SPLIT SYSTEM HEATING PERFORMANCE

EXPANDED PERFORM ANCE DAT A

MODEL: G/VSZ130181A* /

AR*F182416**

 

 

 

 

 

 

 

 

 

HEATING OPERATION

 

 

 

 

 

 

 

Outdoor Am bient Tem perature

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

65

60

55

50

47

45

40

35

30

25

20

17

15

10

5

0

-5

-10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MBh

21.4

20.2

19.0

17.8

17.0

16.5

15.3

14.1

13.3

12.3

11.3

10.7

10.3

9.2

8.2

7.2

6.1

5.0

DELTA T

33.0

31.2

29.4

27.5

26.2

25.4

23.6

21.8

20.6

19.0

17.5

16.5

15.9

14.3

12.7

11.0

9.4

7.7

KW

1.68

1.64

1.61

1.58

1.56

1.54

1.51

1.48

1.46

1.42

1.39

1.37

1.36

1.32

1.29

1.26

1.23

1.19

AMPS

7.3

6.7

6.3

5.9

5.7

5.6

5.3

5.0

4.8

4.6

4.3

4.2

4.2

4.0

3.7

3.5

3.2

2.9

COP

3.73

3.60

3.46

3.30

3.19

3.12

2.96

2.79

2.68

2.53

2.39

2.29

2.22

2.04

1.86

1.66

1.46

1.22

EER

12.8

12.3

11.8

11.3

10.9

10.7

10.1

9.5

9.2

8.7

8.2

7.8

7.6

7.0

6.3

5.7

5.0

4.2

HI PR

392

375

361

345

337

331

318

305

292

279

268

262

257

247

238

228

220

212

LO PR

145

134

126

115

109

105

96

86

77

69

61

57

55

46

40

34

29

23

MODEL: G/VSZ130241A* / AR*F182416**

 

 

 

 

 

 

 

 

 

 

HEATING OPERATION

 

 

 

 

 

 

 

 

Outdoor Am bient Tem perature

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

65

60

55

50

47

45

40

35

 

30

25

20

17

15

10

5

0

-5

-10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MBh

28.9

27.4

25.8

24.1

23.0

22.3

20.7

19.1

 

16.7

15.4

14.2

13.4

12.9

11.6

10.3

9.0

7.6

6.3

DT

32.6

30.9

29.1

27.2

26.0

25.2

23.4

21.6

 

18.9

17.4

16.0

15.1

14.6

13.1

11.6

10.1

8.6

7.1

KW

2.20

2.15

2.11

2.07

2.04

2.02

1.98

1.94

 

1.75

1.71

1.67

1.65

1.63

1.59

1.56

1.52

1.48

1.44

AMPS

9.7

9.0

8.4

7.9

7.6

7.5

7.0

6.7

 

6.4

6.1

5.8

5.6

5.6

5.3

4.9

4.6

4.3

3.8

COP

3.85

3.72

3.57

3.41

3.30

3.23

3.06

2.89

 

2.79

2.63

2.48

2.38

2.31

2.13

1.93

1.73

1.51

1.27

EER

13.2

12.7

12.2

11.7

11.3

11.0

10.5

9.9

 

9.5

9.0

8.5

8.1

7.9

7.3

6.6

5.9

5.2

4.4

HI PR

407

390

375

358

350

343

330

317

 

303

290

278

272

267

257

247

237

228

220

LO PR

135

126

118

108

102

98

90

80

 

73

65

57

53

51

43

37

31

27

22

MODEL: G/VSZ130241B*/ AR*F182416**

 

 

 

 

 

 

 

 

 

 

 

HEATING OPERATION

 

 

 

 

 

 

 

 

Outdoor Ambient Temperature

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

65

60

55

50

 

47

45

40

35

 

30

25

20

17

15

10

5

0

-5

-10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MBh

28.9

27.4

25.8

24.1

 

23.0

22.3

20.7

19.1

 

16.9

15.6

14.3

13.6

13.0

11.7

10.4

9.1

7.7

6.3

Delta T

33.5

31.7

29.8

27.9

 

26.6

25.8

24.0

22.1

 

19.5

18.0

16.6

15.7

15.1

13.6

12.0

10.5

8.9

7.3

KW

2.17

2.12

2.08

2.04

 

2.02

2.00

1.96

1.91

 

1.80

1.76

1.72

1.70

1.68

1.64

1.60

1.57

1.52

1.49

AMPS

10.1

9.3

8.7

8.2

 

7.9

7.7

7.3

6.9

 

6.6

6.3

6.0

5.9

5.8

5.5

5.2

4.9

4.5

4.0

COP

3.91

3.77

3.62

3.46

 

3.34

3.27

3.10

2.92

 

2.74

2.59

2.44

2.33

2.27

2.08

1.89

1.69

1.48

1.25

EER

13.3

12.9

12.4

11.8

 

11.4

11.2

10.6

10.0

 

9.4

8.8

8.3

8.0

7.7

7.1

6.5

5.8

5.1

4.3

HI PR

413

395

380

364

 

355

348

335

321

 

308

294

282

275

271

260

250

240

231

223

LO PR

131

122

114

105

 

99

95

88

78

 

70

63

55

51

50

42

36

30

27

21

M ODEL: G/VSZ130301A* /

AR*F30301**

 

 

 

 

 

 

 

 

 

 

HEATING OPERATION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdo or Am bie nt Te m pe r atur e

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

65

60

55

50

47

45

40

35

 

30

25

20

17

15

10

5

0

-5

-10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MBh

33.2

31.4

29.6

27.6

26.4

25.6

23.8

21.9

 

19.9

18.4

16.9

16.0

15.4

13.8

12.3

10.7

9.1

7.5

DELTA T

29.3

27.7

26.1

24.4

23.3

22.6

21.0

19.3

 

17.6

16.2

14.9

14.1

13.6

12.2

10.8

9.4

8.0

6.6

KW

2.52

2.47

2.42

2.37

2.35

2.32

2.28

2.23

 

2.37

2.32

2.26

2.23

2.21

2.16

2.11

2.05

2.00

1.95

A MPS

9.7

9.0

8.5

8.0

7.7

7.6

7.2

6.9

 

6.6

6.3

6.0

5.9

5.8

5.6

5.2

5.0

4.6

4.2

COP

3.86

3.72

3.57

3.41

3.29

3.22

3.05

2.88

 

2.46

2.32

2.19

2.10

2.04

1.88

1.70

1.52

1.34

1.12

EER

13.2

12.7

12.2

11.6

11.3

11.0

10.4

9.8

 

8.4

7.9

7.5

7.2

7.0

6.4

5.8

5.2

4.6

3.8

HI PR

366

351

337

323

315

309

297

285

 

273

261

250

244

240

231

222

213

205

198

LO PR

129

119

112

103

97

93

86

76

 

69

62

54

50

49

41

35

30

26

20

High pressure is measured at the liquid service valve (the smaller valve). Low pressure is measured at the gauge port connection.

Calculations are based on nominal CFM and 70 °F indoor dry bulb.

AMPS = Outdoor unit amps (comp.+fan) KW = Total system power

*Note: Shaded area is AHRI Rating Conditions at 47° outdoor ambient temberature

37

Page 37
Image 37
Goodman Mfg GSZ/VSZ 13 SEER Split System Heating Performance, Odel G/VSZ130301A AR*F30301, Outdoor Am bient Tem perature