Lenox Elite Series X16 Air Conditioner Units Electrical, 24VAC Transformer, 2INSTALL Thermostat

Page 19

IMPORTANT

Use a thermocouple or thermistor electronic vacuum gauge that is calibrated in microns. Use an instrument capable of accurately measuring down to 50 microns.

WARNING

Danger of Equipment Damage. Avoid deep vacuum operation. Do not use compressors to evacuate a system. Extremely low vacuums can cause internal arcing and compressor failure. Damage caused by deep vacuum operation will void warranty.

Evacuating the system of non−condensables is critical for proper operation of the unit. Non−condensables are defined as any gas that will not condense under

temperatures and pressures present during operation of an air conditioning system. Non−condensables and water suction combine with refrigerant to produce substances that corrode copper piping and compressor parts.

Electrical

In the U.S.A., wiring must conform with current local codes and the current National Electric Code (NEC). In Canada, wiring must conform with current local codes and the current Canadian Electrical Code (CEC).

Refer to the furnace or air handler installation instructions for additional wiring application diagrams and refer to unit nameplate for minimum circuit ampacity and maximum overcurrent protection size.

24VAC TRANSFORMER

Use the transformer provided with the furnace or air handler for low-voltage control power (24VAC − 40 VA minimum)

SIZE CIRCUIT AND INSTALL DISCONNECT

1ReferSWITCHto the unit nameplate for minimum circuit ampacity, and maximum fuse or circuit breaker (HACR per NEC). Install power wiring and properly sized disconnect switch.

MAIN FUSE

BOX/BREAKER

PANEL

DISCONNECT

SWITCH

2INSTALL THERMOSTAT

Install room thermostat (ordered separately) on an inside wall approximately in the center of the conditioned area and 5 feet (1.5m) from the floor. It should not be installed on an outside wall or where it can be affected by sunlight or drafts.

THERMOSTAT

5FEET (1.5M)

NOTE Units are approved for use only with copper conductors. Ground unit at disconnect switch or to an earth ground.

NOTE 24VAC, Class II circuit connections are made in the control panel.

3UNIT LOW VOLTAGE CONNECTIONS

 

C WIRE NUTS

BLUE

YELLOW

 

BLACK

CUTOUT WITH

AGROMMET

24V CONTROL WIRES B

HIGH VOLTAGE FIELD WIRING

FACTORY WIRING

LOW VOLTAGE (24V) FIELD WIRING

 

 

 

 

 

 

 

 

 

WIRE RUN LENGTH

AWG# INSULATION TYPE

 

 

 

 

LESS THAN 100’ (30 METERS)

18

TEMPERATURE RATING

 

 

 

MORE THAN 100’ (30 METERS)

16

35ºC MINIMUM.

 

 

 

 

 

 

 

 

ARun 24VAC control wires through cutout with grommet. B Run 24VAC control wires through wire tie.

C Make 24VAC control wire connections using field provided wire nuts.

D Tighten wire tie to security 24V control wiring.

NOTE − FOR PROPER VOLTAGES, SELECT THERMOSTAT WIRE (CONTROL WIRES) GAUGE PER TABLE ABOVE.

NOTE − WIRE TIE PROVIDES LOW VOLTAGE WIRE STRAIN RELIEF AND TO MAINTAIN SEPARATION OF FIELD INSTALLED LOW AND HIGH VOLTAGE CIRCUITS.

NOTE − DO NOT BUNDLE ANY EXCESS 24VAC CONTROL WIRES INSIDE CONTROL BOX.

