Table 1C — Electrical Data (COBRA™ Energy Recovery 48HJ004-007 Units with 62AQ100)

 

NOMINAL

IFM

CONV

62AQ

POWER SUPPLY

DISCONNECT SIZE*

UNIT

 

FUSE OR

 

 

V-PH-Hz

TYPE

OUTLET

FLA

MCA

FLA

LRA

 

HACR BKR

 

 

 

 

 

 

 

 

 

208/230-1-60

STD

NO

15.1

40.7/40.7

45/45

42/42

161/161

 

STD

YES

15.1

46.7/46.7

50/50

48/48

166/166

 

 

 

 

STD

NO

15.1

33.6/33.6

40/40

36/36

150/150

 

208/230-3-60

STD

YES

15.1

39.6/39.6

45/45

41/41

155/155

 

HIGH STATIC

NO

15.1

34.5/34.5

40/40

37/37

180/180

48HJ004

 

 

HIGH STATIC

YES

15.1

40.5/40.5

45/45

42/42

184/184

 

 

 

 

STD

NO

15.1

16.5

20

18

76

 

460-3-60

STD

YES

15.1

19.2

20

23

80

 

HIGH STATIC

NO

15.1

16.9

20

18

90

 

 

 

 

HIGH STATIC

YES

15.1

19.6

25

24

95

 

208/230-1-60

STD

NO

15.1

50.3/50.3

60/60

51/51

199/199

 

STD

YES

15.1

56.3/56.3

70/70

57/57

204/204

 

 

 

 

STD

NO

15.1

37.6/37.6

45/45

39/39

166/166

 

208/230-3-60

STD

YES

15.1

43.6/43.6

50/50

45/45

171/171

 

HIGH STATIC

NO

15.1

38.5/38.5

45/45

40/40

196/196

48HJ005

 

 

HIGH STATIC

YES

15.1

44.5/44.5

50/50

46/46

200/200

 

 

 

 

STD

NO

15.1

18.2

20

19

83

 

460-3-60

STD

YES

15.1

20.9

25

25

88

 

HIGH STATIC

NO

15.1

18.6

25

19

97

 

 

 

 

HIGH STATIC

YES

15.1

21.3

25

25

102

 

208/230-1-60

STD

NO

15.1

61.4/61.4

70/70

62/62

276/276

 

STD

YES

15.1

67.4/67.4

80/80

68/68

281/281

 

 

 

 

STD

NO

15.1

44.0/44.0

50/50

46/46

228/228

 

208/230-3-60

STD

YES

15.1

50.0/50.0

60/60

51/51

233/233

 

HIGH STATIC

NO

15.1

45.7/45.7

60/60

48/48

247/247

48HJ006

 

 

HIGH STATIC

YES

15.1

51.7/51.7

60/60

53/53

252/252

 

 

 

 

STD

NO

15.1

22.2

25

23

114

 

460-3-60

STD

YES

15.1

24.9

30

28

119

 

HIGH STATIC

NO

15.1

23.0

30

24

123

 

 

 

 

HIGH STATIC

YES

15.1

25.7

30

29

128

 

 

STD

NO

15.1

47.9/47.9

60/60

49/49

260/260

 

208/230-3-60

STD

YES

15.1

53.9/53.9

60/60

55/55

265/265

 

HIGH STATIC

NO

15.1

49.6/49.6

60/60

51/51

279/279

 

 

48HJ007

 

HIGH STATIC

YES

15.1

55.6/55.6

60/60

57/57

284/284

 

STD

NO

15.1

22.8

30

23

127

 

 

 

460-3-60

STD

YES

15.1

25.5

30

29

131

 

HIGH STATIC

NO

15.1

23.6

30

24

136

 

 

 

 

HIGH STATIC

YES

15.1

26.3

30

30

141

LEGEND

FLA — Full Load Amps

HACR — Heating, Air Conditioning and Refrigeration

IFM — Indoor (Evaporator) Fan Motor

LRA — Locked Rotor Amps

MCA — Minimum Circuit Amps

MOCP — Maximum Overcurrent Protection

NEC — National Electrical Code

UL — Underwriters’ Laboratories

*Used to determine minimum disconnect per NEC.

†Single point box CRSINGLE017A00 is part of base unit.

NOTES:

1.In compliance with NEC requirements for multimotor and combi- nation load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. UL, Canada units may be fuse or circuit breaker.

2.Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply volt- age is greater than 2%. Use the following formula to determine the percent of voltage imbalance.

= 100 x

max voltage deviation from average voltage

average voltage

 

Example: Supply voltage is 460-3-60.

AB = 452 v BC = 464 v AC = 455 v

Average Voltage = 452 + 464 + 455 3

1371

=

3

= 457

Determine maximum deviation from average voltage. (AB) 457 – 452 = 5 v

(BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v

Maximum deviation is 7 v.

Determine percent of voltage imbalance.

7

% Voltage Imbalance = 100 x 457

= 1.53%

This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.

17

Image 17
Contents General ContentsSafety Considerations Side View END View InstallationDuct Opening Sizes Side View CRRFCURB002A00 Connector ALT GAS Power Control PKG. Accy Drain HoleRoof Curb Unit Size Accessory CRRFCURB001A00 CRBTMPWR002A00 Roof Curb Unit Size AccessoryCRBTMPWR003A00 CRBTMPWR004A00Part Number Unit Size Equipment SupportRear Right Left Side Front Right Side Page Page Page Make Electrical Connections MAX Weight48HJ008 w/62AQ200 Nominal IFM Conv Power Supply Disconnect Size UnitType Outlet FLA MCA Fuse or LRA Hacr BKR HacrSingle Disconnect Size HeaterPoint BOX Type30.8 025 Cont Type Outlet FLA MCA LRA Hacr BKR Power Supply Disconnect Size Unit Fuse orNominal IFM Conv 40.7 47.7 119 FLA LRA Hacr BKR Type Outlet FLA60.1 Crheater Fuse or Point BOX 68.0 420 68.0 82.8 519/519 017 21.7 25.0 Power Wiring Connections Low Voltage Connections Units with PremierLink Controls Set the Outdoor Cooling and Heat- ing Thermostats Height Width Depth Light Commercial Thermidistat AccessoryInstall Light Commercial Thermidistat Light Commercial Thermidistat Keypad To Test FAN Operational Information START-UP ServicePRE-START-UP Unit Operation Flow Diagram Heating CoolingTroubleshooting Typical Wiring Schematic Standard Controls Typical Wiring Schematic with PremierLink Controls Problem Cause Remedy Heating and Cooling TroubleshootingCopyright 2002 Carrier Corporation III. START-UP Rooftop Unit RTU and Energy Recovery AQ START-UP ChecklistPreliminary Information RTU III. START-UP IV. Light Commercial Thermidistat Accessory