13

COOLING PERFORMANCE DATA

EXPANDED PERFORMANCE DA TA

MODEL: G/V SZ130241B*/ AR*F18 2416* * COOLING OPERATION

Outdoor Ambient Temperature
65 75 85 95 105 115
Entering Indoor W et Bulb Temperature
IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71
MBh 22.5 23.4 25.6 - 22.0 22.8 25.0 - 21.5 22.3 24.4 - 21.0 21.7 23.8 - 19.9 20.6 22.6 - 18.4 19.1 21.0 -
S/T 0.75 0.63 0.44 - 0.78 0.65 0.45 - 0.80 0.67 0.46 - 0.83 0.69 0.48 - 0.86 0.72 0.50 - 0.86 0.72 0.50 -
T 17 15 11 - 18 15 12 - 18 15 12 - 18 15 12 - 17 15 11 - 16 14 11 -
900 KW 1.63 1.66 1.71 - 1.75 1.78 1.84 - 1.85 1.89 1.95 - 1.95 1.99 2.05 - 2.03 2.07 2.14 - 2.10 2.14 2.21 -
AMPS 6.1 6.2 6.4 - 6.5 6.7 6.9 - 7.1 7.3 7.5 - 7.6 7.8 8.0 - 8.1 8.3 8.5 - 8.5 8.8 9.0 -
HI PR 228 246 259 - 256 276 291 - 291 314 331 - 332 357 377 - 373 402 424 - 413 444 469 -
LO PR 103 110 120 - 109 116 127 - 114 121 132 - 119 127 139 - 125 133 145 - 129 138 150 -
MBh 21.9 22.7 24.8 - 21.4 22.2 24.3 - 20.9 21.6 23.7 - 20.4 21.1 23.1 - 19.3 20.0 22.0 - 17.9 18.6 20.3 -
S/T 0.72 0.60 0.42 - 0.74 0.62 0.43 - 0.76 0.64 0.44 - 0.79 0.66 0.46 - 0.82 0.68 0.47 - 0.82 0.69 0.48 -
T 18 16 12 - 18 16 12 - 18 16 12 - 18 16 12 - 18 16 12 - 17 15 11 -
70 800 KW 1.62 1.65 1.70 - 1.74 1.77 1.83 - 1.84 1.88 1.94 - 1.93 1.97 2.04 - 2.01 2.05 2.12 - 2.08 2.12 2.19 -
AMPS 6.0 6.2 6.3 - 6.5 6.6 6.9 - 7.0 7.2 7.4 - 7.5 7.7 8.0 - 8.0 8.2 8.5 - 8.5 8.7 9.0 -
HI PR 226 243 257 - 254 273 288 - 288 310 328 - 329 354 373 - 370 398 420 - 408 440 464 -
LO PR 102 109 119 - 108 115 126 - 112 120 131 - 118 126 137 - 124 132 144 - 128 136 149 -
MBh 20.2 20.9 22.9 - 19.7 20.4 22.4 - 19.3 20.0 21.9 - 18.8 19.5 21.3 - 17.8 18.5 20.3 - 16.5 17.1 18.8 -
S/T 0.69 0.58 0.40 - 0.72 0.60 0.42 - 0.74 0.61 0.43 - 0.76 0.63 0.44 - 0.79 0.66 0.46 - 0.80 0.66 0.46 -
T 18 16 12 - 19 16 12 - 19 16 12 - 19 16 12 - 18 16 12 - 17 15 11 -
700 KW 1.58 1.61 1.66 - 1.69 1.73 1.78 - 1.80 1.83 1.89 - 1.89 1.93 1.99 - 1.96 2.00 2.07 - 2.03 2.07 2.14 -
AMPS 5.9 6.0 6.2 - 6.3 6.5 6.7 - 6.8 7.0 7.2 - 7.3 7.5 7.7 - 7.8 8.0 8.2 - 8.2 8.4 8.7 -
HI PR 219 236 249 - 246 265 280 - 280 301 318 - 319 343 362 - 359 386 407 - 396 426 450 -
LO PR 99 10 6 115 - 105 112 122 - 109 116 127 - 115 122 133 - 120 128 139 - 124 132 144 -
MBh 22.92 23.60 25.54 27.41 22.39 23.05 24.95 26.78 21.85 22.50 24.36 26.14 21.32 21.95 23.76 25.50 20.25 20.85 22.57 24.23 18.76 19.32 20.91 22.44
