COBRA™ Energy Recovery Units
Installation, Start-Up,
and Service Supplement
IMPORTANT: This is a supplemental instruction for the 48/50HJ and the 62AQ Installation,
CONTENTS
Page SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . 1 GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
• ROOF CURB
Step 3 — Field Fabricate Ductwork . . . . . . . . . . . . . . . 3 Step 4 — Rig and Place Unit . . . . . . . . . . . . . . . . . . . . . 6
•POSITIONING
Step 5 — Install Flue Hood (48HJ Only) . . . . . . . . . 11 Step 6 — Install Gas Piping (48HJ Only). . . . . . . . . 11
Step 7 — Install External Trap for Condensate Drain. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Step 8 — Make Electrical Connections . . . . . . . . . . 11
•FIELD POWER SUPPLY
•
•FIELD CONTROL WIRING
•HEAT ANTICIPATOR SETTINGS
Step 9 — Assemble and Mount
Step 11 — Set the Outdoor Cooling and
Heating Thermostats. . . . . . . . . . . . . . . . . . . . . . . . . . 29
LIGHT COMMERCIAL THERMIDISTAT ACCESSORY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Dehumidification Equipment and Connections . . . 30
Step 1 — Select Light Commercial
Thermidistat Location . . . . . . . . . . . . . . . . . . . . . . . . . 30
Step 2 — Set DIP Switches . . . . . . . . . . . . . . . . . . . . . . . 30
Step 3 — Install Light Commercial Thermidistat . . 31
Step 4 — Set Light Commercial Thermidistat
Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Step 5 — Conduct Light Commercial
Thermidistat
Step 6 — Make Final Settings . . . . . . . . . . . . . . . . . . . . 34
OPERATIONAL INFORMATION . . . . . . . . . . . . . . . . . . 34
ROOFTOP UNIT AND ENERGY$RECYCLER2
SAFETY CONSIDERATIONS
Installation and servicing of
Untrained personnel can perform basic maintenance func- tions of cleaning coils and filters and replacing filters. All other operations should be performed by trained service personnel. When working on
Verify that the power source supplied to the unit matches the voltages and amperages listed on the unit rating plate.
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for unbrazing operations. Have fire extinguishers available for all brazing operations.
Disconnect gas piping from unit when leak testing at pressure greater than 1/2 psig. Pres- sures greater than 1/2 psig will cause gas valve damage resulting in hazardous condi- tion. If gas valve is subjected to pressure greater than 1/2 psig, it must be replaced before use. When pressure testing field- supplied gas piping at pressures of 1/2 psig or less, a unit connected to such piping must be isolated by manually closing the gas valve.
Before performing service or maintenance operations on unit, turn off main power switch to unit and install a lock- out tag. Electrical shock could cause personal injury.
GENERAL
Carrier’s
Factory installation of the energy recovery section provides the benefit of reduced
NOTE: Because of the location of the energy recovery section, the unit nameplate has been moved to the opposite end of the rooftop section, on the upper,
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book | 1 | 1 | 4 | 4 | PC 111 Catalog No. | Printed in U.S.A. | Form | Pg 1 | Replaces: | |
Tab | 1a | 1b | 6a | 6b |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|