Raypak 0042B, 0066B, 0180B To Turn Off Gas to the Boiler, Shut-down Procedure, For Honeywell valve

Page 29

technician. Force or attempted repair may result in a fire or explosion.

D.Do not use this boiler if any part has been under water. Immediately call a qualified service techni- cian to inspect the boiler and to replace any part of the control system and any gas control which has been under water.

For Intermittent Ignition (IID) with Honeywell or Robertshaw Gas Valve (All Models)

1.STOP! Read the previous safety information.

2.Set the thermostat to the lowest setting.

3.Turn off all electrical power to the appliance.

4.This boiler is equipped with an ignition device which automatically lights the pilot. Do not try to light the pilot by hand.

GASCONTROL

KNOBSHOWN

IN"OFF"

POSITION

GASINLET

HONEYWELL

(Models 30 - 90)

Fig. 29: Honeywell Gas Valve

5.For Honeywell valve: Turn gas control knob

clockwise to "Off".

For Robertshaw valve: Push in and move gas control lever to "Off" position.

6.Wait 5 minutes to clear out any gas. Then smell for gas, including near the floor. If you smell gas, STOP! Follow "B" in the safety information on the label affixed to the front of the unit. If you don't smell gas, go to the next step.

7.For Honeywell valve: turn gas control counter-

clockwise to "On".

For Robertshaw valve: Move gas control lever to "On" position.

GAS CONTROL

KNOB SHOWN

IN "OFF"

POSITION

GAS INLET

ROBERTSHAW

(All Models)

Fig. 30: Robertshaw Gas Valve

8.Turn on all electrical power to the boiler.

9.Set thermostat to desired setting.

10.If the boiler will not operate, follow the instructions "To Turn Off Gas To Boiler" and call your service technician or gas supplier.

To Turn Off Gas to the Boiler

1.Set the thermostat at the lowest setting.

2.Turn off all electrical power to the boiler if service is to be performed.

3.For Honeywell valve:

Turn gas control knob clockwise to "Off". Make sure knob rest against stop.

For Robertshaw valve:

Push in and move gas control lever to "Off" position.

HONEYWELL PILOT

Fig. 31: Honeywell Pilot

Shut-down Procedure

To prevent freeze damage to the heating system, it is recommended that the following system shut-down procedure be performed.

1.Set the room thermostat to "OFF" or the lowest setting.

2.Turn off all electrical switches to the boiler.

29

Image 29
Contents Raytherm Residential Boilers Page Contents Proposition Pay Attention to These TermsReceiving Equipment General SpecificationsCapacity Input Heating Net Piping ConnectionsGas NPT RatingCode Requirements InstallationMounting Base Clearance RequirementsModel No Combustion/Ventilation AirModel No Sq. in. of Free Area Venting Connections Model No Vent Max Connector Horizontal Diameter Length ftRoof Pitch X/12 Min. ft Common VentsVent Damper Location Vent Damper Installation LocationVent Damper Operation MountingAbbreviationDescription Flair DamperVent Damper Water Connections & System Piping Gas Supply ConnectionsGas Pressure Model No System Flow Max. System Gpm Head ft/WC Single-Zone Piping Piping DiagramsElectrical Wiring Wiring Diagrams Page Page Single-Zone Taco Valve System with Three 3 Zone Pumps Primary/Secondary Pumping System Honeywell Zone Valve IID Units with Low Water Cut-off Device Sequence Operation Servicing ProceduresGeneral Location of Controls Intermittent Ignition Device IIDLighting the Boiler START-UP ProceduresFor Standing Pilot Models Filling the SystemFor Automatic Ignition Models To Turn Off Gas to the Boiler Models 90, 135To Turn Off Gas to the Boiler Shut-down ProcedureFor Honeywell valve Turn gas control knob For Honeywell valveSafe Shut-down Tests Testing the Ignition Safety Shut-offLow Water Cut-Off When Installed Inspection ProceduresProcedure for Cleaning Flue Gas Passageways BurnersTube Cleaning Procedure Typical Repair ProceduresHeat Exchanger Removal Burner Tray RemovalCombustion Chamber Removal Heat Exchanger Re-assemblyProblem Causes Solutions TroubleshootingPiping Adjustment & Replacement of Components Fast-Response Temperature Sensor Module Replacement Replacement Parts ListFast-Response Temperature Sensor Probe Replacement Circulator ReplacementLimited Parts Warranty