INSTALLATION
Continued
CHECK GAS TYPE
Use the correct gas type (natural or propane/LP) for your unit. If your gas supply is not correct, do not instal in fireplace. Call dealer where you bought the appliance for proper type of appliance.
WARNING: This appliance is equipped for (natural or pro- pane/LP) gas. Field conversion is not permitted.
INSTALLATION AND CLEARANCES
Figure 2 shows technical information regarding the installation of your gas log set. Please make sure all specifications shown are applicable before installation is attempted.
|
| SPECIFICATIONS (W.C.) |
| |||
|
| FUEL INLET | MANIFOLD | |||
|
| PRESSURE | PRESSURE | |||
|
|
| Min. | Max. |
|
|
NG |
| 7" | 10.5" | 3.5" |
| |
LP |
| 11" | 14" | 10" |
| |
Figure 2 - Technical Information Chart | ||||||
FLUE OPENING SPECIFICATIONS | ||||||
Note: This vented appliance must be installed only | ||||||
in a | ||||||
place constructed of noncombustible material and | ||||||
connected to a working flue. The fireplace chimney | ||||||
must have a permanent vent opening to outside | ||||||
with minimum openings shown in Figure 3. | ||||||
|
| LOG SIZING REQUIREMENTS |
| |||
|
|
|
| |||
|
| MINIMUM FIREBOX SIZE |
| |||
LOG |
|
| FRONT REAR* MIN. FLUE | |||
SIZE HEIGHT DEPTH WIDTH WIDTH | SIZE | |||||
18" |
| 20" | 14" | 25" | 20.5" | 6.5" |
24" |
| 20" | 14" | 29" | 24.5" | 6.5" |
*Measured at 14" depth |
|
|
| |||
Figure 3 - Sizes and Clearances | ||||||
VENTING SPECIFICATIONS FOR | ||||||
INSTALLATION |
|
|
| |||
The fireplace chimney flue and vent must be draft- | ||||||
ing properly. To check the vent for proper drafting: | ||||||
Light a tightly rolled newspaper on one end and | ||||||
place it at the inside front edge of the fireplace. | ||||||
Observe the smoke and be sure the vent is properly |
drawing it up the chimney. If the smoke spills out into the room, extinguish the flame and remove any obstruction until proper venting is achieved.
The chimney flue damper must be fixed open to pro- vide a minimum of 32 square inch of free air opening at all times during operation of the log set. A damper clamp is included to secure the damper.
The minimum flue sizes shown in Figure 3 are based on a 6' chimney height using round pipe. Your minimum flue size will vary based on input rate and chimney height. Refer to the National Fuel Gas Code ANSI Z223.1/NFPA 54, Section 6.6 for details.
INSTALLING DAMPER CLAMP | |
Secure the damper stop clam to the edge of the | |
damper as shown in Figure 4. If for any reason | |
this clamp doesn't work on your fireplace, another | |
suitable clamp or permanent stop must be installed, | |
or the damper blade must be cut or removed. | |
Damper |
|
Clamp | Damper |
| |
Damper |
|
Clamp |
|
Damper | Damper |
Masonry | Manufactured |
Fireplace | Fireplace |
Figure 4 - Attaching Damper Clamp | |
INSTALLING REMOTE CONTROL | |
ACCESSORY BRACKET | |
If installing optional remote control accessory you | |
will need to install the remote accessory bracket | |
for the receiver. |
|
Use screws provided to attach bracket to valve | |
bracket as shown in Figure 5. | |
Follow installation instructions included with | |
remote accessory. |
|
Valve Bracket |
|
Remote |
|
Bracket |
|
Figure 5 - Attaching Remote Bracket to | |
Valve Bracket |
6 | www.desatech.com |