Mounting

On vertical vents, the vent damper may be mounted with the actuator in any position. On horizontal vents, do not mount the actuator either directly above or directly below the vent pipe; mount the vent damper actuator to the side of the vent.

The vent damper is set up for a continuous pilot sys- tem. If the vent damper is installed on a system with an Intermittent Pilot, the energy savings of the vent damper can be improved by plugging the hole in the vent damper blade using the knockout plug provided in the parts envelope.

Hole in Vent Damper Blade Closed Position

DO NOT plug the hole if installing the vent damper on a continuous pilot system as this will create a haz- ardous condition.Fig. 8: Vent Damper

Fig. 9: Installing The Vent Damper in Horizontal

& Vertical Vents

Fig. 10: D80D General Wiring Diagram

Install the vent damper to service only the single appliance for which it is intended. If improperly installed, a hazardous condition, such as an explo- sion or carbon monoxide poisoning, could result.

Vent Damper Operation

For safe, efficient operation, the vent damper and all flue-product-carrying areas of the appliance must be checked annually, with particular attention given to deterioration from corrosion or other sources.

Check vent damper operation as follows:

1.When the boiler is off, check that the vent damper position indicator points to the closed position (see Fig. 11).

Damper Position Indicator

Damper OpenDamper Closed

Fig. 11: Vent Damper Position Indicator

12

Image 12
Contents Raytherm Residential Boilers Page Contents Pay Attention to These Terms PropositionGeneral Specifications Receiving EquipmentInput Heating Net Piping Connections CapacityGas NPT RatingInstallation Code RequirementsMounting Base Clearance RequirementsCombustion/Ventilation Air Model No Sq. in. of Free AreaModel No Model No Vent Max Connector Horizontal Diameter Length ft Venting ConnectionsCommon Vents Roof Pitch X/12 Min. ftVent Damper Installation Location Vent Damper LocationMounting Vent Damper OperationFlair Damper AbbreviationDescriptionVent Damper Gas Supply Connections Gas PressureWater Connections & System Piping Model No System Flow Max. System Gpm Head ft/WC Piping Diagrams Single-Zone PipingElectrical Wiring Wiring Diagrams Page Page Single-Zone Taco Valve System with Three 3 Zone Pumps Primary/Secondary Pumping System Honeywell Zone Valve IID Units with Low Water Cut-off Device Servicing Procedures Sequence OperationGeneral Location of Controls Intermittent Ignition Device IIDSTART-UP Procedures Lighting the BoilerFor Standing Pilot Models Filling the SystemTo Turn Off Gas to the Boiler Models 90, 135 For Automatic Ignition ModelsShut-down Procedure To Turn Off Gas to the BoilerFor Honeywell valve Turn gas control knob For Honeywell valveTesting the Ignition Safety Shut-off Safe Shut-down TestsInspection Procedures Low Water Cut-Off When InstalledProcedure for Cleaning Flue Gas Passageways BurnersRepair Procedures Tube Cleaning Procedure TypicalHeat Exchanger Removal Burner Tray RemovalHeat Exchanger Re-assembly Combustion Chamber RemovalTroubleshooting Problem Causes SolutionsPiping Adjustment & Replacement of Components Replacement Parts List Fast-Response Temperature Sensor Module ReplacementFast-Response Temperature Sensor Probe Replacement Circulator ReplacementLimited Parts Warranty