Lenox 506637-01 New or Replacement Line Set, Refrigerant Line SET, Refrigerant Line Set

Page 10

New or Replacement Line Set

REFRIGERANT LINE SET

This section provides information on installation or replacement of existing line set. If new or replacement line set is not being installed then proceed to Brazing Connections on page 12.

IMPORTANT

Lennox highly recommends changing line set when converting the existing system from HCFC−22 to HFC−410A. If that is not possible and the line set is the proper size as reference in table 2, use the procedure outlined under Flushing the System on page 13.

If refrigerant lines are routed through a wall, then seal and isolate the opening so vibration is not transmitted to the building. Pay close attention to line set isolation during installation of any HVAC system. When properly isolated from building structures (walls, ceilings. floors), the refrigerant lines will not create unnecessary vibration and subsequent sounds. See figure 6 for recommended installation practices. Also, consider the following when placing and installing a high−efficiency outdoor unit.

Liquid lines that meter the refrigerant, such as RFC1 liquid lines, must not be used in this application. Existing line set of proper size as listed in table 2 may be reused. If system was previously charged with HCFC−22 refrigerant, then existing line set must be flushed (see Flushing Line Set and Indoor Coil on page15).

Field refrigerant piping consists of liquid and vapor lines from the outdoor unit to the indoor unit coil (braze connections). Use Lennox L15 (sweat, non−flare) series line set, or field−fabricated refrigerant line sizes as listed in table 2.

NOTE When installing refrigerant lines longer than 50 feet, see the Lennox Refrigerant Piping Design and Fabrication Guidelines, CORP. 9351−L9, or contact Lennox Technical Support Product Applications for assistance.

To obtain the correct information from Lennox, be sure to communicate the following information:

SModel (XC16) and size of unit (e.g. −036).

SLine set diameters for the unit being installed as listed in table 2 and total length of installation.

SNumber of elbows vertical rise or drop in the piping.

The compressor is charged with sufficient Polyol ester oil for line set lengths up to 50 feet. Recommend adding oil to system based on the amount of refrigerant charge in the system. No need to add oil in system with 20 pounds of refrigerant or less. For systems over 20 pounds − add one ounce of every five pounds of refrigerant.

Recommended topping−off POE oils are Mobil EAL ARCTIC 22 CC or ICI EMKARATEt RL32CF.

IMPORTANT

Mineral oils are not compatible with HFC−410A. If oil must be added, it must be a Polyol Ester oil.

Table 2. Refrigerant Line Set

Model

Field Connections

 

Recommended Line Set

 

 

 

 

 

 

Liquid Line

Suction Line

Liquid Line

Suction Line

L15 Line Set

 

 

 

 

 

 

XC16−024−230

3/8" (10 mm)

3/4" (19 mm)

3/8" (10 mm)

3/4" (19 mm)

L15−41

 

 

 

 

 

 

XC16−036−230

 

 

 

 

 

 

3/8" (10 mm)

7/8" (22 mm)

3/8" (10 mm)

7/8" (22 mm)

L15−65

XC16−048−230

 

 

 

 

 

 

 

 

 

 

 

XC16−060−230

3/8" (10 mm)

1−1/8" (29 mm)

3/8" (10 mm)

1−1/8" (29 mm)

Field Fabricated

 

 

 

 

 

 

NOTE

 

 

 

 

 

 

 

 

 

 

 

Page 10

506637−01 11/10

Image 10
Contents Shipping and Packing List Table of ContentsGeneral AIR ConditionerSide View Unit Dimensions − Inches mmModel Number Identification XXX 230 TOP ViewTypical Unit Parts Arrangement Plumbing and Switches ComponentsControl Panel Operating Service Valves Operating Gauge Set and Service ValvesUsing Manifold Gauge SET Torque RequirementsTo Access Service Port Operating Angle Type Service ValveOperating Ball Type Service Valve Reinstall Stem CapRecovering Refrigerant Recovering Refrigerant from Existing SystemRefrigerant from System 1DISCONNECT Power 2CONNECT Manifold Gauge SETPositioning Considerations New Outdoor Unit PlacementClearance on ALL Sides Placing Unit on SlabDetail a Outside Unit Placement Placement, Slab Mounting and Stabilizing UnitRoof Mounting Removing and Installing PanelsLouvered Panel Installation Louvered Panel RemovalRefrigerant Line SET New or Replacement Line SetRefrigerant Line Set Refrigerant Line SET From Vertical to Horizontal Refrigerant Line SET Alling Horizontal RunsBrazing Connections Brazing Procedures 1CUT and Debur6BRAZE Line SET Wrap Service ValvesFlow Nitrogen 7PREPARATION for Next StepInstalling Indoor Expansion Valve Flushing Line Set and Indoor CoilSensing Bulb Installation Installing Indoor Metering DeviceIndoor Expansion Valve Installation Equalizer Line InstallationLeak Test Line Set and Indoor Coil Leak TestEvacuating Line Set and Indoor Coil Evacuating SystemElectrical Size Circuit and Install Disconnect2INSTALL Thermostat 24VAC TransformerTypical Unit Wiring Diagram Servicing Units Delivered Void of Charge Unit Start−UpSystem Refrigerant Connections for Testing and ChargingWhen to CHARGE? RequirementsWeigh in Charging Method Checking AIR Flow AT Indoor CoilCalculating System Charge for Outdoor Unit Void of Charge Above BelowSystem Operation TWO−STAGE CompressorIndoor Unit MaintenanceUnit Components Indoor CoilHomeowner Compressor Start−Up and Performance ChecklistTemperature Outdoor Unit FAN Motor

Elite Series X16 Air Conditioner Units, 506637-01 specifications

The Lenox 506637-01, Elite Series X16 Air Conditioner is a top-tier cooling solution that stands out in the residential HVAC market. Known for its impressive energy efficiency and advanced features, this unit is designed to provide homeowners with exceptional comfort while also keeping energy bills in check.

One of the main highlights of the Elite Series X16 is its SEER rating, which stands at an impressive 16. This makes it one of the most energy-efficient air conditioning systems available, ensuring that it operates effectively without consuming excessive power. By converting less energy into cooling, homeowners can enjoy lower utility bills and a reduced carbon footprint.

The X16 model features a two-stage cooling system, which allows for better humidity control and more even temperature distribution throughout the home. Unlike standard single-stage units that operate at full capacity at all times, the two-stage system enables the air conditioner to run at a lower, more efficient speed for the majority of its operation, only ramping up when additional cooling is needed. This not only enhances comfort but also extends the lifespan of the unit.

Incorporating advanced technology, the Elite Series X16 utilizes a high-efficiency scroll compressor and innovative airflow design. This results in quieter operation, providing a peaceful indoor environment. The noise levels are minimal, making it suitable for nighttime use or for homes where noise might be a concern.

The air conditioner is built with durability in mind, featuring a robust cabinet that protects against the elements and potential wear and tear over time. Its louvered design provides additional protection for critical components, ensuring longevity and consistent performance.

Furthermore, the X16 is compatible with smart thermostats and home automation systems, allowing homeowners to optimize their cooling schedules remotely. This connectivity helps users make informed decisions about energy usage, further enhancing efficiency while providing ultimate control over home comfort.

In summary, the Lenox 506637-01, Elite Series X16 Air Conditioner provides an excellent blend of energy efficiency, advanced technology, and a focus on comfort and durability. With its two-stage cooling system, high SEER rating, and quiet operation, it is an ideal choice for those seeking a reliable, high-performance cooling solution for their homes.