Desa VGL30NRA, VGL24NRA Checking GAS Connections, Test Pressures In Excess Of 1/2 Psig 3.5 kPa

Page 15

INSTALLATION

Continued

WARNING: Use pipe joint sealant that is resistant to liquid petroleum (LP) gas.

We recommend that you install a sediment trap in supply line as shown in Figure 14. Locate sediment trap where it is within reach for cleaning. Install in piping system between fuel supply and heater. Locate sediment trap where trapped matter is not likely to freeze. A sediment trap traps moisture and contaminants. This keeps them from going into heater controls. If sediment trap is not installed or is installed wrong, heater may not run properly.

CAUTION: Avoid damage to regulator. Hold gas regulator with wrench when connecting it to gas piping and/or fittings.

CHECKING GAS CONNECTIONS

WARNING: Test all gas piping and connections, internal and external to unit, for leaks after installing or servicing. Correct all leaks at once.

WARNING:Neveruseanopen flame to check for a leak. Apply a noncorrosive leak detection fluid toalljoints.Bubblesformingshow a leak. Correct all leaks at once.

CAUTION: Make sure exter- nal regulator has been installed between propane/LP supply and heater.SeeguidelinesunderCon- necting to Gas Supply, page 11.

PRESSURE TESTING GAS SUPPLY PIPING SYSTEM

CSA Design-Certified

Equipment Shutoff Valve

With 1/8" NPT Tap*

Approved Flexible Gas Hose (if allowed by local codes)

From External Regulator (11" W.C.** to 14" W.C. Pressure)

Test Pressures In Excess Of 1/2 PSIG (3.5 kPa)

1.

Disconnect appliance with its appliance main

 

gas valve (control valve) and equipment

 

shutoff valve from gas supply piping system.

 

Pressures in excess of 1/2 psig will damage

 

heater regulator.

2.

Cap off open end of gas pipe where equipment

 

3" Minimum

 

 

Cap Pipe

Tee

Gas

Nipple

Joint

Sediment Trap

Control

Figure 14 - Gas Connection

*Purchase the optional CSA design-certified equipment shutoff valve from your dealer. See Accessories, page 29.

** Minimum inlet pressure for purpose of input adjustment.

 

shutoff valve was connected.

3.

Pressurize supply piping system by either

 

opening propane/LP supply tank valve for

 

propane/LP gas or opening main gas valve

 

located on or near gas meter for natural gas,

 

or using compressed air.

4.

Check all joints of gas supply piping system.

 

Apply noncorrosive leak detection fluid to gas

 

joints. Bubbles forming show a leak.

5.

Correct all leaks at once.

6.

Reconnect heater and equipment shutoff

 

valve to gas supply. Check reconnected fit-

 

tings for leaks.

Test Pressures Equal To or Less Than 1/2 PSIG (3.5 kPa)

1.Close equipment shutoff valve (see Figure 15, page 16).

2.Pressurize supply piping system by either opening propane/LP supply tank valve for propane/LP gas or opening main gas valve located on or near gas meter for natural gas, or using compressed air.

112882-01B

www.desatech.com

15

Image 15
Contents What to do if YOU Smell GAS Table of Contents Safety Information Safety Information Local Codes Product FeaturesRemote Control Accessories Product IdentificationUnusually Tight Construction AIR for Combustion VentilationProviding Adequate Ventilation Determining FRESH-AIR Flow for Fireplace LocationAIR for Combustion Ventilatioin Ventilation AIRVentilation Air From Inside Building Ventilation Air From Outdoors InstallationLog Check GAS TypeLog Size Side Wall Ceiling Minimum Firebox SizeDetermining Minimum Mantel Clearances When Using a Hood Mantel ClearancesMinimum Noncombustible Material Clearances Minimum Mantel Clearances Without Using Hood Floor Clearances Installing Damper Clamp Accessory for Vented OperationInstallation Items Needed Installing Heater Base AssemblyExternal Regulator With Vent Pointing Down Connecting to GAS SupplyChecking GAS Connections Test Pressures In Excess Of 1/2 Psig 3.5 kPaTest Pressures Equal To or Less Than 1/2 Psig 3.5 kPa Equipment Shutoff Valve Installing Optional Remote AccessoriesConnecting Wires Log #1 Installing LogsFor Your Safety Read Before Lighting Operating HeaterLighting Instructions To Turn OFF GAS To Appliance Manual Lighting ProcedureON/OFF Series Model Ghrcb Optional HAND-HELD Remote OperationThermostat Series Model GhrctbMain Burner Auto Shutoff FeatureInspecting Burners Pilot Flame PatternCleaning Maintenance Burner Injector Holder and Pilot AIR Inlet HoleLogs Observed Problem Possible Cause Remedy TroubleshootingSee Cleaning and Mainte Moisture/condensation noticed Statement above Gas leak. See WarningTechnical Service Wiring DiagramReplacement Parts Service HintsEquipment Shutoff Valve GA5010 Cleaning KIT CCKReceiver and HAND-HELD Remote Control KIT Ghrcb Series Information VideoIllustrated Parts Breakdown Parts List Warranty Information Keep this WarrantyLimited Warranty VENT-FREE GAS LOG Heaters