Samsung AQV12EWEN, AQV09EWEN, AQV09EWEX, AQV12EWEX Correct Inclined, Cracked, Outer Diameter, Ditch

Page 32

Cutting or extending the pipe

5. Check if you flared the pipe correctly (see examples of incorrectly flared pipes below).

Correct

Inclined

Damaged

Cracked

Uneven

 

 

Surface

 

Thickness

6.Align the pipes to connect them easily. Tighten the flare nuts first with your hands, and then with a torque wrench, applying the following torque:

Flare nut

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor outlet

 

pipe

 

 

 

 

 

Connecting pipe

Outer Diameter

Torque (kgf•cm)

ø6.35 mm

140~170

ø9.52 mm

250~280

ø12.70 mm

380~420

ø15.88 mm

440~480

ø19.05 mm

990~1210

ø22.23 mm

990~1210

• Excessive torque can be cause of gas leakage. In case brazing the pipe, the nitrogen gas must be blown into the

pipe (50 Pa). The joint must be accessible and serviceable.

7. For further details on how to connect to the outdoor unit and purge the air, refer to page 34~36.

• Tighten the flare nut with torque wrench according to specified method.

If the flare nut is over-tightened, the flare may break and cause refrigerant gas leakage.

Installing and connecting the drain hose of the indoor unit

When installing the drain hose for the indoor unit, check if condensation draining is adequate. When passing the drain hose through the 65-mm hole drilled in the wall, check the followings:

Wall

Indoor unit

Drain hose

The drain hose must not be bent.

The drain hose must NOT slant upwards.

5cm less

Keep a clearance of at least 5cm between the end of the drain hose and the ground.

The end of the drain hose must NOT be placed under water.

Ditch

Do not place the end of the drain hose in a hollow.

32

Vivaldi Cystal EUR_AQV09E@@ IB&IM_32449A_E.indd 32

2011-3-7 15:45:38

Image 32
Contents Vivaldi Cystal EURAQV09E@@ IB&IM32449AE.indd 2011-3-7 Contents Safety precautions Important safety symbols and precautionsFollow directions Wall socketFor Using For Cleaning Checking before use Operation rangesPower Checking the name of the partsMain parts DisplayChecking the remote controller Remote controller buttonsRemote controller display Battery changing timeStoring the remote controller Inserting the batteriesBasic function Button to adjust the temperature PressAdjusting the air flow direction Using the Turbo functionPress the Air swing button on the remote controller Vertical air flowWhen the air conditioner is on and in cool/heat mode Press the button on the remote controllerPress the Set/Cancel button to active it on ModePress the On Timer/Off Timer button to set the time Setting the On/Off timerPress the On Timer/Off Timer button Using the SPi function Using the Smart Saver functionUsing the Quiet function Using the Auto Clean functionWhen the air conditioner is turned on You can reduce the noise generated from an indoor unitCleaning the air conditioner Cleaning the indoor unitCleaning the outdoor unit heat exchanger Opening the panelCleaning the air filter Removing the Air filterOpen the panel and put the Air filter out Dry the Air filter in a ventilated areaMaintaining the air conditioner Periodical checksTroubleshooting Connection Outdoor unit Heat exchanger during Heat mode in winterFlow movement changes. It is normal AQV09E, AQV12E, AQV18E, AQV24E General informationIncluded Models Remark Choosing the installation location Installing the unitPower supply line, fuse or circuit breaker  a place where the air filter can be replaced easilyWhere sulfide gas exists Outdoor UnitWhen installing more than 1 outdoor unit When the air outlet is towards the wall Figure Description Top view Side viewAccessories in the outdoor unit case AccessoriesAccessories in the indoor unit case Fixing the installation plate Optional accessoriesTools required for installation General Tools Tools for test operationsConnecting the cable Connecting the assembly cableCable specification Each wire is labeled with the corresponding terminal number Smooth the cut edges Cut off the remaining foam insulationPurging the indoor unit Cutting or extending the pipeUnscrew the caps at the end of each pipe Put a flare nut slightly into the pipe and modify the flarePipe 50 Pa. The joint must be accessible and serviceable Correct InclinedCracked Outer DiameterDrain hose installation Ensure that condensation draining is adequate Purging the connected pipesConnect a drain hose to the drain plug Adding Refrigerant 1975 Please fill in with indelible ink the factory refrigerant charge of the product Performing the gas leak tests To check for gas leaks on the outdoor unitTo check for gas leaks on the indoor unit Leak test with nitrogen before opening valvesOutdoor unit installed on the wall by rack Then place the indoor unit on the installation plateFixing the indoor unit in place Fixing the outdoor unit in placeFinal Check and Trial Operation How to connect your extended power cables Apply heat to the contraction tube to contract itAfter tube contraction work is completed, wrap it with Insulation tape to finishEnglish 42 27 7267864, € 0.07/min70 70 19 +381Air Conditioner