Desa VFRMV18PA, VFRMV18NA, VFRMV24NA, VFRMV24PA Mantel Clearances, Floor Clearances

Page 11

INSTALLATION

Continued

MANTEL CLEARANCES

In addition to meeting noncombustible material clearances, you must also meet required clearances between fireplace opening and mantel shelf. If you do not meet the clearances listed below, you will need a hood.

Determining Minimum Mantel Clearance If you meet minimum clearance between mantel shelf and top of fireplace opening, a hood is not required (see Figure 6).

Determining Minimum Mantel Clearance When Using a Hood

If minimum clearances in Figure 6 are not met, you must have a hood. When using a hood there are still certain minimum mantel clearances required. Follow minimum clearances shown in Figure 7 when using hood.

NOTICE: Surface temperatures ofadjacentwallsandmantelsbe- comehotduringoperation.Walls and mantels above the firebox may become hot to the touch. If installed properly, these tem- peratures meet the requirement of the national product standard. Follow all minimum clearances shown in this manual.

NOTICE: If your installation does not meet the minimum clear- ances shown, you must do one of the following:

operate the logs only with the

 

flue damper open and damper

 

clamp installed

raise the mantel to an ac-

10"

8"

6"

2 1/2"

Minimum Non-

 

(A)

 

Combustible

 

12"

Material

Mantel Shelf

28" 34 1/2" 38 5/8"

Underside of

Mantel Shelf

All minimum

42" distances are in inches

ceptable height

• remove the mantel

FLOOR CLEARANCES

A. If installing appliance on the floor level, you

must maintain the minimum distance of 14"

to combustibles (see Figure 8).

Minimum Non-

Distances to

Combustible

Underside of

Material Height

Mantel

Top of Fireplace Opening

B. If combustible materials are less than 14" to

the fireplace, you must install appliance at

least 5" above the combustible flooring (see

Figure 9).

Figure 6 - Minimum Mantel Clearances

Without Using Hood

12"

10"

8"

6"

2 1/2"

Minimum Non-

 

Combustible

8"

Material

 

Min.

Hood (GA6050, GA6052 or GA6053)

14 1/2" 18 5/8" 22 1/2"

Distances to

Underside of

Mantel

 

 

Combustible

Underside of

14"

Material

 

Min.

 

Mantel Shelf

 

 

 

Noncombustible

 

 

Material

All minimum

Figure 8 - Minimum Fireplace Clearances

26" distances are

in inches

If Installed at Floor Level

Top of Fireplace

 

Opening

 

Figure 7 - Minimum Mantel Clearances

Hearth

Combustible

 

 

Material

When Using Hood

5"

 

 

Min.

 

 

Figure 9 - Minimum Fireplace Clearances

 

Above Combustible Flooring

114745-01B

www.desatech.com

11

Image 11
Contents Ansi Z21.11.2a-2003 Ansi Z21.60-2003 VFRMV18NA, VFRMV18PA VFRMV24NA, VFRMV24PATable of Contents Safety Information Provide adequate clearances around air openings Unpacking Product IdentificationLocal Codes Determining FRESH-AIR Flow for Appliance Location AIR for Combustion VentilationProviding Adequate Ventilation Ventilation Air From Inside Building Ventilation AIRVentilation Air From Outdoors AIR for Combustion Ventilation InstallationCheck GAS Type Installation and Clearances for VENT-FREE OperationMinimum Noncombustible Material Clearances InstallationFloor Clearances Mantel ClearancesMasonry Manufactured FireplaceFireplace Installing Damper Clamp Accessory for Vented OperationInstalling Heater Assembly Installation Items NeededPropane/LP External Regulator Supply Tank Vent Pointing Down Connecting to GAS SupplyPropane/LP From Checking GAS ConnectionsTo Gas Control Valve Test Pressures Equal To or Less Than 1/2 Psig 3.5 kPa Test Pressures In Excess Of 1/2 Psig 3.5 kPaLighting Instructions For Your Safety Read Before LightingOperating Heater Shutting Off Heater To Turn OFF GAS To AppliancePropane/LP Natural Thermostat Series Model Ghrctb Manual Lighting ProcedureOptional HAND-HELD Remote Operation ON/OFF Series Model GhrcbCheck pilot flame pattern and burner flame pat- terns often Auto Shutoff FeatureInspecting Burners Pilot Flame PatternBurner Injector Holder and Pilot AIR Inlet Hole Cleaning MaintenanceBurner Flame Pattern Propane/LP Wiring DiagramObserved Problem Possible Cause Remedy TroubleshootingLow gas pressure Assembly Out when control knob is reSafety interlock system has Clean ODS/pilot seeTurning control knob to HI Cleaners or similar productsGas regulator defective Replace gas regulator Operation Processes and logs curing Hours of operationGas leak. See Warning Accessories SpecificationsReplacement Parts Technical ServiceFB36CA, FB42C Series CIRCULATING, FB36NCA, FB42NC Receiver and HAND-HELD Thermostat Remote Control KIT GhrctbReceiver and HAND-HELD Remote Control KIT Ghrcb WALL-MOUNT Thermostat Switch GWMT1VFRMV18NA, VFRMV18PA Illustrated Parts BreakdownParts List 114745-01B 114745-01B Limited Warranty VENT-FREE GAS LOG Heaters Warranty InformationKeep this Warranty

VFRMV24PA, VFRMV18PA, VFRMV18NA, VFRMV24NA, VFRMV24PA specifications

Desa's VFRMV series is a line of advanced heating solutions designed for energy efficiency and optimal comfort. The series includes models VFRMV24PA, VFRMV18PA, VFRMV18NA, VFRMV24NA, and VFRMV24PA. Each model is tailored to meet different heating demands, making them suitable for various residential and commercial applications.

One of the defining features of the VFRMV series is its inverter technology, which adjusts the compressor speed to match the heating or cooling needs of the environment. This capability not only enhances energy efficiency but also contributes to a quieter operation. Users can expect significant energy savings, as the inverter technology minimizes energy consumption during periods of low demand.

Each model in the VFRMV series boasts high-performance SEER and HSPF ratings, indicating superior energy efficiency and performance. With such ratings, these units are designed to make substantial contributions to reducing heating and cooling costs while complying with modern environmental standards.

The VFRMV24PA and VFRMV24NA models are particularly effective in larger spaces, offering robust heating capacities while remaining energy efficient. On the other hand, the VFRMV18PA and VFRMV18NA models cater to medium-sized spaces, ensuring that homes or offices maintain a comfortable atmosphere without overspending on energy bills.

Additional characteristics include advanced filtration systems that improve indoor air quality by removing dust, allergens, and pollutants. This feature is particularly beneficial for allergy sufferers or anyone keen on maintaining a healthier living environment.

Moreover, the VFRMV series incorporates smart home compatibility, allowing users to control their heating and cooling systems remotely via smartphone apps. This feature not only adds convenience but also enables better energy management, as users can adjust settings based on their schedules or occupancy patterns.

In summary, Desa's VFRMV series, comprising models VFRMV24PA, VFRMV18PA, VFRMV18NA, VFRMV24NA, and VFRMV24PA, offers a blend of efficiency, performance, and advanced technology. The use of inverter technology, high SEER and HSPF ratings, robust heating capabilities, advanced filtration, and smart home features make these units ideal choices for anyone looking to enhance comfort while minimizing energy expenses.