Lochinvar Hot Water Generator 5Troubleshooting, Symptom, Probable Cause, Corrective Action

Page 14
Pressure

Hot Water Generator Installation and Operation Manual

5Troubleshooting

SYMPTOM

PROBABLE CAUSE

 

CORRECTIVE ACTION

 

 

 

 

 

 

 

 

 

Pressure

relief

valve

• The primary / inlet temperature control

• Verify

control

valve

bulb

was installed in

“pops”.

 

 

 

valve is not closing properly.

 

 

tank bulbwell.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• The secondary / outlet energy source

• Verify

control

valve

actuator

is

 

 

 

 

pressure

control system

is

not

operating properly.

 

 

 

 

 

 

 

 

 

 

 

operating properly.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• The

over-temperature

limit system

is

• Check the individual components of the

 

 

 

 

out of adjustment, or some component

system and repair or replace the failed

 

 

 

 

of the system has failed.

 

 

 

component(s) as necessary.

 

 

 

 

 

 

 

 

 

Water shuts down at or

• The

over-temperature

limit system

is

• Check the individual components of the

too close to (above or

out of adjustment, or some component

system and repair or replace the failed

below) the design outlet

of the system has failed.

 

 

 

component(s) as necessary.

 

 

 

temperature.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A loud banging in the

• The condensate / water return piping

• Reconfigure

the

condensate

/

water

water

heater,

primary

has

not

been

installed

properly,

return

piping

and check valve to allow

piping,

or

condensate /

allowing the condensate / water to

for proper

drainage.

Check

to

assure

water return piping (not

drain

freely

 

(by

gravity);

the

that there is no restriction in the

to be

confused

with a

condensate

/

water

drain

line

is

condensate

/

water

drain line.

Replace

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

normal

clicking noise

restricted;

or

the

condensate

/ water

the check

valve

if

it

is

leaking

or

has

check valve is leaking or has failed.

 

failed.

Also,

check

to

assure

that

there

made during operation).

 

 

 

 

 

 

 

 

 

is no restriction in the condensate /

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

water drain line.

 

 

 

 

 

 

 

 

 

 

 

• Primary /

inlet

steam line

is

not

• The steam supply should be clean dry

 

 

 

 

properly trapped (steam as energy

steam. Do

not

slug

 

controls

system

 

 

 

 

source only).

 

 

 

 

 

with

boiler

 

startup

condensate.

 

This

 

 

 

 

 

 

 

 

 

 

 

 

can damage controls as well as tube

 

 

 

 

 

 

 

 

 

 

 

 

bundle.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Manual background 14 Manual background

Image 14
Contents HOT WATER GENERATOR Unit shown with optional control packageDANGER ContentsHazard definitions Hot Water Generator Installation Instructions 1General informationAvailability Figure 1 Vertical Tanks Figure 2 Horizontal Tanks Optional control packages see page1General information OptionsFigure 4 Water to Water Optional Control Package 1General information continuedFigure 3 Steam to Water Optional Control Package WARNING Areas of potential dangerFigure 5 Steam to Water Storage Heater 2InstallationTransporting and unpacking the unit Figure 6 Water to Water Storage HeaterMounting the unit 2Installation continuedExamining the unit Unit and components2Installation Connecting the energy sourcePiping the relief valves to drain Steam or boiler waterCompleting installation 2Installation continued3Operation Startup procedureShutdown procedure Time Interval 4InspectionRECOMMENDED INSPECTIONS Power ConnectionsPROBABLE CAUSE 5TroubleshootingSYMPTOM CORRECTIVE ACTIONPROBABLE CAUSE 5Troubleshooting continuedSYMPTOM CORRECTIVE ACTIONPROBABLE CAUSE 5TroubleshootingSYMPTOM CORRECTIVE ACTION6Maintenance Storage tank maintenanceFigure 7 Horizontal Storage Tank w/Anodes 6MaintenanceMagnesium anode rod inspection Figure 8 Vertical Storage Tank w/AnodesFigure 9 Pump Wiring Diagram 6Maintenance continuedComponents replacement Tube bundle - inspection and replacement 6MaintenancePower connections - rewiring replacement6Maintenance continued 5.Replace the damaged section of line or valve6Maintenance Strainers - inspection and replacement6Maintenance continued Traps - replacement steam systems only7Notes 7Notes HWG-i&o-01 CP-2M-12/05