Raypak 0180B, 0066B To Turn Off Gas to the Boiler Models 90, 135, For Automatic Ignition Models

Page 28

For Standing Pilot Models with Robertshaw Gas Valve, 2-stage Operation

(Models 90, 135 & 180)

1.STOP! Read the safety information.

2.Set the thermostat to the lowest setting.

3.Turn off all electrical power to the boiler.

4.Push in and move gas control lever counter-

clockwise to "OFF" position.

GAS CONTROL

LEVER SHOWN

IN "OFF" POSITION

GAS INLET

Fig. 27: Gas Valve

NOTE: Lever cannot be moved from "ON" to "OFF" unless lever is pushed in slightly. Do not force.

5.Wait five (5) minutes to clear out any gas. Then smell for gas, including near the floor. If you smell gas, STOP! Follow "B" in the safety information on the label affixed to the unit. If you don't smell gas, go to the next step.

6.Locate pilot mounted on the right side of the burner tray, and right of first burner.

HONEYWELL PILOT

ROBERTSHAW PILOT

Fig. 28: Pilots

7.Move control lever clockwise to "SET" position and immediately light pilot with a match.

8.Hold lever in "SET" position for 1/2 minute after pilot is lit. Release lever, and it will spring back to "PILOT" position. Pilot should remain lit. If it goes out, repeat steps 4 through 8.

*If lever does not spring back to "PILOT" position when released, stop and immediately call your service technician or gas supplier.

*If the pilot does not stay lit after several tries,

move the gas control lever to "OFF" and call your service technician or gas supplier.

9.Stand to the side of the boiler and move the gas

10.Turncontrolonleverall electricalcounter-powerclockwiseto the boiler. to "ON".

11.Set the thermostat to the desired setting.

To Turn Off Gas to the Boiler (Models 90, 135 & 180)

1.Set the thermostat to the lowest setting.

2.Turn off all electrical power to the boiler

3.Push in and move gas control lever counter-

clockwise

to "OFF" position. Do not force.

For Automatic Ignition Models

Please read carefully and understand the following safety information before operating the boiler.

WARNING: If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life.

A.This boiler is equipped with an ignition device which automatically lights the pilot. Do not try to light the pilot by hand; or this boiler may not have a pilot and is equipped with a hot surface ignition device which automatically lights the burners. Do not try to light the burners by hand.

B.BEFORE OPERATING smell all around the boiler area for gas. Be sure to smell next to the floor because some gases are heavier than air and will settle on the floor.

WHAT TO DO IF YOU SMELL GAS

• Do not try to light any appliance.

• Do not touch any electrical switch.

• Do not use any phone in your building.

• Immediately call your gas supplier from a neigh- bor's phone. Follow the gas supplier's instructions.

• If you cannot reach your gas supplier, call the fire department.

C.Use only your hand to push in, move or turn the gas control knob or lever. Never use tools. If the knob or lever will not push in, move or turn by hand don't try to repair it, call a qualified service

28

Image 28
Contents Raytherm Residential Boilers Page Contents Pay Attention to These Terms PropositionGeneral Specifications Receiving EquipmentInput Heating Net Piping Connections CapacityGas NPT RatingInstallation Code RequirementsMounting Base Clearance RequirementsModel No Sq. in. of Free Area Combustion/Ventilation AirModel No Model No Vent Max Connector Horizontal Diameter Length ft Venting ConnectionsCommon Vents Roof Pitch X/12 Min. ftVent Damper Installation Location Vent Damper LocationMounting Vent Damper OperationFlair Damper AbbreviationDescriptionVent Damper Gas Pressure Gas Supply ConnectionsWater Connections & System Piping Model No System Flow Max. System Gpm Head ft/WC Piping Diagrams Single-Zone PipingElectrical Wiring Wiring Diagrams Page Page Single-Zone Taco Valve System with Three 3 Zone Pumps Primary/Secondary Pumping System Honeywell Zone Valve IID Units with Low Water Cut-off Device Servicing Procedures Sequence OperationGeneral Location of Controls Intermittent Ignition Device IIDSTART-UP Procedures Lighting the BoilerFor Standing Pilot Models Filling the SystemTo Turn Off Gas to the Boiler Models 90, 135 For Automatic Ignition ModelsShut-down Procedure To Turn Off Gas to the BoilerFor Honeywell valve Turn gas control knob For Honeywell valveTesting the Ignition Safety Shut-off Safe Shut-down TestsInspection Procedures Low Water Cut-Off When InstalledProcedure for Cleaning Flue Gas Passageways BurnersRepair Procedures Tube Cleaning Procedure TypicalHeat Exchanger Removal Burner Tray RemovalHeat Exchanger Re-assembly Combustion Chamber RemovalTroubleshooting Problem Causes SolutionsPiping Adjustment & Replacement of Components Replacement Parts List Fast-Response Temperature Sensor Module ReplacementFast-Response Temperature Sensor Probe Replacement Circulator ReplacementLimited Parts Warranty