure a motorized 2-way valve (for cooling) locally and attach it to the water pipe that is not used for cooling. Connect the valve cables (as described in Electrical section).

Press long the TEST + SET + SELECT switches on the remote controller to change the Hydro Unit function code, and change address 02 to 0, and then press the SET button to enable the function.

Press the TEST button to exit the setting mode.

• Stick the optional insulator for cooling to the bottom of the Hydro Unit.

Settings for hot water supply

Prepare the optional hot water cylinder.

Procure a motorized 3-way (diverter) valve locally and perform piping. Connect the valve cables (as described in Electrical section).

Set DIP SW12-1 on the Hydro Unit board to OFF.

Connect the power supply unit for the hot water cylinder heater to terminals TB03 L and N of the Hydro Unit.

Connect cables between the Hydro Unit and the hot water cylinder as follows:

Hydro Unit terminals

TB03

(1), (2), and earth —

Hot water cylinder (1), (2), and earth

 

TB06

A, B, and earth —

Hot water cylinder A, B, and earth

Image 26
Contents AIR to Water Heat Pump Estia Hot Water Cylinder UK Estia SystemEstia Hot Water Cylinder EU Purpose Toshiba Supply Part name Model code Options required for each function14 kW Procure locallyInstallation Examples Space Cooling and Space Heating with Domestic Hot WaterZone Space Heating with Domestic Hot Water Hydro Unit Exploded View Refrigerant Pipe Lengths and Height Refrigeration and Water Cycle Diagrams Hydro UnitRefrigerant Piping Minimum Pipe LengthOutdoor Unit HWS-802H-E HWS-1102H-E, 1402H-E Water Piping Limitations Water PipingWater Connections Piping to hot water tank optionExample ActionWater quality Pump operation / configurationWater charging Piping insulationElectrical Connections Box layout Terminal Block ConnectionsPower Lines Schematic Control Lines Schematic Wiring specification control line Electrical supply / cable specificationsWiring specifications power line Control parts specificationsElectrical connection to hydro unit Input line specificationsEarthing arrangements Outdoor unit to hydro unit electrical connectionElectrical connection for external booster heater Electrical connection for external additional pump P2Way valve diverter connection Required Valve SpecificationWay valve for cooling connection Diverter Valve Description SW13-1Way mixing valve connection Required Actuator SpecificationElectrical Connection Hot Water Cylinder temperature Sensor Hot water cylinder connection optionalSetting DIP Switches on the Board in the Hydro Unit Hydro Unit Remote Control Buttons and FunctionsDisplay Description Display ExplanationZONE1, ZONE2 Display HOT Water DescriptionSetting procedure for Remote Controller function code Function Code AccessSetting procedure for Hydro Unit function code Display ExplanationMain setting items Main setting item Function Code ListFunction Setting for cooling Settings by PurposeSettings when hot water supply function is not used Settings for hot water supplySettings for 2-zone temperature control Test RunSymptom Possible cause Sensor Temperature Monitoring FunctionFault Symptoms Code No Location IndicationAlarm Indications Alarm Main failure part Description Indication Outdoor Alarm indicationAlarm Indications Outdoor Fault Diagnosis Check of the current abnormal status

A09-01P specifications

The Toshiba A09-01P is a cutting-edge air conditioning unit that has garnered attention for its sleek design and advanced technology. This model is well-suited for both residential and commercial spaces, providing efficient cooling and heating, which makes it a versatile choice for year-round comfort.

One of the standout features of the A09-01P is its energy efficiency, marked by its high SEER (Seasonal Energy Efficiency Ratio) rating. This means that it uses less electricity compared to traditional models, which is beneficial not only for the environment but also for reducing utility bills. The unit employs inverter technology, which allows the compressor to adjust its output based on the cooling demand. This results in more consistent temperatures and minimizes energy waste.

The Toshiba A09-01P is also equipped with a multi-stage air purification system. This advanced filtration process includes a pre-filter, a HEPA filter, and an activated carbon filter. The pre-filter captures larger particles, while the HEPA filter can remove up to 99.97% of microscopic allergens and pollutants. The activated carbon filter helps to eliminate odors, ensuring that the air quality remains fresh and clean.

In terms of user convenience, the device comes with a smart remote control that allows users to adjust settings without getting up. It features programmable timers and multiple modes, including auto, cool, and dry modes, aiding users in customizing their experience according to specific needs.

The unit's compact design allows for installation in tighter spaces, making it ideal for urban environments where real estate is at a premium. The quiet operation of the A09-01P is another significant advantage, ensuring that it runs unobtrusively in the background, making it perfect for bedrooms or offices.

Furthermore, Toshiba has integrated smart technology into the A09-01P, allowing it to be controlled via smartphone apps. This feature adds an extra layer of convenience, enabling users to manage their indoor climate even when they are away from home.

Overall, the Toshiba A09-01P stands out in the air conditioning market due to its combination of energy efficiency, advanced filtration, and user-friendly features, making it a wise investment for any space requiring climate control.