Maytag HV650HBVITCGA, HV640YBVITCGA, HV650YBVITCGA, HV640HBVITCGA ALL AIR from Inside Buildings See

Page 12

Chemical vapor corrosion of the flue, blower assembly and vent system may occur if air for combustion contains certain chemical vapors. Spray can propellants, cleaning solvents, refrigerator and air conditioner refrigerants, swimming pool chemicals, calcium and sodium chloride, waxes, bleach and process chemicals are typical compounds which are potentially corrosive.

A. ALL AIR FROM INSIDE BUILDINGS: (See Figure 11 and 12)

The confined space shall be provided with two permanent openings communicating directly with an additional room(s) of sufficient volume so that the combined volume of all spaces meets the criteria for an unconfined space. The total input of all gas utilization equipment installed in the combined space shall be considered in making this determination. Each opening shall have a minimum free area of one square inch per 1,000 Btu per hour (22 cm2/kW) of the total input rating of all gas utilization equipment in the confined space, but not less than 100 square inches (645 cm2). One opening shall commence within 12 inches (31 cm) of the top and one commencing within 12 inches (31 cm) of the bottom of the enclosures.

FIGURE12.

B. ALL AIR FROM OUTDOORS: (See Figures 13, 14 and 15)

The confined space shall be provided with two permanent openings, one commencing within 12 inches (31 cm) of the top and one commencing within 12 inches (31 cm) from the bottom of the enclosure. The openings shall communicate directly, or by ducts, with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors.

1.When directly communicating with the outdoors, each opening shall have a minimum free area of 1 square inch per 4,000 Btu per hour (5.5 cm2/kW) of total input rating of all equipment in the enclosure, see Figure 13.

FIGURE13.

2.When communicating with the outdoors through vertical ducts, each opening shall have a minimum free area of 1 square inch per 4,000 Btu per hour (5.5 cm2/kW) of total input rating of all equipment in the enclosure, see Figure 14.

3.When communicating with the outdoors through horizontal ducts, each opening shall have a minimum free area of 1 square inch per 2,000 Btu per hour (11 cm2/kW)) of total input rating of all equipment in the enclosure, see Figure 15.

FIGURE14.

4.When ducts are used, they shall be of the same cross-sectional area as the free area of the openings to which they connect. The minimum short side dimension of rectangular air ducts shall not be less than 3 inches (7.6 cm), see Figure 15.

FIGURE15.

5.Louvers and Grilles: In calculating free area, consideration shall be given to the blocking effect of louvers, grilles or screens protecting openings. Screens used shall not be smaller than 1/4 inch (6.4 mm) mesh. If the free area through a design of louver or grille is known, it should be used in calculating the size opening required to provide the free area specified. If the design and free area is not known, it may be assumed that wood louvers will be 20-25 percent free area and metal louvers and grilles will have 60-75 percent free area. Louvers and grilles shall be fixed in the open position or interlocked with the equipment so that they are opened automatically during equipment operation.

6.Special Conditions Created by Mechanical Exhausting or Fireplaces: operation of exhaust fans, ventilation systems, clothes dryers or fireplaces may create conditions requiring special attention to avoid unsatisfactory operation of installed gas utilization equipment.

12

Image 12
Contents Series Six HV640YBVITCGA HV650YBVITCGA HV640HBVITCGA HV650HBVITCGASafe INSTALLATION, USE and Service Important DefinitionsSafety Precautions Table of Contents Product Specifications Preparing for the InstallationAttempting to Install or Operate the Water Heater Customer ResponsibilitiesAccessories Materials and Basic Tools NeededTypical Installation Natural HOT Surface Igniter & Main BurnerPropane HOT Surface Igniter & Main Burner Mixing Valve Usage Installation Instructions Removing the Old Water HeaterFacts to Consider about the Location Insulation Blankets ALL AIR from Inside Buildings See Water Piping Hotter Water can ScaldTEMPERATURE-PRESSURE Relief Valve Valve and Pipe Insulation if suppliedGAS Piping with Flexibleconnector GAS PipingBlower Assembly Installation SequenceofinstallationSediment Traps Filling the Water HeaterVent Connections to Blower Assembly Venting and InstallationCondensation Maximum Vent LengthsVent Terminal Installation VentingVertical Vent Through Roof Vertical Vent RestrictionsVent Pipe Preparation Recommended BRUSH* Size for Primer Cement ApplicationsStepb StepeStepf Step GPowerbeforeservicing Operating InstructionsDo not try to light the burner by hand What to do if YOU Smell GASTemperature Regulation Temperature Setting Burns on Adult SkinFor Your Information Start UP ConditionsOperational Conditions Service and Adjustment Burner CleaningVenting System Inspection Burner Operation and InspectionTEMPERATURE-PRESSURE Relief Valve Operation Drain Valve Washer ReplacementService Anode ROD Inspection DrainingLeakage Checkpoints Troubleshooting Guidelines Water Heater ControlTroubleshooting Guidelines Repair Parts List Burner Assembly Outer Door AlternateMaytag GAS Water Heater HV640YBVITCGAFull ONE Year Warranty Limited Parts WarrantyLimited Tank Warranty Against Leaks To Receive Warranty Service