Lenox Elite Series X16 Air Conditioner Units, 506637-01 Leak Test Line Set and Indoor Coil

Page 17

IMPORTANT

The Environmental Protection Agency (EPA) prohibits the intentional venting of HFC refrigerants during maintenance, service, repair and disposal of appliance. Approved methods of recovery, recycling or reclaiming must be followed.

IMPORTANT

Leak Test Line Set and Indoor Coil

WARNING

When using a high pressure gas such as dry nitrogen to pressurize a refrigeration or air conditioning system, use a regulator that can control the pressure down to 1 or 2 psig (6.9 to 13.8 kPa).

If this unit is being matched with an approved line set or indoor unit coil which was previously charged with mineral oil, or if it is being matched with a coil which was manufactured before January of 1999, the coil and line set must be flushed prior to installation. Take care to empty all existing traps. Polyol ester (POE) oils are used in Lennox units charged with HFC−410A refrigerant. Residual mineral oil can act as an insulator, preventing proper heat transfer. It can also clog the expansion device, and reduce the system performance and capacity.

Failure to properly flush the system per the instructions below will void the warranty.

IMPORTANT

Leak detector must be capable of sensing HFC refrigerant.

WARNING

Refrigerant can be harmful if it is inhaled. Refrigerant must be used and recovered responsibly.

Failure to follow this warning may result in personal injury or death.

1CONNECT GAUGE SET

AConnect an HFC−410A manifold gauge set high pressure hose to the vapor valve service port.

NOTE , the high pressure hose is connected to

the liquid line port. However, connecting it to the vapor port better protects the manifold gauge set from high pressure damage.

BWith both manifold valves closed, connect the cylinder of HFC−410A refrigerant to the center port of the manifold gauge set.

NOTE Later in the procedure, the HFC−410A container will be replaced by the nitrogen container.

LOW

B

HIGH

MANIFOLD GAUGE SET

OUTDOOR UNIT

A

TO VAPOR

SERVICE VALVE

NITROGEN

HFC−410A

2TEST FOR LEAKS

After the line set has been connected to the indoor and outdoor units, check the line set connections and indoor unit for leaks. Use the following procedure to test for leaks:

A With both manifold valves closed, connect the cylinder of HFC−410A refrigerant to the center port of the manifold gauge set. Open the valve on the HFC−410A cylinder (vapor only).

B Open the high pressure side of the manifold to allow HFC−410A into the line set and indoor unit. Weigh in a trace amount of HFC−410A. [A trace amount is a maximum of two ounces (57 g) refrigerant or three pounds (31 kPa) pressure]. Close the valve on the HFC−410A cylinder and the valve on the high pressure side of the manifold gauge set. Disconnect the HFC−410A cylinder.

C Connect a cylinder of dry nitrogen with a pressure regulating valve to the center port of the manifold gauge set.

D Adjust dry nitrogen pressure to 150 psig (1034 kPa). Open the valve on the high side of the manifold gauge set in order to pressurize the line set and the indoor unit.

E After a few minutes, open one of the service valve ports and verify that the refrigerant added to the system earlier is measurable with a leak detector.

F After leak testing disconnect gauges from service ports.

Figure 11. Leak Test

Page 17

XC16 SERIES

Image 17
Contents General Table of ContentsShipping and Packing List AIR ConditionerModel Number Identification XXX 230 Unit Dimensions − Inches mmSide View TOP ViewControl Panel Plumbing and Switches ComponentsTypical Unit Parts Arrangement Using Manifold Gauge SET Operating Gauge Set and Service ValvesOperating Service Valves Torque RequirementsOperating Ball Type Service Valve Operating Angle Type Service ValveTo Access Service Port Reinstall Stem CapRefrigerant from System 1DISCONNECT Power Recovering Refrigerant from Existing SystemRecovering Refrigerant 2CONNECT Manifold Gauge SETClearance on ALL Sides New Outdoor Unit PlacementPositioning Considerations Placing Unit on SlabPlacement, Slab Mounting and Stabilizing Unit Detail a Outside Unit PlacementLouvered Panel Installation Removing and Installing PanelsRoof Mounting Louvered Panel RemovalRefrigerant Line Set New or Replacement Line SetRefrigerant Line SET Refrigerant Line SET Alling Horizontal Runs Refrigerant Line SET From Vertical to HorizontalBrazing Connections 1CUT and Debur Brazing ProceduresFlow Nitrogen Wrap Service Valves6BRAZE Line SET 7PREPARATION for Next StepFlushing Line Set and Indoor Coil Installing Indoor Expansion ValveIndoor Expansion Valve Installation Installing Indoor Metering DeviceSensing Bulb Installation Equalizer Line InstallationLeak Test Leak Test Line Set and Indoor CoilEvacuating System Evacuating Line Set and Indoor Coil2INSTALL Thermostat Size Circuit and Install DisconnectElectrical 24VAC TransformerTypical Unit Wiring Diagram Unit Start−Up Servicing Units Delivered Void of ChargeWhen to CHARGE? Connections for Testing and ChargingSystem Refrigerant RequirementsCalculating System Charge for Outdoor Unit Void of Charge Checking AIR Flow AT Indoor CoilWeigh in Charging Method Below AboveTWO−STAGE Compressor System OperationUnit Components MaintenanceIndoor Unit Indoor CoilHomeowner Temperature Start−Up and Performance ChecklistCompressor Outdoor Unit FAN Motor

Elite Series X16 Air Conditioner Units, 506637-01 specifications

The Lenox 506637-01, Elite Series X16 Air Conditioner is a top-tier cooling solution that stands out in the residential HVAC market. Known for its impressive energy efficiency and advanced features, this unit is designed to provide homeowners with exceptional comfort while also keeping energy bills in check.

One of the main highlights of the Elite Series X16 is its SEER rating, which stands at an impressive 16. This makes it one of the most energy-efficient air conditioning systems available, ensuring that it operates effectively without consuming excessive power. By converting less energy into cooling, homeowners can enjoy lower utility bills and a reduced carbon footprint.

The X16 model features a two-stage cooling system, which allows for better humidity control and more even temperature distribution throughout the home. Unlike standard single-stage units that operate at full capacity at all times, the two-stage system enables the air conditioner to run at a lower, more efficient speed for the majority of its operation, only ramping up when additional cooling is needed. This not only enhances comfort but also extends the lifespan of the unit.

Incorporating advanced technology, the Elite Series X16 utilizes a high-efficiency scroll compressor and innovative airflow design. This results in quieter operation, providing a peaceful indoor environment. The noise levels are minimal, making it suitable for nighttime use or for homes where noise might be a concern.

The air conditioner is built with durability in mind, featuring a robust cabinet that protects against the elements and potential wear and tear over time. Its louvered design provides additional protection for critical components, ensuring longevity and consistent performance.

Furthermore, the X16 is compatible with smart thermostats and home automation systems, allowing homeowners to optimize their cooling schedules remotely. This connectivity helps users make informed decisions about energy usage, further enhancing efficiency while providing ultimate control over home comfort.

In summary, the Lenox 506637-01, Elite Series X16 Air Conditioner provides an excellent blend of energy efficiency, advanced technology, and a focus on comfort and durability. With its two-stage cooling system, high SEER rating, and quiet operation, it is an ideal choice for those seeking a reliable, high-performance cooling solution for their homes.