Lenox Elite Series X16 Air Conditioner Units, 506637-01 installation instructions Homeowner

Page 27

SDigital volt/amp meter

SElectronic temperature thermometer

SOn-off toggle switch

Procedure

NOTE − Block outdoor coil to maintain a minimum of 375 psig during testing).

1.Turn main power OFF to outdoor unit.

2.Adjust room thermostat set point 5ºF above the room temperature.

3.Remove control access panel. Install refrigeration gauges on unit. Attach the amp meter to the common (black wire) wire of the compressor harness. Attach thermometer to discharge line as close as possible to the compressor.

4.Turn toggle switch OFF and install switch in series with Y2 wire from room thermostat.

5.Cycle main power ON.

6.Allow pressures and temperatures to stabilize before taking measurements (may take up to 10 minutes).

7.Record all of the readings for the Y1 demand.

8.Close switch to energize Y2 demand. Verify power is going to compressor solenoid.

9.Allow pressures and temperatures to stabilize before taking any measured reading (this may take up to 10 minutes).

10.Record all of the readings with the Y1 and Y2 demand.

11.If temperatures and pressures change in the direction noted in chart, the compressor is properly modulating from low to high capacity. (If no amperage, pressures or temperature readings change when this test is performed, the compressor is not modulating between low and high capacity and replacement is necessary).

12.After testing is complete, return unit to original set up.

HOMEOWNER

Cleaning of the outdoor unit’s coil should be performed by a trained service technician. Contact your dealer and set up a schedule (preferably twice a year, but at least once a year) to inspect and service your outdoor unit. The following maintenance may be performed by the homeowner.

IMPORTANT

Sprinklers and soaker hoses should not be installed where they could cause prolonged exposure to the outdoor unit by treated water. Prolonged exposure of the unit to treated water (i.e., sprinkler systems, soakers, waste water, etc.) will corrode the surface of steel and aluminum parts and diminish performance and longevity of the unit.

Outdoor Coil

The outdoor unit must be properly maintained to ensure its proper operation.

SPlease contact your dealer to schedule proper inspection and maintenance for your equipment.

SMake sure no obstructions restrict airflow to the outdoor unit.

SGrass clippings, leaves, or shrubs crowding the unit can cause the unit to work harder and use more energy.

SKeep shrubbery trimmed away from the unit and periodically check for debris which collects around the unit.

Cleaning of the outdoor unit’s coil should be performed by a trained service technician. Contact your dealer and set up a schedule (preferably twice a year, but at least once a year) to inspect and service your outdoor unit.

Routine Maintenance

In order to ensure peak performance, your system must be properly maintained. Clogged filters and blocked airflow prevent your unit from operating at its most efficient level.

1.Air Filter Ask your Lennox dealer to show you where your indoor unit’s filter is located. It will be either at the indoor unit (installed internal or external to the cabinet) or behind a return air grille in the wall or ceiling. Check the filter monthly and clean or replace it as needed.

2.Disposable Filter Disposable filters should be replaced with a filter of the same type and size.

NOTE If you are unsure about the filter required for your system, call your Lennox dealer for assistance.

3.Reusable Filter Many indoor units are equipped with reusable foam filters. Clean foam filters with a mild soap and water solution; rinse thoroughly; allow filter to dry completely before returning it to the unit or grille.

NOTE The filter and all access panels must be in place any time the unit is in operation.

4.Indoor Unit The indoor unit’s evaporator coil is equipped with a drain pan to collect condensate formed as your system removes humidity from the inside air. Have your dealer show you the location of the drain line and how to check for obstructions. (This would also apply to an auxiliary drain, if installed.)

Thermostat Operation

See the thermostat homeowner manual for instructions on how to operate your thermostat.

Preservice Check

If your system fails to operate, check the following before calling for service:

SVerify room thermostat settings are correct.

SVerify that all electrical disconnect switches are ON.

SCheck for any blown fuses or tripped circuit breakers.

SVerify unit access panels are in place.

SVerify air filter is clean.

SIf service is needed, locate and write down the unit model number and have it handy before calling.

