Raypak 241275 manual Troubleshooting, Elodrive Actuator Rotation Knob Setting

Page 7

Fig. 8: Elodrive Actuator — Rotation Knob Setting

Fig. 9: Elodrive Actuator — Actuator Shown in Full

System Flow Position

NOTE: Elodrive actuator is Nema 4 rated.

TROUBLESHOOTING

Check your power source using a Volt-Ohm meter; check the following voltages at TB1 terminal block:

TB1-1 to TB1-2 = 108 VAC Minimum, 132 VAC Maximum

TB1-1 to TB1-3 = 108 VAC Minimum, 132 VAC Maximum

TB1-2 to TB1-3 = Must be less than .6 VAC

IF CALL FOR HEAT LED does not illuminate when the heater has a CFH signal, check for 24VAC at the heater CPW Board (J17-TRIG) output. If voltage is present, check wiring using the wiring diagram. If volt- age is not present, the problem exists in the heater.

IF VALVE DOES NOT MOVE: Check for voltage out at

TB2-1: Should be a 1VDC to 10VDC output to the actuator valve. If no voltage is present, check for volt- age at TB2-3, there should be a 12VDC signal. If the 12VDC signal is not present, verify that the converter is wired correctly using the wiring diagram.

IF SENSOR OUT OF RANGE LED is illuminated: The set point temperature has not been reached within the 7 minute time period.

Push the Reset Switch (see Fig. 4) or remove power and watch for proper operation.

Check pump sizing and valve/piping sizing and cor- rect as necessary.

Replace sensor.

Check wiring using wiring diagram.

7

Image 7
Contents Installation and Operating Instructions Page Time/Temperature Relationships in Scalds General SafetyCold Water Start InstallationOperation Connecting Power to the ControllerCold Start Sequence Operation Mode Selection SwitchElodrive Actuator Rotation Knob Setting TroubleshootingCold Water Start Troubleshooting Guide Wiring Diagram Cold Water RUN Model Pump Injection & Heater Pump Comparison Hi DeltaBefore Starting Injection Pump Cover InstallationPlace the cover on the pump Typical Boiler Piping Hi Delta shown Sequence of Operation START-UP ProcedureWiring Diagram Step Cold Water Run Troubleshooting GuideCold Water Start Illustrated Parts ListsCall OUT Description HI Delta MVB Cold Water Run Call Description HI Delta MVB OUT