Samsung AQV12EWEX, AQV12EWEN, AQV09EWEN, AQV09EWEX manual Adding Refrigerant

Page 35

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3. Connect the charging hose of the low-pressure side of manifold gauge to a

 

 

 

Manifold gauge

 

 

 

 

 

 

gas service port as seen in the picture.

 

 

 

 

 

 

 

 

 

 

4.Open the valve of the low pressure side of manifold gauge counterclockwise.

5.Purge the air in the connected pipes using the vacuum pump for about 15 minutes.

Make sure that pressure gauge shows -0.1MPa(-76cmHg) after about 10 minutes.

This procedure is very important to avoid a gas leak.

Close the valve of the low pressure side of manifold gauge clockwise.

Turn off the vacuum pump.

Check for 2 minutes if there is any pressure change.

Remove the hose of the low pressure side of manifold gauge.

6.Set a valve cork of liquid and gas service port to the open position.

Valve

Gas service port <Low pressure>

 

Vacuum

Liquid service port

Pump

<High pressure>

(Backward flowing

 

prevention)

ENGLISH

7.

Mount the valve stem nuts and the service port cap to the valve, and tighten

 

 

them at the torque of 183kgf•cm with a torque wrench.

Valve stem

8.

Check for a gas leak paying particular attention to the 3-way valve’s stem nuts

Stem nut

 

and to the service port cap (Refer to page 37).

 

A

 

 

 

 

(Gas)

 

 

B

 

 

(liquid)

Adding Refrigerant

Add refrigerant charge according to table below:

If you use a pipe longer than 5m,

‘15’g of refrigerant R410A must be added for each extra meter.

If you use a pipe shorter than 5m,

The purge time is normal.

Refer to the Service Manual for further details.

• The remaining air in the Refrigeration cycle, which contains moisture, may cause malfunction on the compressor.

• Always contact the service center or a professional installation agency for product installation.

35

Vivaldi Cystal EUR_AQV09E@@ IB&IM_32449A_E.indd 35

2011-3-7 15:45:44

Image 35
Contents Vivaldi Cystal EURAQV09E@@ IB&IM32449AE.indd 2011-3-7 Contents Wall socket Safety precautionsImportant safety symbols and precautions Follow directionsFor Using For Cleaning Operation ranges Checking before useDisplay PowerChecking the name of the parts Main partsRemote controller buttons Checking the remote controllerInserting the batteries Remote controller displayBattery changing time Storing the remote controllerBasic function Press Button to adjust the temperatureVertical air flow Adjusting the air flow directionUsing the Turbo function Press the Air swing button on the remote controllerMode When the air conditioner is on and in cool/heat modePress the button on the remote controller Press the Set/Cancel button to active it onPress the On Timer/Off Timer button to set the time Setting the On/Off timerPress the On Timer/Off Timer button Using the Smart Saver function Using the SPi functionYou can reduce the noise generated from an indoor unit Using the Quiet functionUsing the Auto Clean function When the air conditioner is turned onOpening the panel Cleaning the air conditionerCleaning the indoor unit Cleaning the outdoor unit heat exchangerDry the Air filter in a ventilated area Cleaning the air filterRemoving the Air filter Open the panel and put the Air filter outPeriodical checks Maintaining the air conditionerTroubleshooting Connection Outdoor unit Heat exchanger during Heat mode in winterFlow movement changes. It is normal AQV09E, AQV12E, AQV18E, AQV24E General informationIncluded Models Remark  a place where the air filter can be replaced easily Choosing the installation locationInstalling the unit Power supply line, fuse or circuit breakerOutdoor Unit Where sulfide gas existsTop view Side view When installing more than 1 outdoor unitWhen the air outlet is towards the wall  Figure DescriptionAccessories in the outdoor unit case AccessoriesAccessories in the indoor unit case Tools for test operations Fixing the installation plateOptional accessories Tools required for installation General ToolsConnecting the cable Connecting the assembly cableCable specification Each wire is labeled with the corresponding terminal number Cut off the remaining foam insulation Smooth the cut edgesPut a flare nut slightly into the pipe and modify the flare Purging the indoor unitCutting or extending the pipe Unscrew the caps at the end of each pipeOuter Diameter Pipe 50 Pa. The joint must be accessible and serviceableCorrect Inclined CrackedDrain hose installation Ensure that condensation draining is adequate Purging the connected pipesConnect a drain hose to the drain plug Adding Refrigerant 1975 Please fill in with indelible ink the factory refrigerant charge of the product Leak test with nitrogen before opening valves Performing the gas leak testsTo check for gas leaks on the outdoor unit To check for gas leaks on the indoor unitFixing the outdoor unit in place Outdoor unit installed on the wall by rackThen place the indoor unit on the installation plate Fixing the indoor unit in placeFinal Check and Trial Operation Insulation tape to finish How to connect your extended power cablesApply heat to the contraction tube to contract it After tube contraction work is completed, wrap it withEnglish +381 42 277267864, € 0.07/min 70 70 19Air Conditioner