Lenox 506637-01 Operating Gauge Set and Service Valves, Torque Requirements

Page 4

WARNING

Electric Shock Hazard. Can cause injury or death. Unit must be grounded in accordance with national and local codes.

Line voltage is present at all components when unit is not in operation on units with single-pole contactors. Disconnect all remote electric power supplies before opening access panel. Unit may have multiple power supplies.

CAUTION

Physical contact with metal edges and corners while applying excessive force or rapid motion can result in personal injury. Be aware of, and use caution when working near these areas during installation or while servicing this equipment.

Operating Gauge Set and Service Valves

These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities who have jurisdiction before installation.

TORQUE REQUIREMENTS

When servicing or repairing heating, ventilating, and air conditioning components, ensure the fasteners are appropriately tightened. Table 1 lists torque values for fasteners.

IMPORTANT

Only use Allen wrenches of sufficient hardness (50Rc − Rockwell Harness Scale minimum). Fully insert the wrench into the valve stem recess.

Service valve stems are factory−torqued (from 9 ft−lbs for small valves, to 25 ft−lbs for large valves) to prevent refrigerant loss during shipping and handling. Using an Allen wrench rated at less than 50Rc risks rounding or breaking off the wrench, or stripping the valve stem recess.

See the Lennox Service and Application Notes #C−08−1 for further details and information.

IMPORTANT

To prevent stripping of the various caps used, the appropriately sized wrench should be used and fitted snugly over the cap before tightening.

Table 1. Torque Requirements

Parts

Recommended Torque

 

 

 

Service valve cap

8 ft.− lb.

11 NM

 

 

 

Sheet metal screws

16 in.− lb.

2 NM

 

 

 

Machine screws #10

28 in.− lb.

3 NM

 

 

 

Compressor bolts

90 in.− lb.

10 NM

 

 

 

Gauge port seal cap

8 ft.− lb.

11 NM

 

 

 

USING MANIFOLD GAUGE SET

When checking the system charge, only use a manifold gauge set that features low loss anti−blow back fittings.

Manifold gauge set used with HFC−410A refrigerant systems must be capable of handling the higher system operating pressures. The gauges should be rated for use with pressures of 0 − 800 psig on the high side and a low side of 30" vacuum to 250 psig with dampened speed to 500 psi. Gauge hoses must be rated for use at up to 800 psig of pressure with a 4000 psig burst rating.

OPERATING SERVICE VALVES

The liquid and vapor line service valves are used for removing refrigerant, flushing, leak testing, evacuating, checking charge and charging.

Each valve is equipped with a service port which has a factory−installed valve stem. Figure 2 provides information on how to access and operating both angle and ball service valves.

Page 4

506637−01 11/10

Image 4
Contents Table of Contents GeneralShipping and Packing List AIR ConditionerUnit Dimensions − Inches mm Model Number Identification XXX 230Side View TOP ViewTypical Unit Parts Arrangement Plumbing and Switches ComponentsControl Panel Operating Gauge Set and Service Valves Using Manifold Gauge SETOperating Service Valves Torque RequirementsOperating Angle Type Service Valve Operating Ball Type Service ValveTo Access Service Port Reinstall Stem CapRecovering Refrigerant from Existing System Refrigerant from System 1DISCONNECT PowerRecovering Refrigerant 2CONNECT Manifold Gauge SETNew Outdoor Unit Placement Clearance on ALL SidesPositioning Considerations Placing Unit on SlabDetail a Outside Unit Placement Placement, Slab Mounting and Stabilizing UnitRemoving and Installing Panels Louvered Panel InstallationRoof Mounting Louvered Panel RemovalRefrigerant Line SET New or Replacement Line SetRefrigerant Line Set Refrigerant Line SET From Vertical to Horizontal Refrigerant Line SET Alling Horizontal RunsBrazing Connections Brazing Procedures 1CUT and DeburWrap Service Valves Flow Nitrogen6BRAZE Line SET 7PREPARATION for Next StepInstalling Indoor Expansion Valve Flushing Line Set and Indoor CoilInstalling Indoor Metering Device Indoor Expansion Valve InstallationSensing Bulb Installation Equalizer Line InstallationLeak Test Line Set and Indoor Coil Leak TestEvacuating Line Set and Indoor Coil Evacuating SystemSize Circuit and Install Disconnect 2INSTALL ThermostatElectrical 24VAC TransformerTypical Unit Wiring Diagram Servicing Units Delivered Void of Charge Unit Start−UpConnections for Testing and Charging When to CHARGE?System Refrigerant RequirementsWeigh in Charging Method Checking AIR Flow AT Indoor CoilCalculating System Charge for Outdoor Unit Void of Charge Above BelowSystem Operation TWO−STAGE CompressorMaintenance Unit ComponentsIndoor Unit Indoor CoilHomeowner Start−Up and Performance Checklist TemperatureCompressor Outdoor Unit FAN Motor

Elite Series X16 Air Conditioner Units, 506637-01 specifications

The Lenox 506637-01, Elite Series X16 Air Conditioner is a top-tier cooling solution that stands out in the residential HVAC market. Known for its impressive energy efficiency and advanced features, this unit is designed to provide homeowners with exceptional comfort while also keeping energy bills in check.

One of the main highlights of the Elite Series X16 is its SEER rating, which stands at an impressive 16. This makes it one of the most energy-efficient air conditioning systems available, ensuring that it operates effectively without consuming excessive power. By converting less energy into cooling, homeowners can enjoy lower utility bills and a reduced carbon footprint.

The X16 model features a two-stage cooling system, which allows for better humidity control and more even temperature distribution throughout the home. Unlike standard single-stage units that operate at full capacity at all times, the two-stage system enables the air conditioner to run at a lower, more efficient speed for the majority of its operation, only ramping up when additional cooling is needed. This not only enhances comfort but also extends the lifespan of the unit.

Incorporating advanced technology, the Elite Series X16 utilizes a high-efficiency scroll compressor and innovative airflow design. This results in quieter operation, providing a peaceful indoor environment. The noise levels are minimal, making it suitable for nighttime use or for homes where noise might be a concern.

The air conditioner is built with durability in mind, featuring a robust cabinet that protects against the elements and potential wear and tear over time. Its louvered design provides additional protection for critical components, ensuring longevity and consistent performance.

Furthermore, the X16 is compatible with smart thermostats and home automation systems, allowing homeowners to optimize their cooling schedules remotely. This connectivity helps users make informed decisions about energy usage, further enhancing efficiency while providing ultimate control over home comfort.

In summary, the Lenox 506637-01, Elite Series X16 Air Conditioner provides an excellent blend of energy efficiency, advanced technology, and a focus on comfort and durability. With its two-stage cooling system, high SEER rating, and quiet operation, it is an ideal choice for those seeking a reliable, high-performance cooling solution for their homes.