Maytag HRN31275P, HRN11250P, HRP31250P, HRP31240P, HRP11275P manual Temperature-Pressure Relief Valve

Page 16

Secure all insulation using tape.

FIGURE 23.

Temperature-Pressure Relief Valve

Temperature-pressure relief valve must comply with ANSI Z21.22 and ASME code.

Properly sized temperature-relief valve must be installed in opening provided.

Can result in overheating and excessive tank pressure.

Can cause serious injury or death.

must not be blocked or reduced in size under any circumstances. Excessive length, over 30 feet (9.14 m), or use of more than four elbows can cause restriction and reduce the discharge capacity of the valve, see Figure 24.

No valve or other obstruction is to be placed between the relief valve and the tank. Do not connect tubing directly to discharge drain unless a 6 inch air gap is provided. To prevent bodily injury, hazard to life, or property damage, the relief valve must be allowed to discharge water in quantities should circumstances demand. If the discharge pipe is not connected to a drain or other suitable means, the water flow may cause property damage.

This heater is provided with a properly certified combination temperature - pressure relief valve by the manufacturer.

The valve is certified by a nationally recognized testing laboratory that maintains periodic inspection of production of listed equipment of materials as meeting the requirements for Relief Valves and Automatic Gas Shut-off Devices for Hot Water Supply Systems, ANSI Z21.22 and the code requirements of ASME.

If replaced, the valve must meet the requirements of local codes, but not less than a combination temperature and pressure relief valve certified as indicated in the above paragraph.

The valve must be marked with a maximum set pressure not to exceed the marked hydrostatic working pressure of the water heater (150 psi = 1,035 kPa) and a discharge capacity not less than the water heater input rate as shown on the model rating plate.

For safe operation of the water heater, the relief valve must not be removed from its designated opening nor plugged.

The temperature-pressure relief valve must be installed directly into the fitting of the water heater designed for the relief valve. Position the valve downward and provide tubing so that any discharge will exit only within 6 inches (153 mm) above, or at any distance below the structural floor. Be certain that no contact is made with any live electrical part. The discharge opening

FIGURE24.

The Discharge Pipe:

Shall not be smaller in size than the outlet pipe size of the valve, or have any reducing couplings or other restrictions.

Shall not be plugged or blocked.

Shall be of material listed for hot water distribution.

Shall be installed so as to allow complete drainage of both the temperature-pressure relief valve, and the discharge pipe.

Shall terminate at an adequate drain.

Shall not have any valve between the relief valve and tank.

16

Image 16
Contents Series Twelve Safe INSTALLATION, USE and Service Important DefinitionsSafety Precautions Table of Contents To Install or Operate the Water Heater Product SpecificationsCustomer Responsibilities Accessories and Tools Needed AccessoriesAdditional Tools Needed When Sweat Soldering ToolsInstructions for Installation Removing the Old Water HeaterTypical Installation Thermostat Pilot & Main BurnerMixing Valve Usage Locating the NEW Water Heater Facts to Consider About the LocationCombustion Air and Ventilation VentingclearancesVenting Through Roof Clearances Insulation Blankets ALL AIR from Inside BuildingsWater Piping Valve and Pipe Insulation Temperature-Pressure Relief Valve Wiring Filling the Water HeaterWiring Diagram USE Without Power CordVenting Throughan Outside Wall VentingGallon 70,000 and 75,000 BTU/HR Models only Optional 4 Vent Piping ALL 40 and 50 Gallon 40,000 BTU/HR Models onlyVenting System Example Installations For ALL Models 50 Gallon 40,000 BTU/HR Models Optional 4 Vent Piping DIA. Vent NumberofALL 40 and 50 Gallon 40,000 BTH/HR Models only DIA. Vent NumberofApproximate Setting Time for ALL 40 and 50 Gallon 40,000 BTU/HR ModelsCementing PVC, ABS or Cpvc Pipe and Fittings Movement CompleteConnecting PVC, ABS or Cpvc Pipe Vent to Blower Venting Through a Roof ALL ModelsALL 40 and 50 Gallon 40,000 BTH/HR Models only Gas Piping GAS Piping with Flexible Connector Sediment TrapsBefore the Water Heater will Operate Operating InstructionsOperation Temperature Regulation OperatingCheck for Leaks Water Heating Ignition SequenceTime to Produce For Your Safety Read Before Lighting Service and Maintenance Tank Sediment CleaningBurner Cleaning Vent System InspectionGas Control Valve & Burner Assembly Replacement Information Anode Rod InspectionDraining HousekeepingDrain Valve Washer Replacement Temperature-Pressure Relief Valve OperationService Start Up Conditions TroubleshootingOperational Conditions High Temperature Limit Switch Single-Use Type Energy Cut Off Leakage Checkpoints Troubleshooting YESSystem Check Problem Cause Solution Repair Parts List Maytag GAS Water HeatersKey Model Numbers Part Description HRN11250P HRN31250P Key Model Numbers Part Description HRN11275P HRN31275P MAYTAG/STATE Part Number Conversion KEY Page Page Page Warranty