LIGHT COMMERCIAL
THERMIDISTAT ACCESSORY
General — A Light Commercial Thermidistat Accessory (part number
The Light Commercial Thermidistat is a
Power — Note that this control does not require batteries and is not “power stealing.” It does require 24 vac (R and C terminals) from the RTU’s
Dehumidification Equipment and Connec- tions — The dehumidification output terminals on the Light Commercial Thermidistat must be connected to the dehumidify input terminals on the energy recovery section. Additionally, if the RTU is equipped with optional MoistureMi$er™ Dehumid- ification accessory, a relay in the energy recovery section energizes the MoistureMi$er solenoid to activate the enhanced dehumidification mode.
Step 1 — Select Light Commercial Thermidis- tat Location — Light Commercial Thermidistat should be
mounted:
•Approximately 5 ft (1.5 m) from floor.
•Close to or in a frequently used room, preferably on an inside partitioning wall.
•On a section of wall without pipes or ductwork.
The Light Commercial Thermidistat should NOT be mounted:
•Close to a window, on an outside wall, or next to a door leading to the outside.
•Exposed to direct light and heat from a lamp, sun, fire- place, or other
•Close to or in direct airflow from supply registers and
•In areas with poor air circulation, such as behind a door or in an alcove.
HEIGHT (in.) | WIDTH (in.) | DEPTH (in.) |
41/4 | 71/2 | 13/8 |
Fig. 13 — Light Commercial
Thermidistat Accessory
FOR MOISTUREMI$ER UNITS ONLY
LIGHT
COMMERCIAL
THERMIDISTAT
ACCESSORY
OPTIONAL
HUMIDISTAT (HL38MG029)
Fig. 14 — Light Commercial Thermidistat
Accessory Low-Voltage Connections
Step 2 — Set DIP Switches — There is a
1.Open hinged Light Commercial Thermidistat cover.
2.Remove cover completely by gently snapping it apart at the hinge.
3.Switches are located in upper right corner of circuit board. To change switch position, use corner of a small screwdriver to slide switch to opposite position.
4.After switches have been set, do not reassemble the 2 halves. The rear plastic will be first mounted to wall.
SWITCH 1 — Not used SWITCH 2 — Not used
SWITCH 3 — SMART/CONVENTIONAL RECOVERY — Selects between conventional or smart recovery from setback. Conventional recovery changes to new set point at prepro- grammed time. Smart recovery, which is active in both heating and cooling, starts selected cycle 90 minutes earlier and smoothly adjusts set point so room will arrive at programmed temperature at programmed time.
NOTE: The occupied output is only energized at the prepro- grammed time.
To Set:
OFF — for smart recovery. This is factory default. ON — for conventional recovery.
SWITCH 4 — INSTALLER TEST OFF/ON — Selects a special installer test mode that assists with checkout and troubleshooting. See Step 5 — Conduct Light Commercial Thermidistat
To Set:
OFF — for normal operation. (Factory default setting.) ON — for Installer Test mode.
30