SPLIT SYSTEM HEATING PERFORMANCE

EXPANDED PERFORMANCE DATA

MODEL: G/VSZ130361A* / AR*F364216**

 

 

 

 

 

 

 

 

 

HEATING OPERATION

 

 

 

 

 

 

 

Outdoor Ambient Temperature

 

 

 

 

 

 

 

 

 

65

60

55

50

47

45

40

35

30

25

20

17

15

10

5

0

-5

-10

MBh

42.7

40.5

38.1

35.6

34.0

32.9

30.6

28.2

19.9

18.4

16.9

16.0

15.4

13.8

12.3

10.7

9.1

7.5

DELTA T

31.0

29.4

27.7

25.9

24.7

23.9

22.2

20.5

14.5

13.4

12.3

11.6

11.2

10.0

8.9

7.8

6.6

5.4

KW

3.07

3.01

2.96

2.90

2.87

2.85

2.79

2.74

2.82

2.76

2.70

2.67

2.64

2.58

2.52

2.46

2.40

2.35

AMPS

14.2

13.2

12.3

11.6

11.2

11.0

10.4

9.9

9.4

9.0

8.6

8.4

8.3

7.9

7.4

7.0

6.5

5.8

COP

4.07

3.93

3.77

3.59

3.47

3.39

3.21

3.02

2.07

1.95

1.84

1.76

1.71

1.57

1.42

1.27

1.11

0.93

EER

13.9

13.4

12.9

12.3

11.8

11.6

11.0

10.3

7.1

6.7

6.3

6.0

5.8

5.4

4.9

4.3

3.8

3.2

HI PR

372

356

343

328

320

314

302

290

277

265

254

248

244

235

226

216

209

201

LO PR

133

123

115

106

100

96

89

79

71

64

56

52

50

42

37

31

27

21

 

MODEL: G/VSZ130361B* / AR*F364216**

 

 

 

 

 

 

 

 

 

 

HEATING OPERATION

 

 

 

 

 

 

 

 

Outdoor Ambient Temperature

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

65

60

55

50

47

45

40

35

30

25

20

17

15

10

5

0

-5

-10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MBh

42.7

40.5

38.1

35.6

34.0

32.9

30.6

28.2

2.6

2.4

2.2

2.1

2.0

1.8

1.6

1.4

1.2

1.0

 

Delta T

33.0

31.2

29.4

27.5

26.2

25.4

23.6

21.8

2.0

1.9

1.7

1.6

1.6

1.4

1.2

1.1

0.9

0.8

 

KW

3.09

3.03

2.97

2.90

2.87

2.84

2.79

2.73

2.70

2.64

2.58

2.54

2.52

2.45

2.39

2.33

2.27

2.21

 

AMPS

14.0

13.0

12.1

11.4

11.0

10.8

10.2

9.7

9.3

8.8

8.4

8.2

8.1

7.7

7.2

6.8

6.3

5.6

 

COP

4.05

3.91

3.76

3.59

3.47

3.39

3.21

3.03

0.28

0.27

0.25

0.24

0.23

0.22

0.20

0.18

0.15

0.13

 

EER

13.8

13.4

12.8

12.3

11.8

11.6

11.0

10.4

1.0

0.9

0.9

0.8

0.8

0.7

0.7

0.6

0.5

0.4

 

HI PR

383

368

353

338

330

324

311

299

286

273

262

256

251

242

233

223

215

208

 

LO PR

133

123

115

106

100

96

89

79

71

64

56

52

50

42

37

31

27

21

 

MODEL: GSZ130363A* / AR*F364216**

 

 

 

 

 

 

 

 

 

HEATING OPERATION

 

 

 

 

 

 

 

 

Outdoor Ambient Temperature

 

 

 

 

 

 

 

 

 

65

60

55

50

47

45

40

35

30

25

20

17

15

10

5

0

-5

-10

 

MBh

42.7

40.5

38.1

35.6

34.0

32.9

30.6

28.2

19.9

18.4

16.9

16.0

15.4

13.8

12.3

10.7

9.1

7.5

 

DT

31.0

29.4

27.7

25.9

24.7

23.9

22.2

20.5

14.5

13.4

12.3

11.6

11.2

10.0

8.9

7.8

6.6

5.4

 

KW

2.90

2.84

2.79

2.73

2.70

2.68

2.63

2.58

2.42

2.37

2.32

2.29

2.27

2.22

2.17

2.12

2.07

2.02

 

AMPS

9.9

9.2

8.7

8.2

7.9

7.8

7.4

7.0

6.7

6.5

6.2

6.0

6.0

5.7

5.3

5.1

4.7

4.3

 

COP

4.32

4.17

4.00

3.81

3.68

3.60

3.41

3.21

2.41

2.27

2.14

2.05

1.99

1.82

1.65

1.48

1.29

1.08

 

EER

14.8

14.2

13.7

13.0

12.6

12.3

11.6

11.0

8.2

7.8

7.3

7.0

6.8

6.2

5.7

5.0

4.4

3.7

 

HI PR

383

368

353

338

330

324

311

299

286

273

262

256

251

242

233

223

215

208

 

LO PR

138

128

120

110

104

100

92

82

74

66

58

54

52

44

38

32

28

22

High pressure is measured at the liquid service valve (the smaller valve). Low pressure is measured at the gauge port connection.

Calculations are based on nominal CFM and 70 °F indoor dry bulb.

AMPS = Outdoor unit amps (comp.+fan) KW = Total system power

*Note: Shaded area is AHRI Rating Conditions at 47° outdoor ambient temberature

38

Page 38
Image 38
Goodman Mfg GSZ/VSZ 13 SEER service manual Outdoor Ambient Temperature, 34.0