Carrier 48/50HJ004-014 specifications Cooling, Heating

Page 37

Table 2 — Light Commercial Thermidistat (LCT) Operating Sequence and System Response

UNOCCUPIED

 

COOLING

ER Comp

 

ER Fans

 

 

RT Comp 1

 

RT Comp 2

 

RT Fans

 

RT Heat

Indoor Temperature Above 2nd Stage

 

 

 

 

 

 

 

 

 

 

 

 

Set Point

 

 

 

 

 

 

 

 

 

 

 

 

 

Humidity Low & OAT Low

On

 

On (cyc.)

 

 

On w/o MM

 

Off

 

On (cyc.)

 

Off

 

 

 

 

 

 

 

Humidity Low & OAT High

Off

 

Off

 

 

On w/o MM

 

w/o MM

 

On (cyc.)

 

Off

 

Humidity High & OAT Low

Off

 

Off

 

 

On w MM

 

On w MM

 

On (cyc.)

 

Off

 

Humidity High & OAT High

Off

 

Off

 

 

On w MM

 

On w MM

 

On (cyc.)

 

Off

Indoor Temperature Between 1st and

 

 

 

 

 

 

 

 

 

 

 

 

2nd Stage Set Points

 

 

 

 

 

 

 

 

 

 

 

 

 

Humidity Low & OAT Low

Off

 

On (cyc.)

 

 

Off

 

Off

 

On (cyc.)

 

Off

 

 

 

 

 

 

 

Humidity Low & OAT High

Off

 

Off

 

 

On w/o MM

 

Off

 

On (cyc.)

 

Off

 

Humidity High & OAT Low

Off

 

Off

 

 

On w MM

 

Off

 

On (cyc.)

 

Off

 

Humidity High & OAT High

Off

 

Off

 

 

On w MM

 

Off

 

On (cyc.)

 

Off

Indoor Temperature Below 1st Stage

Off

 

Off

 

 

Off

 

Off

 

Off

 

Off

Set Point

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE: OAT < 55° all compression off*

 

 

 

 

 

 

 

 

 

 

 

 

 

HEATING

ER Comp.

 

ER Fans

 

 

RT Comps.

 

RT Fans

 

RT Heat

 

 

Indoor Temperature Above 1st Set

Off

 

Off

 

 

Off

 

Off

 

Off

 

 

Point

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor Temperature Between 1st and

Off

 

Off

 

 

Off

 

On (cyc.)

 

On, 50%

 

 

2nd Stage Set Points

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor Temperature Below 2nd Stage

Off

 

Off

 

 

Off

 

On (cyc.)

 

On, 100%

 

 

Set Point

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OCCUPIED

 

 

 

 

 

 

 

 

 

 

COOLING

ER Comp

 

ER Fans

 

 

RT Comp 1

 

RT Comp 2

 

RT Fan

 

RT Heat

Indoor Temperature Above 2nd Stage

 

 

 

 

 

 

 

 

 

 

 

 

Set Point

 

 

 

 

 

 

 

 

 

 

 

 

 

Humidity Low & OAT Low

On

 

On

 

 

On w/o MM

 

On w/o MM

 

On

 

Off

 

 

 

 

 

 

 

Humidity Low & OAT High

On

 

On

 

 

On w/o MM

 

On w/o MM

 

On

 

Off

 

Humidity High & OAT Low

On

 

On

 

 

On w MM

 

On w MM

 

On

 

Off

 

Humidity High & OAT High

On

 

On

 

 

On w MM

 

On w MM

 

On

 

Off

Indoor Temperature Between 1st and

 

 

 

 

 

 

 

 

 

 

 

 

2nd Stage Set Points

 

 

 

 

 

 

 

 

 

 

 

 

 

Humidity Low & OAT Low

Off

 

On

 

 

Off

 

Off

 

On

 

Off

 

 

 

 

 

 

 

Humidity Low & OAT High

On

 

On

 

 

On w/o MM

 

Off

 

On

 

Off

 

Humidity High & OAT Low

On

 

On

 

 

On w MM

 

Off

 

On

 

