Maytag HRP31240P, HRN11250P, HRP31250P, HRP11275P, HRN31275P, HRN31250P, HRN31240P manual Gas Piping

Page 26

ALL 40 AND 50 GALLON 40,000 BTH/HR MODELS ONLY -

OPTIONAL 2” VENT PIPING

2” DIA. VENT

NUMBEROF

MAX. LENGTH (FT.)

90o ELBOWS*

50

1

45

2

40

3

35

4

30

5

25

6

*Two 45o elbows are equivalent to one 90o elbow.

One 90o elbow equals 5 feet of equivalent vent length.

Gas Piping

Make sure the gas supplied is the same type listed on the model rating plate. The inlet gas pressure must not exceed 14 inch water column (2.6kPa) for natural and propane (L.P.) gas. The minimum inlet gas pressure listed on the rating plate is for the purpose of input adjustment. If the gas control valve is subjected to pressures exceeding 1/2 pound per square inch (3.5kPa), the damage to the gas control valve could result in a fire or explosion from leaking gas.

If the main gas line Shut-off serving all gas appliances is used, also turn “OFF” the gas at each appliance. Leave all gas appliances shut “OFF” until the water heater installation is complete.

A gas line of sufficient size must be run to the water heater. Consult the current edition of National Fuel Gas Code ANSI Z223.1/NFPA 54 and your gas supplier concerning pipe size.

There must be:

A readily accessible manual shut off valve in the gas supply line serving the water heater, and

A drip leg (sediment trap) ahead of the gas control valve to help prevent dirt and foreign materials from entering the gas control valve.

A flexible gas connector or a ground joint union between the shut off valve and control valve to permit servicing of the unit.

Be sure to check all the gas piping for leaks before lighting the water heater. Use a soapy water solution, not a match or open flame. Rinse off soapy solution and wipe dry.

The minimum inlet gas pressure shown on the rating plate is that which will permit firing at the rated input.

If a standard model is installed above 3,300 feet (1,006 m) or a high altitude model is installed above 5,500 feet (1,676 m) the input rating should be reduced at the rate of 4 percent for each 1,000 feet (305 m ) above sea level which requires replacement of the burner orifice in accordance with National Fuel Gas Code ANSI Z223.1/NFPA 54. Contact Maytag Customer Service

Center at 1-800-788-8899 or your local gas supplier or call for further information.

Failure to replace the standard orifice with a high altitude orifice when installed at elevations above 3,300 feet (1,006 m) or above 5,500 feet (1,676 m) for high altitude model could result in improper and inefficient operation of the appliance, producing carbon monoxide gas in excess of safe limits, which could result in serious injury or death. Contact Maytag Customer

Service at 1-800-788-8899 or your local gas supplier for any specific changes which may be required in your area.

Use pipe joint compound or teflon tape marked as being resistant to the action of petroleum (Propane [L.P.]) gases.

The appliance and its gas connection must be leak tested before placing the appliance in operation.

The appliance and its individual Shut-off valve shall be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 pound per square inch (3.5kPa). It shall be isolated from the gas supply piping system by closing its individual manual Shut-off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 pound per square inch (3.5kPa).

Connecting the gas piping to the gas control valve of the water heater can be accomplished by either of the two methods, shown in Figures 49 and 50.

26

Image 26
Contents Series Twelve Safe INSTALLATION, USE and Service Important DefinitionsSafety Precautions Table of Contents Customer Responsibilities Product SpecificationsTo Install or Operate the Water Heater Additional Tools Needed When Sweat Soldering Accessories and Tools NeededAccessories ToolsInstructions for Installation Removing the Old Water HeaterTypical Installation Thermostat Pilot & Main BurnerMixing Valve Usage Locating the NEW Water Heater Facts to Consider About the LocationCombustion Air and Ventilation VentingclearancesVenting Through Roof Clearances Insulation Blankets ALL AIR from Inside BuildingsWater Piping Valve and Pipe Insulation Temperature-Pressure Relief Valve Wiring Filling the Water HeaterWiring Diagram USE Without Power CordGallon 70,000 and 75,000 BTU/HR Models only VentingVenting Throughan Outside Wall Optional 4 Vent Piping ALL 40 and 50 Gallon 40,000 BTU/HR Models onlyVenting System Example Installations For ALL Models ALL 40 and 50 Gallon 40,000 BTH/HR Models only 50 Gallon 40,000 BTU/HR ModelsOptional 4 Vent Piping DIA. Vent Numberof DIA. Vent Numberof Cementing PVC, ABS or Cpvc Pipe and Fittings Approximate Setting Time for ALL 40 and 50 Gallon 40,000 BTU/HR Models Movement CompleteConnecting PVC, ABS or Cpvc Pipe Vent to Blower Venting Through a Roof ALL ModelsALL 40 and 50 Gallon 40,000 BTH/HR Models only Gas Piping GAS Piping with Flexible Connector Sediment TrapsOperation Operating InstructionsBefore the Water Heater will Operate Check for Leaks Temperature RegulationOperating Water Heating Ignition SequenceTime to Produce For Your Safety Read Before Lighting Burner Cleaning Service and MaintenanceTank Sediment Cleaning Vent System InspectionDraining Gas Control Valve & Burner Assembly Replacement InformationAnode Rod Inspection HousekeepingService Temperature-Pressure Relief Valve OperationDrain Valve Washer Replacement Operational Conditions TroubleshootingStart Up Conditions High Temperature Limit Switch Single-Use Type Energy Cut Off Leakage Checkpoints Troubleshooting YESSystem Check Problem Cause Solution Repair Parts List Maytag GAS Water HeatersKey Model Numbers Part Description HRN11250P HRN31250P Key Model Numbers Part Description HRN11275P HRN31275P MAYTAG/STATE Part Number Conversion KEY Page Page Page Warranty