DTIGHTEN WIRE TIE

Page 19

XC16 SERIES

Image 19
Contents AIR Conditioner Table of ContentsGeneral Shipping and Packing ListTOP View Unit Dimensions − Inches mmModel Number Identification XXX 230 Side ViewTypical Unit Parts Arrangement Plumbing and Switches ComponentsControl Panel Torque Requirements Operating Gauge Set and Service ValvesUsing Manifold Gauge SET Operating Service ValvesReinstall Stem Cap Operating Angle Type Service ValveOperating Ball Type Service Valve To Access Service Port2CONNECT Manifold Gauge SET Recovering Refrigerant from Existing SystemRefrigerant from System 1DISCONNECT Power Recovering RefrigerantPlacing Unit on Slab New Outdoor Unit PlacementClearance on ALL Sides Positioning ConsiderationsPlacement, Slab Mounting and Stabilizing Unit Detail a Outside Unit PlacementLouvered Panel Removal Removing and Installing PanelsLouvered Panel Installation Roof MountingRefrigerant Line SET New or Replacement Line SetRefrigerant Line Set Refrigerant Line SET Alling Horizontal Runs Refrigerant Line SET From Vertical to HorizontalBrazing Connections 1CUT and Debur Brazing Procedures7PREPARATION for Next Step Wrap Service ValvesFlow Nitrogen 6BRAZE Line SETFlushing Line Set and Indoor Coil Installing Indoor Expansion ValveEqualizer Line Installation Installing Indoor Metering DeviceIndoor Expansion Valve Installation Sensing Bulb InstallationLeak Test Leak Test Line Set and Indoor CoilEvacuating System Evacuating Line Set and Indoor Coil24VAC Transformer Size Circuit and Install Disconnect2INSTALL Thermostat ElectricalTypical Unit Wiring Diagram Unit Start−Up Servicing Units Delivered Void of ChargeRequirements Connections for Testing and ChargingWhen to CHARGE? System RefrigerantWeigh in Charging Method Checking AIR Flow AT Indoor CoilCalculating System Charge for Outdoor Unit Void of Charge Below AboveTWO−STAGE Compressor System OperationIndoor Coil MaintenanceUnit Components Indoor UnitHomeowner Outdoor Unit FAN Motor Start−Up and Performance ChecklistTemperature Compressor

Elite Series X16 Air Conditioner Units, 506637-01 specifications

The Lenox 506637-01, Elite Series X16 Air Conditioner is a top-tier cooling solution that stands out in the residential HVAC market. Known for its impressive energy efficiency and advanced features, this unit is designed to provide homeowners with exceptional comfort while also keeping energy bills in check.

One of the main highlights of the Elite Series X16 is its SEER rating, which stands at an impressive 16. This makes it one of the most energy-efficient air conditioning systems available, ensuring that it operates effectively without consuming excessive power. By converting less energy into cooling, homeowners can enjoy lower utility bills and a reduced carbon footprint.

The X16 model features a two-stage cooling system, which allows for better humidity control and more even temperature distribution throughout the home. Unlike standard single-stage units that operate at full capacity at all times, the two-stage system enables the air conditioner to run at a lower, more efficient speed for the majority of its operation, only ramping up when additional cooling is needed. This not only enhances comfort but also extends the lifespan of the unit.

Incorporating advanced technology, the Elite Series X16 utilizes a high-efficiency scroll compressor and innovative airflow design. This results in quieter operation, providing a peaceful indoor environment. The noise levels are minimal, making it suitable for nighttime use or for homes where noise might be a concern.

The air conditioner is built with durability in mind, featuring a robust cabinet that protects against the elements and potential wear and tear over time. Its louvered design provides additional protection for critical components, ensuring longevity and consistent performance.

Furthermore, the X16 is compatible with smart thermostats and home automation systems, allowing homeowners to optimize their cooling schedules remotely. This connectivity helps users make informed decisions about energy usage, further enhancing efficiency while providing ultimate control over home comfort.

In summary, the Lenox 506637-01, Elite Series X16 Air Conditioner provides an excellent blend of energy efficiency, advanced technology, and a focus on comfort and durability. With its two-stage cooling system, high SEER rating, and quiet operation, it is an ideal choice for those seeking a reliable, high-performance cooling solution for their homes.