Carrier 48/50HJ004-014 specifications 82.8 519/519 017 21.7 25.0

Page 26

Table 1H — Electrical Data (COBRA™ Energy Recovery 50HJ008-014 Units with 62AQ300) (cont)

 

 

 

 

 

HEATER

HEAT

 

POWER SUPPLY

 

SINGLE

DISCONNECT SIZE*

UNIT

NOMINAL

IFM

CONV

62AQ

CRHEATER

 

 

 

 

FUSE OR

 

POINT BOX

 

 

 

V-PH-Hz

TYPE

OUTLET

FLA

FLA

MCA

MOCP

CRSINGLE

FLA

LRA

 

---A00

HACR BKR

 

 

 

 

 

 

 

 

 

 

---A00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NONE

—/—

82.8/ 82.8

90/ 90

90/ 90

519/519

 

 

 

 

 

017

21.7/

25.0

82.8/

82.8

90/ 90

90/

90

519/519

 

 

STD

NO

29.8

010

33.4/

38.5

86.4/

92.8

100/110

90/

91

519/519

 

 

012

66.7/

77.0

128.1/140.9

150/150

123/135

519/519

 

 

 

 

 

 

 

 

 

 

012+017

88.4/102.0

155.2/172.2

175/175

148/164

519/519

 

 

 

 

 

010+012

104.2/120.3

175.0/165.0

175/200

166/185

519/519

 

 

 

 

 

NONE

—/—

88.8/ 88.8

100/100

96/ 96

523/523

 

 

 

 

 

017

21.7/

25.0

88.8/

88.8

100/100

96/

96

523/523

 

 

STD

YES

29.8

010

33.4/

38.5

91.2/

97.0

110/110

96/

96

523/523

 

 

012

66.7/

77.0

132.9/145.1

150/150

129/140

523/523

 

 

 

 

 

 

 

 

 

 

012+017

88.4/102.0

160.0/176.4

175/200

154/169

523/523

 

208/230-3-60

 

 

 

010+012

104.2/120.3

179.8/169.2

200/200

172/190

523/523

 

 

 

 

NONE

—/—

87.2/ 87.2

100/100

95/ 95

542/542

 

 

 

 

 

 

 

 

 

 

017

21.7/

25.0

87.2/

87.2

100/100

95/

95

542/542

 

 

HIGH STATIC

NO

29.8

010

33.4/3

8.5

90.8/ 97.2

100/110

95/

96

542/542

 

 

012

66.7/

77.0

132.5/145.3

150/150

128/140

542/542

 

 

 

 

 

 

 

 

 

 

012+017

88.4/102.0

159.6/176.6

175/200

153/169

542/542

 

 

 

 

 

010+012

104.2/120.3

179.4/169.4

200/200

171/190

542/542

 

 

 

 

 

NONE

—/—

93.2/ 93.2

100/100

101/101

547/547

 

 

 

 

 

017

21.7/

25.0

93.2/ 93.2

100/100

101/101

547/547

 

 

HIGH STATIC

YES

29.8

010

33.4/

38.5

95.6/101.4

110/110

101/101

547/547

 

 

012

66.7/

77.0

137.3/149.5

150/150

134/145

547/547

 

 

 

 

 

 

 

 

 

 

012+017

88.4/102.0

164.4/180.8

175/200

159/174

547/547

50HJ012

 

 

 

 

010+012

104.2/120.3

184.2/173.6

200/200

177/195

547/547

 

 

 

 

NONE

 

40.7

45.0

44.0

260.0

 

 

 

 

 

 

 

 

 

 

 

016

16.7

45.8

60.0

011

44.0

261.0

 

 

STD

NO

15.8

013

19.8

49.7

60.0

011

47.0

261.0

 

 

014

33.4

66.7

80.0

014

62.0

261.0

 

 

 

 

 

 

 

 

 

 

014+016

50.2

87.6

100.0

016

81.0

261.0

 

 

 

 

 

013+015

60.1

85.0

110.0

016

93.0

261.0

 

 

 

 

 

NONE

 

43.4

45.0

47.0

262.0

 

 

 

 

 

016

16.7

47.9

60.0

014

47.0

263.0

 

 

STD

YES

15.8

013

19.8

51.8

60.0

011

49.0

263.0

 

 

014

33.4

68.8

80.0

014

65.0

263.0

 

 

 

 

 

 

 

 

 

 

014+016

50.2

89.7

100.0

016

84.0

263.0

 

460-3-60

 

 

 

013+015

60.1

87.1

110.0

016

95.0

263.0

 

 

 

 

NONE

 

43.3

50.0

47.0

272.0

 

 

 

 

 

 

 

 

 

 

 

016

16.7

48.4

60.0

014

47.0

272.0

 

 

HIGH STATIC

NO

15.8

013

19.8

52.3

60.0

011

50.0

272.0

 

 

014

33.4

69.3

80.0

014

65.0

272.0

 

 

 

 

 

 

 

 

 

 

014+016

50.2

90.2

100.0

016

84.0

272.0

 

 

 

 

 

013+015

60.1

87.6

110.0

016

96.0

272.0

 

 

 

 

 

NONE

 

46.0

50.0

0.0

50.0

274.0

 

 

 

 

 

016

16.7

50.5

60.0

014

50.0

274.0

 

 

HIGH STATIC

YES

15.8

013

19.8

54.4

60.0

011

52.0

274.0

 

 

014

33.4

71.4

90.0

014

68.0

274.0

 

 

 

 

 

