Samsung AQV12EWEN manual Connecting the assembly cable, Cable specification, Connecting the cable

Page 28

Fixing the installation plate

2. Fix the indoor unit.

If you fix the indoor unit on a wall

(1) Fix the installation plate to the wall giving attention to the weight of the indoor unit.

• If you mount the plate to a concrete wall using plastic anchors, make sure that gaps between the wall and the plate, created by projected anchor, is less than 20mm.

Plastic

Anchor

<20mm

Wall

If you fix the indoor unit on a window frame

(1)Determine the positions of the wooden uprights to be attached to the window frame.

(2)Attach the wooden uprights to the window frame giving attention to the weight of the indoor unit.

(3)Attach the installation plate to the wooden upright using tapping screws.

If you fix the indoor unit on a gypsum board

(1)Use stud finder to find out locations of the studs.

(2)Fix the plate hanger on two studs.

Search for other spots if there are less than two studs, or the distance between the studs are different from the plate hanger.

Fix the installation plate without inclining to one side.

Make sure that a wall can withstand the weight of the product. If you install the product in a place where it is not

strong enough to withstand the product weight, the unit could fall and cause injury.

Connecting the assembly cable

Cable specification

Model

Power cable

Interconnection cable

Type GL

 

 

 

 

 

 

 

 

 

 

09/12

3G, 2.5mm² H07RN-F

3G, 1.5mm² H07RN-F

20A

 

 

 

 

18/24

2G, 0.75mm² H05RN-F

25A

 

 

 

 

 

 

 

 

 

• Connect the power cable to the auxiliary circuit breaker. If every pole fails to connect to the power supply, it must be incorporated in a wire with a contact opening of ≥3mm.

Connecting the cable

When you install the unit, make first refrigerant connections and then electrical connections. Connect the air conditioner to grounding system before performing the electrical connection. If unit is uninstalled, first disconnect electrical cables, then refrigerant connections.

If the outdoor unit is more than 5 meters away from the indoor unit, you must extend the cable.

The maximum length of the cable is 15(09/12)/20(18/24) meters.

1.Extend the assembly cable if necessary.

Do not connect two or more different cables to extend the length. It may cause fire.

28

Vivaldi Cystal EUR_AQV09E@@ IB&IM_32449A_E.indd 28

2011-3-14 14:01:36

Image 28
Contents Vivaldi Cystal EURAQV09E@@ IB&IM32449AE.indd 2011-3-7 Contents Safety precautions Important safety symbols and precautionsFollow directions Wall socketFor Using For Cleaning Checking before use Operation rangesPower Checking the name of the partsMain parts DisplayChecking the remote controller Remote controller buttonsRemote controller display Battery changing timeStoring the remote controller Inserting the batteriesBasic function Button to adjust the temperature PressAdjusting the air flow direction Using the Turbo functionPress the Air swing button on the remote controller Vertical air flowWhen the air conditioner is on and in cool/heat mode Press the button on the remote controllerPress the Set/Cancel button to active it on ModePress the On Timer/Off Timer button Setting the On/Off timerPress the On Timer/Off Timer button to set the time Using the SPi function Using the Smart Saver functionUsing the Quiet function Using the Auto Clean functionWhen the air conditioner is turned on You can reduce the noise generated from an indoor unitCleaning the air conditioner Cleaning the indoor unitCleaning the outdoor unit heat exchanger Opening the panelCleaning the air filter Removing the Air filterOpen the panel and put the Air filter out Dry the Air filter in a ventilated areaMaintaining the air conditioner Periodical checksTroubleshooting Flow movement changes. It is normal Outdoor unit Heat exchanger during Heat mode in winterConnection Included Models Remark General informationAQV09E, AQV12E, AQV18E, AQV24E Choosing the installation location Installing the unitPower supply line, fuse or circuit breaker  a place where the air filter can be replaced easilyWhere sulfide gas exists Outdoor UnitWhen installing more than 1 outdoor unit When the air outlet is towards the wall Figure Description Top view Side viewAccessories in the indoor unit case AccessoriesAccessories in the outdoor unit case Fixing the installation plate Optional accessoriesTools required for installation General Tools Tools for test operationsCable specification Connecting the assembly cableConnecting the cable Each wire is labeled with the corresponding terminal number Smooth the cut edges Cut off the remaining foam insulationPurging the indoor unit Cutting or extending the pipeUnscrew the caps at the end of each pipe Put a flare nut slightly into the pipe and modify the flarePipe 50 Pa. The joint must be accessible and serviceable Correct InclinedCracked Outer DiameterDrain hose installation Connect a drain hose to the drain plug Purging the connected pipesEnsure that condensation draining is adequate Adding Refrigerant  the factory refrigerant charge of the product Please fill in with indelible ink1975 Performing the gas leak tests To check for gas leaks on the outdoor unitTo check for gas leaks on the indoor unit Leak test with nitrogen before opening valvesOutdoor unit installed on the wall by rack Then place the indoor unit on the installation plateFixing the indoor unit in place Fixing the outdoor unit in placeFinal Check and Trial Operation How to connect your extended power cables Apply heat to the contraction tube to contract itAfter tube contraction work is completed, wrap it with Insulation tape to finishEnglish 42 27 7267864, € 0.07/min70 70 19 +381Air Conditioner