S/T 0.86 0.77 0.58 0.37 0.89 0.79 0.60 0.39 0.91 0.81 0.62 0.40 0.94 0.84 0.64 0.41 0.97 0.87 0.66 0.42 0.98 0.88 0.67 0.43
T201815102019151120191511201915112019151119171410
900 KW 1.64 1.67 1.73 1.78 1.76 1.80 1.85 1.91 1.87 1.91 1.97 2.03 1.96 2.01 2.07 2.14 2.04 2.09 2.16 2.23 2.11 2.16 2.23 2.30
AMPS 6.1 6.3 6.5 6.7 6.6 6.8 7.0 7.2 7.2 7.3 7.6 7.9 7.7 7.8 8.1 8.4 8.1 8.3 8.6 8.9 8.6 8.8 9.1 9.5
HI PR 231 248 262 273 259 279 294 307 294 317 334 349 335 361 381 397 377 406 429 447 417 448 474 494
LO PR 104 111 121 129 110 117 128 137 115 122 133 142 121 128 140 149 126 134 147 156 131 139 152 162
MBh 22.3 22.9 24.8 26.6 21.7 22.4 24.2 26.0 21.2 21.8 23.6 25.4 20.7 21.3 23.1 24.8 19.7 20.2 21.9 23.5 18.2 18.8 20.3 21.8
S/T 0.82 0.73 0.55 0.36 0.85 0.76 0.57 0.37 0.87 0.78 0.59 0.38 0.90 0.80 0.61 0.39 0.93 0.83 0.63 0.40 0.94 0.84 0.63 0.41
T2119161121191611211916112120 16 11 21 19 16 11 20 18 15 10
75 800 KW 1.63 1.66 1.71 1.77 1.75 1.79 1.84 1.90 1.85 1.89 1.95 2.02 1.95 1.99 2.05 2.12 2.03 2.07 2.14 2.21 2.10 2.14 2.21 2.28
AMPS 6.1 6.2 6.4 6.6 6.5 6.7 6.9 7.2 7.1 7.3 7.5 7.8 7.6 7.8 8.0 8.3 8.1 8.3 8.5 8.9 8.5 8.8 9.0 9.4
HI PR 228 246 260 271 256 276 291 304 291 314 331 345 332 357 377 393 373 402 424 443 413 444 469 489
LO PR 103 110 120 128 109 116 127 135 114 121 132 141 119 127 139 148 125 133 145 155 129 138 150 160
MBh 20.5 21.1 22.9 24.6 20.1 20.7 22.4 24.0 19.6 20.2 21.8 23.4 19.1 19.7 21.3 22.9 18.2 18.7 20.2 21.7 16.8 17.3 18.7 20.1
S/T 0.79 0.70 0.53 0.34 0.82 0.73 0.55 0.36 0.84 0.75 0.57 0.36 0.86 0.77 0.58 0.38 0.90 0.80 0.61 0.39 0.90 0.81 0.61 0.39
T212016112220161122201611222016112120161120181510
700 KW 1.59 1.62 1.67 1.72 1.71 1.74 1.80 1.85 1.81 1.85 1.91 1.97 1.90 1.94 2.00 2.07 1.98 2.02 2.09 2.15 2.05 2.09 2.16 2.23
AMPS 5.9 6.0 6.2 6.5 6.4 6.5 6.7 7.0 6.9 7.1 7.3 7.6 7.4 7.6 7.8 8.1 7.8 8.0 8.3 8.6 8.3 8.5 8.8 9.1
HI PR 222 238 252 263 249 267 282 295 283 304 321 335 322 346 366 382 362 390 412 429 400 431 455 474
LO PR 100 107 117 124 106 113 123 131 110 117 128 136 116 123 134 143 121 129 141 150 125 133 146 155
Shaded area is ACCA (TVA) conditions IDB: Entering Indoor Dry Bulb Temperature KW=Total system pow er AMPS=outdoor unit amps (comp.+fan)
Hi
g
h and low pressures are measured at the liquid and suction service valves.

G/VSZ130241B*