Lochinvar Hot Water Generator operation manual 5Troubleshooting continued, Symptom, Probable Cause

Page 13
5Troubleshooting (continued)

Hot Water Generator Installation and Operation Manual

5Troubleshooting (continued)

 

SYMPTOM

 

PROBABLE CAUSE

 

CORRECTIVE ACTION

Outlet

temperature • Inlet

energy source

pressure

is too

• For steam

systems

check the

primary

fluctuates widely.

low or boiler water temperature is too low.

energy source pressure/temperature. If the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

reading is low, adjust the inlet

 

 

 

 

 

 

 

 

pressure/temperature to meet the design

 

 

 

 

 

 

 

 

requirements. If there is a restriction in the

 

 

 

 

 

 

 

 

primary energy source line, the pressure

 

 

 

 

 

 

 

 

reading will drop excessively when the

 

 

 

 

 

 

 

 

generator calls for full energy on steam

 

 

 

 

 

 

 

 

systems, even though the pressure seems

 

 

 

 

 

 

 

 

to be normal during light demand. If the

 

 

 

 

 

 

 

 

primary pressure is correct, the system

 

 

 

 

 

 

 

 

should reach design pressure for energy

 

 

 

 

 

 

 

 

source in the tube bundle as the

 

 

 

 

 

 

 

 

 

 

temperature of the water in the tank

 

 

 

 

 

 

 

 

heater approaches shutoff.

 

 

 

 

• The condensate / water return piping

• Reconfigure

the condensate

/

water

 

 

has

not been installed properly,

return piping and check valve

to

allow

 

 

allowing the condensate / water to

for proper drainage.

Check to assure

 

 

drain

freely

(by

gravity);

the

that there is no restriction in the

 

 

condensate / water drain line is

condensate / water drain line.

Replace

 

 

restricted; or the condensate / water

the check valve if it is leaking or has

 

 

check valve is leaking or has failed.

 

failed. Also, check

to assure that

there

 

 

 

 

 

 

 

 

is no restriction in the condensate /

 

 

 

 

 

 

 

 

water drain line.

 

 

 

 

 

• The primary / inlet temperature control

• Verify control valve bulb was installed in

 

 

valve is not closing properly.

 

the bulbwell.

 

 

 

 

 

 

• Bypass

valve

not

adjusted

(boiler

• Adjust bypass valve approximately half

 

 

water).

 

 

 

 

closed. Readjust as necessary.

 

 

 

 

• The primary / inlet temperature control

• Verify control valve actuator is working

 

 

valve is not opening properly.

 

properly , if not replace.

 

 

Excess or

insufficient

• The

 

condensate

/ water return piping

• Reconfigure

the

condensate

/

water

condensate (boiler water)

has

 

not

been

installed

properly,

return piping and check valve

to

allow

being

returned from the

allowing

the condensate / water to

for proper

drainage.

Check to

assure

drain

freely

(by

gravity);

the

that

there

 

is

no

restriction

 

in

the

unit.

 

 

 

 

 

 

condensate / water drain line is

condensate / water drain line.

Replace

 

 

 

 

 

 

restricted; or the condensate / water

the check valve if it is leaking or has

 

 

 

check valve is leaking or has failed.

 

failed.

Also,

check

to assure that

there

 

 

 

 

 

 

 

 

 

 

 

is no restriction in the condensate /

 

 

 

 

 

 

 

 

 

 

 

water drain line.

 

 

 

 

 

 

 

 

• Bypass loop valve not adjusted (boiler

• Adjust bypass valve approximately half

 

 

 

water).

 

 

 

 

 

closed. Readjust as necesssary.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Steam

being

discharged • The

tube

bundle

is

heavily

scaled

or

• Call

Lochinvar

Corporation,

 

or

an

into

the

condensate

damaged.

 

 

 

 

 

authorized

sales

agent for instructions

drain.

 

 

 

 

 

 

 

 

 

 

on repair or replacement.

 

 

 

Manual background 13 Manual background

Image 13
Contents Unit shown with optional control package HOT WATER GENERATORHazard definitions ContentsDANGER Availability 1General informationHot Water Generator Installation Instructions 1General information Optional control packages see pageFigure 1 Vertical Tanks Figure 2 Horizontal Tanks OptionsFigure 3 Steam to Water Optional Control Package 1General information continuedFigure 4 Water to Water Optional Control Package WARNING Areas of potential dangerTransporting and unpacking the unit 2InstallationFigure 5 Steam to Water Storage Heater Figure 6 Water to Water Storage HeaterExamining the unit 2Installation continuedMounting the unit Unit and componentsPiping the relief valves to drain Connecting the energy source2Installation Steam or boiler water2Installation continued Completing installationShutdown procedure Startup procedure3Operation RECOMMENDED INSPECTIONS 4InspectionTime Interval Power ConnectionsSYMPTOM 5TroubleshootingPROBABLE CAUSE CORRECTIVE ACTIONSYMPTOM 5Troubleshooting continuedPROBABLE CAUSE CORRECTIVE ACTIONSYMPTOM 5TroubleshootingPROBABLE CAUSE CORRECTIVE ACTIONStorage tank maintenance 6MaintenanceMagnesium anode rod inspection 6MaintenanceFigure 7 Horizontal Storage Tank w/Anodes Figure 8 Vertical Storage Tank w/AnodesComponents replacement 6Maintenance continuedFigure 9 Pump Wiring Diagram Power connections - rewiring 6MaintenanceTube bundle - inspection and replacement replacement5.Replace the damaged section of line or valve 6Maintenance continuedStrainers - inspection and replacement 6MaintenanceTraps - replacement steam systems only 6Maintenance continued7Notes 7Notes HWG-i&o-01 CP-2M-12/05