 

 

 

 

 

014+016

50.2

92.3

100.0

016

87.0

274.0

 

 

 

 

 

013+015

60.1

89.7

110.0

016

98.0

274.0

 

 

 

 

 

NONE

—/—

90.4/ 90.4

100/100

98/ 98

604/604

 

 

 

 

 

017

21.7/

25.0

90.4/

90.4

100/100

98/

98

604/604

 

 

STD

NO

29.8

010

33.4/

38.5

90.8/

97.2

100/110

98/

98

604/604

 

 

012

66.7/

77.0

132.5/145.3

150/150

128/140

604/604

 

 

 

 

 

 

 

 

 

 

012+017

88.4/102.0

159.6/176.6

175/200

153/169

604/604

 

 

 

 

 

010+012

104.2/120.3

179.4/169.4

200/200

171/190

604/604

 

 

 

 

 

NONE

—/—

96.4/ 96.4

100/100

104/104

609/609

 

 

 

 

 

017

21.7/

25.0

96.4/ 96.4

100/100

104/104

609/609

 

 

STD

YES

29.8

010

33.4/

38.5

95.6/101.4

110/110

104/104

609/609

 

 

012

66.7/

77.0

137.3/149.5

150/150

134/145

609/609

 

 

 

 

 

 

 

 

 

 

012+017

88.4/102.0

164.4/180.8

175/200

159/174

609/609

50HJ014

208/230-3-60

 

 

 

010+012

104.2/120.3

184.2/173.6

200/200

177/195

609/609

 

 

 

NONE

 

44.9

50.0

49.0

287.0

 

 

 

 

 

 

 

 

 

 

 

016

16.7

48.4

60.0

014

49.0

287.0

 

 

STD

NO

15.8

013

19.8

52.3

60.0

011

50.0

287.0

 

 

016

16.7

48.4

70.0

014

49.0

287.0

 

 

 

 

 

 

 

 

 

 

014+016

50.2

90.2

100.0

016

84.0

287.0

 

 

 

 

 

013+015

60.1

87.6

110.0

016

96.0

287.0

 

 

 

 

 

NONE

 

47.6

50.0

51.0

289.0

 

 

 

 

 

016

16.7

50.5

60.0

014

51.0

289.0

 

 

STD

YES

15.8

013

19.8

54.4

60.0

011

52.0

289.0

 

 

016

16.7

50.5

70.0

014

51.0

289.0

 

 

 

 

 

 

 

 

 

 

014+016

50.2

92.3

100.0

016

87.0

289.0

 

 

 

 

 

013+015

60.1

89.7

110.0

016

98.0

289.0

 

LEGEND

FLA

Full Load Amps

HACR

Heating, Air Conditioning and Refrigeration

IFM

Indoor (Evaporator) Fan Motor

LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps

MOCP

Maximum Overcurrent Protection

NEC

National Electrical Code

UL

Underwriters’ Laboratories

*Used to determine minimum disconnect per NEC.

†Single point box CRSINGLE017A00 is part of base unit.

NOTES:

1.In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. UL, Canada units may be fuse or circuit breaker.

2.Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percent of voltage imbalance.

max voltage deviation from average voltage

= 100 x

average voltage

Example: Supply voltage is 460-3-60.

AB = 452 v

BC = 464 v

AC = 455 v

452 + 464 + 455

Average Voltage =

3

1371

=

3

= 457

Determine maximum deviation from average voltage. (AB) 457 – 452 = 5 v

(BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v Maximum deviation is 7 v.

Determine percent of voltage imbalance.

7

% Voltage Imbalance = 100 x 457

= 1.53%

This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.

26

Image 26
Contents General ContentsSafety Considerations Side View END View InstallationDuct Opening Sizes Side View CRRFCURB002A00 Connector ALT GAS Power Control PKG. Accy Drain HoleRoof Curb Unit Size Accessory CRRFCURB001A00 CRBTMPWR003A00 Roof Curb Unit Size AccessoryCRBTMPWR002A00 CRBTMPWR004A00Unit Size Equipment Support Part NumberRear Right Left Side Front Right Side Page Page Page MAX Weight Make Electrical Connections48HJ008 w/62AQ200 Type Outlet FLA MCA Fuse or LRA Hacr BKR Power Supply Disconnect Size UnitNominal IFM Conv HacrPoint BOX HeaterSingle Disconnect Size Type30.8 025 Cont Type Outlet FLA MCA LRA Hacr BKR Power Supply Disconnect Size Unit Fuse orNominal IFM Conv 40.7 47.7 119 Type Outlet FLA FLA LRA Hacr BKR60.1 Crheater Fuse or Point BOX 68.0 420 68.0 82.8 519/519 017 21.7 25.0 Power Wiring Connections Low Voltage Connections Units with PremierLink Controls Set the Outdoor Cooling and Heat- ing Thermostats Light Commercial Thermidistat Accessory Height Width DepthInstall Light Commercial Thermidistat Light Commercial Thermidistat Keypad To Test FAN Operational Information START-UP ServicePRE-START-UP Unit Operation Flow Diagram Cooling HeatingTroubleshooting Typical Wiring Schematic Standard Controls Typical Wiring Schematic with PremierLink Controls Heating and Cooling Troubleshooting Problem Cause RemedyCopyright 2002 Carrier Corporation III. START-UP Rooftop Unit RTU and Energy Recovery AQ START-UP ChecklistPreliminary Information RTU IV. Light Commercial Thermidistat Accessory III. START-UP