Page 27

XC16 SERIES

Image 27
Contents AIR Conditioner Table of ContentsGeneral Shipping and Packing ListTOP View Unit Dimensions − Inches mmModel Number Identification XXX 230 Side ViewPlumbing and Switches Components Typical Unit Parts ArrangementControl Panel Torque Requirements Operating Gauge Set and Service ValvesUsing Manifold Gauge SET Operating Service ValvesReinstall Stem Cap Operating Angle Type Service ValveOperating Ball Type Service Valve To Access Service Port2CONNECT Manifold Gauge SET Recovering Refrigerant from Existing SystemRefrigerant from System 1DISCONNECT Power Recovering RefrigerantPlacing Unit on Slab New Outdoor Unit PlacementClearance on ALL Sides Positioning ConsiderationsPlacement, Slab Mounting and Stabilizing Unit Detail a Outside Unit PlacementLouvered Panel Removal Removing and Installing PanelsLouvered Panel Installation Roof MountingNew or Replacement Line Set Refrigerant Line SETRefrigerant Line Set Refrigerant Line SET Alling Horizontal Runs Refrigerant Line SET From Vertical to HorizontalBrazing Connections 1CUT and Debur Brazing Procedures7PREPARATION for Next Step Wrap Service ValvesFlow Nitrogen 6BRAZE Line SETFlushing Line Set and Indoor Coil Installing Indoor Expansion ValveEqualizer Line Installation Installing Indoor Metering DeviceIndoor Expansion Valve Installation Sensing Bulb InstallationLeak Test Leak Test Line Set and Indoor CoilEvacuating System Evacuating Line Set and Indoor Coil24VAC Transformer Size Circuit and Install Disconnect2INSTALL Thermostat ElectricalTypical Unit Wiring Diagram Unit Start−Up Servicing Units Delivered Void of ChargeRequirements Connections for Testing and ChargingWhen to CHARGE? System RefrigerantChecking AIR Flow AT Indoor Coil Weigh in Charging MethodCalculating System Charge for Outdoor Unit Void of Charge Below AboveTWO−STAGE Compressor System OperationIndoor Coil MaintenanceUnit Components Indoor UnitHomeowner Outdoor Unit FAN Motor Start−Up and Performance ChecklistTemperature Compressor

Elite Series X16 Air Conditioner Units, 506637-01 specifications

The Lenox 506637-01, Elite Series X16 Air Conditioner is a top-tier cooling solution that stands out in the residential HVAC market. Known for its impressive energy efficiency and advanced features, this unit is designed to provide homeowners with exceptional comfort while also keeping energy bills in check.

One of the main highlights of the Elite Series X16 is its SEER rating, which stands at an impressive 16. This makes it one of the most energy-efficient air conditioning systems available, ensuring that it operates effectively without consuming excessive power. By converting less energy into cooling, homeowners can enjoy lower utility bills and a reduced carbon footprint.

The X16 model features a two-stage cooling system, which allows for better humidity control and more even temperature distribution throughout the home. Unlike standard single-stage units that operate at full capacity at all times, the two-stage system enables the air conditioner to run at a lower, more efficient speed for the majority of its operation, only ramping up when additional cooling is needed. This not only enhances comfort but also extends the lifespan of the unit.

Incorporating advanced technology, the Elite Series X16 utilizes a high-efficiency scroll compressor and innovative airflow design. This results in quieter operation, providing a peaceful indoor environment. The noise levels are minimal, making it suitable for nighttime use or for homes where noise might be a concern.

The air conditioner is built with durability in mind, featuring a robust cabinet that protects against the elements and potential wear and tear over time. Its louvered design provides additional protection for critical components, ensuring longevity and consistent performance.

Furthermore, the X16 is compatible with smart thermostats and home automation systems, allowing homeowners to optimize their cooling schedules remotely. This connectivity helps users make informed decisions about energy usage, further enhancing efficiency while providing ultimate control over home comfort.

In summary, the Lenox 506637-01, Elite Series X16 Air Conditioner provides an excellent blend of energy efficiency, advanced technology, and a focus on comfort and durability. With its two-stage cooling system, high SEER rating, and quiet operation, it is an ideal choice for those seeking a reliable, high-performance cooling solution for their homes.