Maytag HRP31240P, HRN11250P, HRP31250P, HRP11275P, HRN31275P, HRN31250P manual Troubleshooting, Yes

Page 38

TROUBLESHOOTING (Continued)

This troubleshooting guide has been supplied for use by qualified service personnel who have a complete understanding of both electricity and gas.

Label all wiring before disconnecting any wiring; to ensure correct reconnection. Failure to follow this instruction could cause improper and possible dangerous operation, resulting in DEATH, SERIOUS BODILY INJURY, OR PROPERTY DAMAGE.

THERMOSTAT AND GAS SUPPLY CHECK

NO

Turn “ON” gas supply.

Is gas being supplied to the thermostat?

YES

Is thermostat calling for heat? Run (HOT) water from heater and set adjustment button higher. Check using a manometer at thermostat pressure tap.

YES

Call gas company to increase gas pressure.

Is there a minimum gas pressure 4” W.C. for natural gas or 10” W.C. for propane (L.P.) gas?

NO

YES

GO TO SYSTEM CHECK

SECTION, PAGE 39.

38

Image 38
Contents Series Twelve Safe INSTALLATION, USE and Service Important DefinitionsSafety Precautions Table of Contents Customer Responsibilities Product SpecificationsTo Install or Operate the Water Heater Additional Tools Needed When Sweat Soldering Accessories and Tools NeededAccessories ToolsInstructions for Installation Removing the Old Water HeaterTypical Installation Thermostat Pilot & Main BurnerMixing Valve Usage Locating the NEW Water Heater Facts to Consider About the LocationCombustion Air and Ventilation VentingclearancesVenting Through Roof Clearances Insulation Blankets ALL AIR from Inside BuildingsWater Piping Valve and Pipe Insulation Temperature-Pressure Relief Valve Wiring Filling the Water HeaterWiring Diagram USE Without Power CordGallon 70,000 and 75,000 BTU/HR Models only VentingVenting Throughan Outside Wall Optional 4 Vent Piping ALL 40 and 50 Gallon 40,000 BTU/HR Models onlyVenting System Example Installations For ALL Models ALL 40 and 50 Gallon 40,000 BTH/HR Models only 50 Gallon 40,000 BTU/HR ModelsOptional 4 Vent Piping DIA. Vent Numberof DIA. Vent NumberofCementing PVC, ABS or Cpvc Pipe and Fittings Approximate Setting Time forALL 40 and 50 Gallon 40,000 BTU/HR Models Movement CompleteConnecting PVC, ABS or Cpvc Pipe Vent to Blower Venting Through a Roof ALL ModelsALL 40 and 50 Gallon 40,000 BTH/HR Models only Gas Piping GAS Piping with Flexible Connector Sediment TrapsOperation Operating InstructionsBefore the Water Heater will Operate Check for Leaks Temperature RegulationOperating Water Heating Ignition SequenceTime to Produce For Your Safety Read Before Lighting Burner Cleaning Service and MaintenanceTank Sediment Cleaning Vent System InspectionDraining Gas Control Valve & Burner Assembly Replacement InformationAnode Rod Inspection HousekeepingService Temperature-Pressure Relief Valve OperationDrain Valve Washer Replacement Operational Conditions Troubleshooting Start Up Conditions High Temperature Limit Switch Single-Use Type Energy Cut Off Leakage Checkpoints Troubleshooting YESSystem Check Problem Cause Solution Repair Parts List Maytag GAS Water HeatersKey Model Numbers Part Description HRN11250P HRN31250P Key Model Numbers Part Description HRN11275P HRN31275P MAYTAG/STATE Part Number Conversion KEY Page Page Page Warranty