Lochinvar Hot Water Generator 6Maintenance continued, Components replacement, Pump Wiring Diagram

Page 17
6Maintenance (continued)

Hot Water Generator Installation and Operation Manual

6Maintenance (continued)

Component(s) replacement

Circulating pump - inspection and replacement

Lochinvar Hot Water Generators can be equipped with a circulating pump to assist in the even heating of the water. If the unit is equipped with a circulating pump, the following procedure should be followed to replace the pump.

1.Follow Steps 1 through 5 of the shutdown procedure (page 10) to take the unit off-line before attempting to service the circulating pump.

The combination of electricity and water ￿ WARNING can pose a very dangerous situation. Turn

off / disconnect all electric power before attempting any maintenance procedure.

2. Refer to the manufacturer’s documentation supplied with the unit pertaining to testing the pump. If found to be defective or questionable, replace the pump by continuing with the steps that follow.

3. After assuring that the power has been turned off, disconnect the electric leads to the circulating pump (FIG. 9).

4. Close the manual shutoff valves located near the inlet and outlet ports of the pump.

5. Break the joints between the pump and the inlet and outlet piping. Remove the pump.

6. Reconnect the pump to the inlet and outlet piping. Follow recommendations contained in the manufacturer’s documentation, local codes, or accepted contractor practices as to the use and / or type of joint compound or sealer at the connections.

7. Open the manual shutoff valves located on the inlet and outlet sides of the pump and check for any leakage at the joints.

8. Reconnect the electric leads to the pump (reference FIG. 9 to assure proper wiring).

9. Follow the startup procedures (page 10) to put the unit back on-line. Carefully check all connections for any sign of leakage.

Circulating pump shutoff valves - replacement

If the Lochinvar Hot Water Generator is equipped with a circulating pump to assist in the even heating of the water, manual shutoff valves will be located on both the inlet and outlet side piping. To replace the valves, follow the procedure detailed below.

1.Follow Steps 1 through 5 of the shutdown procedure (page 10) to take the unit off-line before attempting to service the circulating pump shutoff valves.

The combination of electricity and water ￿ WARNING can pose a very dangerous situation. Turn

off / disconnect all electric power before attempting any maintenance procedure.

2. After assuring that the power has been turned off, disconnect the electric leads to the circulating pump (FIG. 9).

3. Break the joints between the pump and the inlet and outlet piping. Remove the pump.

4. Remove the shutoff valves.

5. Install the new valves. Follow recommendations contained in the manufacturer’s documentation, local codes, or accepted contractor practices as to the use and / or type of joint compound or sealer at the connections.

6. Reconnect the pump to the inlet and outlet piping. Follow recommendations contained in the manufacturer’s documentation, local codes, or accepted contractor practices as to the use and / or type of joint compound or sealer at the connections.

7. Open the manual shutoff valves located on the inlet and outlet sides of the pump.

8. Reconnect the electric leads to the pump (reference FIG. 9 to assure proper wiring).

9. Follow the startup procedures (page 10) to put the unit back on-line. Carefully check all joints for any sign of leakage.

Figure 9_Pump Wiring Diagram

Component(s) replacement 17 Figure 9_Pump Wiring Diagram

Image 17
Contents Unit shown with optional control package HOT WATER GENERATORDANGER ContentsHazard definitions Hot Water Generator Installation Instructions 1General informationAvailability 1General information Optional control packages see pageFigure 1 Vertical Tanks Figure 2 Horizontal Tanks OptionsFigure 3 Steam to Water Optional Control Package 1General information continuedFigure 4 Water to Water Optional Control Package WARNING Areas of potential dangerTransporting and unpacking the unit 2InstallationFigure 5 Steam to Water Storage Heater Figure 6 Water to Water Storage HeaterExamining the unit 2Installation continuedMounting the unit Unit and componentsPiping the relief valves to drain Connecting the energy source2Installation Steam or boiler water2Installation continued Completing installation3Operation Startup procedureShutdown procedure RECOMMENDED INSPECTIONS 4InspectionTime Interval Power ConnectionsSYMPTOM 5TroubleshootingPROBABLE CAUSE CORRECTIVE ACTIONSYMPTOM 5Troubleshooting continuedPROBABLE CAUSE CORRECTIVE ACTIONSYMPTOM 5TroubleshootingPROBABLE CAUSE CORRECTIVE ACTIONStorage tank maintenance 6MaintenanceMagnesium anode rod inspection 6MaintenanceFigure 7 Horizontal Storage Tank w/Anodes Figure 8 Vertical Storage Tank w/AnodesFigure 9 Pump Wiring Diagram 6Maintenance continuedComponents replacement Power connections - rewiring 6MaintenanceTube bundle - inspection and replacement replacement5.Replace the damaged section of line or valve 6Maintenance continuedStrainers - inspection and replacement 6MaintenanceTraps - replacement steam systems only 6Maintenance continued7Notes 7Notes HWG-i&o-01 CP-2M-12/05