Raypak 0180B, 0066B, 0042B manual Model No System Flow Max. System Gpm Head ft/WC

Page 16

shipped loose. The full open position is appropriate for most systems, and ensures adequate flow through the boiler.

If system flow is inadequate, (indicated by excessive temperature drop through the system) the bypass valve can be throttled slightly. Care must be taken against over-throttling which may lead to inadequate flow through the boiler and boiler harmonics (a hum- ming sound from the heat exchanger).

If adequate system flow cannot be obtained without causing harmonics, an additional pump is required. The factory-mounted circulator will provide adequate water flow for systems designed at a 20°F temperature drop, and system pressure drop or head not exceed- ing that which is shown in Table J.

Model No.

System Flow

Max. System

(gpm)

Head (ft/WC)

H-0042

3.5

8.0

H-0066

5.3

8.5

H-0090

7.3

6.5

H-0135

11.0

10.0

H-0180

14.6

7.0

Table J: System Pressure Drop

When the total system head exceeds the available head pressures, a primary/secondary pumping system is recommended.

The minimum boiler operating temperature should be 105°F. When operating at low temperature applica- tions, ∆T (temperature rise) must be 20°F or less.

Propylene glycol solution is commonly used in the heating system when freeze protection is required. This will affect the system design and pump perform- ance. As a rule of thumb, 50% solution of propylene glycol will require the system flow (gpm) to increase by 14%, and the system head (ft/WC) by 23% in order to maintain the same heat transfer load.

Systems with multiple zones may require an addition- al circulator. Consult manufacturer's data for valve pressure drops. When an indirect water heating sys- tem is used, it is recommended that a separate circulator be installed to meet the required flow and pressure drop conditions of the indirect water heater. We recommend that the make-up water from the cold water line have a check valve, gate valve, and feedwa- ter regulator set at 12 psi. Install unions and gate or ball valves at inlet and outlet connections at the boiler to facilitate servicing.

The pressure relief valve is mounted on the boiler and must be piped to a drain. We recommend that all high points be vented and that purge valves be installed. A boiler installed above radiation level must be provided with a low water cut-off device. See page 27 for wiring hook-up.

The boiler, when used in connection with a refrigera- tion system, must be installed so that the chilled medium is piped in parallel with the boiler with appro- priate valves to prevent the chilled medium from entering the boiler.

The boiler piping system of a hot water heating boiler, that is connected to heating coils located in air han- dling units where they may be exposed to refrigerated air circulation, must be equipped with flow control valves or other automatic means to prevent gravity cir- culation of the boiler water during the cooling cycle.

A diaphragm expansion tank should be installed in the return line. A typical 8"-diameter expansion tank can be used on models H-0042, and H-0066, and an 11"- diameter expansion tank can be used on models H-0090, H-0135 and H-0180. Consult tank manufac- turer for correct sizing.

16

Image 16
Contents Raytherm Residential Boilers Page Contents Pay Attention to These Terms PropositionGeneral Specifications Receiving EquipmentInput Heating Net Piping Connections CapacityGas NPT RatingInstallation Code RequirementsMounting Base Clearance RequirementsModel No Sq. in. of Free Area Combustion/Ventilation AirModel No Model No Vent Max Connector Horizontal Diameter Length ft Venting ConnectionsCommon Vents Roof Pitch X/12 Min. ftVent Damper Installation Location Vent Damper LocationMounting Vent Damper OperationFlair Damper AbbreviationDescriptionVent Damper Gas Pressure Gas Supply ConnectionsWater Connections & System Piping Model No System Flow Max. System Gpm Head ft/WC Piping Diagrams Single-Zone PipingElectrical Wiring Wiring Diagrams Page Page Single-Zone Taco Valve System with Three 3 Zone Pumps Primary/Secondary Pumping System Honeywell Zone Valve IID Units with Low Water Cut-off Device Servicing Procedures Sequence OperationGeneral Location of Controls Intermittent Ignition Device IIDSTART-UP Procedures Lighting the BoilerFor Standing Pilot Models Filling the SystemTo Turn Off Gas to the Boiler Models 90, 135 For Automatic Ignition ModelsShut-down Procedure To Turn Off Gas to the BoilerFor Honeywell valve Turn gas control knob For Honeywell valveTesting the Ignition Safety Shut-off Safe Shut-down TestsInspection Procedures Low Water Cut-Off When InstalledProcedure for Cleaning Flue Gas Passageways BurnersRepair Procedures Tube Cleaning Procedure TypicalHeat Exchanger Removal Burner Tray RemovalHeat Exchanger Re-assembly Combustion Chamber RemovalTroubleshooting Problem Causes SolutionsPiping Adjustment & Replacement of Components Replacement Parts List Fast-Response Temperature Sensor Module ReplacementFast-Response Temperature Sensor Probe Replacement Circulator ReplacementLimited Parts Warranty
Related manuals
Manual 39 pages 210 b