Off

 

Humidity High & OAT High

On

 

On

 

 

On w MM

 

Off

 

On

 

Off

Indoor Temperature Below 1st Stage

 

 

 

 

 

 

 

 

 

 

 

 

Set Point

 

 

 

 

 

 

 

 

 

 

 

 

 

Humidity Low

Off

 

On

 

 

Off

 

Off

 

On

 

Off

 

 

 

 

 

 

 

Humidity High

On

 

On

 

 

Off

 

Off

 

On

 

Off

NOTE: OAT < 55° all compression off*

 

 

 

 

 

 

 

 

 

 

 

 

 

HEATING

ER Comp

 

ER Fans

 

 

RT Comps

 

RT Fans

 

RT Heat

 

 

Indoor Temperature Above 1st Stage

Off

 

On

 

 

Off

 

On

 

Off

 

 

Set Point

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor Temperature Between 1st and

 

 

 

 

 

 

 

 

 

 

 

 

2nd Stage Set Points

 

 

 

 

 

 

 

 

 

 

 

 

 

OAT >Set Pt

On

 

On

 

 

Off

 

On

 

Off

 

 

 

 

 

 

 

 

 

 

OAT <Set Pt

On

 

On

 

 

Off

 

On

 

On, 50%

 

 

Indoor Temperature Below 2nd Stage

 

 

 

 

 

 

 

 

 

 

 

 

Set Point

 

 

 

 

 

 

 

 

 

 

 

 

 

OAT >Set Pt

On

 

On

 

 

Off

 

On

 

On, 50%

 

 

 

 

 

 

 

 

 

 

OAT <Set Pt

On

 

On

 

 

Off

 

On

 

On, 100%

 

 

 

LEGEND

 

 

 

 

 

 

 

 

 

 

 

 

Comp — Compressor

 

 

 

 

 

 

 

 

 

 

 

 

ER

Energy Recovery section

 

 

 

 

 

 

 

 

 

 

 

 

MMMoistureMi$er™ Dehumidification Device OAT — Outdoor-Air Temperature

RT — Rooftop Unit Set Pt — Set Point

*Unless unit compressor has been rewired as described in Step 11 (page 29).

37

Image 37
Contents Safety Considerations ContentsGeneral Duct Opening Sizes InstallationSide View END View Side View Roof Curb Unit Size Accessory CRRFCURB001A00 Connector ALT GAS Power Control PKG. Accy Drain HoleCRRFCURB002A00 CRBTMPWR002A00 Roof Curb Unit Size AccessoryCRBTMPWR003A00 CRBTMPWR004A00Part Number Unit Size Equipment SupportRear Right Left Side Front Right Side Page Page Page Make Electrical Connections MAX Weight48HJ008 w/62AQ200 Nominal IFM Conv Power Supply Disconnect Size UnitType Outlet FLA MCA Fuse or LRA Hacr BKR HacrSingle Disconnect Size HeaterPoint BOX Type30.8 025 Cont Nominal IFM Conv Power Supply Disconnect Size Unit Fuse orType Outlet FLA MCA LRA Hacr BKR 40.7 47.7 119 FLA LRA Hacr BKR Type Outlet FLA60.1 Crheater Fuse or Point BOX 68.0 420 68.0 82.8 519/519 017 21.7 25.0 Power Wiring Connections Low Voltage Connections Units with PremierLink Controls Set the Outdoor Cooling and Heat- ing Thermostats Height Width Depth Light Commercial Thermidistat AccessoryInstall Light Commercial Thermidistat Light Commercial Thermidistat Keypad To Test FAN Operational Information PRE-START-UP ServiceSTART-UP Unit Operation Flow Diagram Heating CoolingTroubleshooting Typical Wiring Schematic Standard Controls Typical Wiring Schematic with PremierLink Controls Problem Cause Remedy Heating and Cooling TroubleshootingCopyright 2002 Carrier Corporation Preliminary Information RTU Rooftop Unit RTU and Energy Recovery AQ START-UP ChecklistIII. START-UP III. START-UP IV. Light Commercial Thermidistat Accessory