SPLIT SYSTEM HEATING PERFORMANCE
EXPANDED PERFORMANCE DATA
MODEL: GSZ130483A* / AR*F486016** |
|
|
|
|
|
|
|
|
| HEATING OPERATION | ||||||||
|
|
|
|
|
|
| Outdoor Ambient Temperature |
|
|
|
|
|
|
| ||||
| 65 | 60 | 55 | 50 | 47 | 45 | 40 | 35 | 30 | 25 | 20 | 17 | 15 | 10 | 5 | 0 | ||
MBh | 55.3 | 52.4 | 49.3 | 46.1 | 44.0 | 42.6 | 39.6 | 36.5 | 33.6 | 31.1 | 28.6 | 27.0 | 26.0 | 23.3 | 20.7 | 18.0 | 15.4 | 12.6 |
DT | 32.0 | 30.3 | 28.5 | 26.7 | 25.5 | 24.7 | 22.9 | 21.1 | 19.5 | 18.0 | 16.5 | 15.6 | 15.0 | 13.5 | 12.0 | 10.4 | 8.9 | 7.3 |
KW | 3.94 | 3.87 | 3.80 | 3.72 | 3.68 | 3.65 | 3.58 | 3.51 | 3.49 | 3.42 | 3.34 | 3.30 | 3.27 | 3.20 | 3.12 | 3.05 | 2.98 | 2.90 |
AMPS | 11.1 | 10.3 | 9.7 | 9.1 | 8.8 | 8.6 | 8.2 | 7.8 | 7.5 | 7.2 | 6.8 | 6.7 | 6.6 | 6.3 | 5.9 | 5.6 | 5.2 | 4.7 |
COP | 4.10 | 3.96 | 3.80 | 3.62 | 3.50 | 3.42 | 3.24 | 3.05 | 2.82 | 2.66 | 2.50 | 2.39 | 2.33 | 2.14 | 1.94 | 1.73 | 1.51 | 1.27 |
EER | 14.0 | 13.5 | 13.0 | 12.4 | 11.9 | 11.7 | 11.1 | 10.4 | 9.6 | 9.1 | 8.6 | 8.2 | 7.9 | 7.3 | 6.6 | 5.9 | 5.2 | 4.3 |
HI PR | 386 | 370 | 356 | 340 | 332 | 326 | 313 | 300 | 288 | 275 | 264 | 258 | 253 | 243 | 234 | 224 | 216 | 209 |
LO PR | 126 | 117 | 110 | 101 | 95 | 91 | 84 | 75 | 68 | 60 | 53 | 49 | 48 | 40 | 35 | 29 | 26 | 20 |
MODEL: GSZ130484A* / AR*F486016** |
|
|
|
|
|
|
|
|
| HEATING OPERATION | ||||||||
|
|
|
|
|
|
| Outdoor Ambient Temperature |
|
|
|
|
|
|
| ||||
| 65 | 60 | 55 | 50 | 47 | 45 | 40 | 35 | 30 | 25 | 20 | 17 | 15 | 10 | 5 | 0 | ||
MBh | 55.3 | 52.4 | 49.3 | 46.1 | 44.0 | 42.6 | 39.6 | 36.5 | 33.6 | 31.1 | 28.6 | 27.0 | 26.0 | 23.3 | 20.7 | 18.0 | 15.4 | 12.6 |
DT | 32.0 | 30.3 | 28.5 | 26.7 | 25.5 | 24.7 | 22.9 | 21.1 | 19.5 | 18.0 | 16.5 | 15.6 | 15.0 | 13.5 | 12.0 | 10.4 | 8.9 | 7.3 |
KW | 3.94 | 3.87 | 3.80 | 3.73 | 3.68 | 3.65 | 3.58 | 3.51 | 3.49 | 3.42 | 3.34 | 3.30 | 3.27 | 3.20 | 3.12 | 3.05 | 2.98 | 2.90 |
AMPS | 6.1 | 5.7 | 5.4 | 5.1 | 4.9 | 4.8 | 4.6 | 4.4 | 4.2 | 4.0 | 3.8 | 3.8 | 3.7 | 3.5 | 3.3 | 3.2 | 3.0 | 2.7 |
COP | 4.10 | 3.96 | 3.80 | 3.62 | 3.50 | 3.42 | 3.24 | 3.05 | 2.82 | 2.66 | 2.50 | 2.39 | 2.33 | 2.14 | 1.94 | 1.73 | 1.51 | 1.27 |
EER | 14.0 | 13.5 | 13.0 | 12.4 | 11.9 | 11.7 | 11.1 | 10.4 | 9.6 | 9.1 | 8.6 | 8.2 | 7.9 | 7.3 | 6.6 | 5.9 | 5.2 | 4.3 |
HI PR | 386 | 370 | 356 | 340 | 332 | 326 | 313 | 300 | 288 | 275 | 264 | 258 | 253 | 243 | 234 | 224 | 216 | 209 |
LO PR | 126 | 117 | 110 | 101 | 95 | 91 | 84 | 75 | 68 | 60 | 53 | 49 | 48 | 40 | 35 | 29 | 26 | 20 |
MODEL: GSZ130603A* /AR*F486016** |
|
|
|
|
|
|
|
|
| HEATING OPERATION | ||||||||
|
|
|
|
|
|
| Outdoor Ambient Temperature |
|
|
|
|
|
|
| ||||
| 65 | 60 | 55 | 50 | 47 | 45 | 40 | 35 | 30 | 25 | 20 | 17 | 15 | 10 | 5 | 0 | ||
MBh | 72.9 | 69.0 | 65.0 | 60.7 | 58.0 | 56.2 | 52.2 | 48.1 | 44.9 | 41.4 | 38.1 | 36.0 | 34.7 | 31.1 | 27.6 | 24.0 | 20.5 | 16.8 |
DT | 37.5 | 35.5 | 33.4 | 31.2 | 29.8 | 28.9 | 26.9 | 24.8 | 23.1 | 21.3 | 19.6 | 18.5 | 17.8 | 16.0 | 14.2 | 12.4 | 10.6 | 8.6 |
KW | 5.21 | 5.11 | 5.01 | 4.91 | 4.86 | 4.81 | 4.72 | 4.62 | 4.65 | 4.55 | 4.45 | 4.39 | 4.34 | 4.24 | 4.14 | 4.04 | 3.94 | 3.84 |
AMPS | 13.1 | 12.2 | 11.4 | 10.7 | 10.3 | 10.1 | 9.5 | 9.0 | 8.6 | 8.2 | 7.8 | 7.7 | 7.6 | 7.2 | 6.7 | 6.3 | 5.8 | 5.2 |
COP | 4.10 | 3.95 | 3.79 | 3.62 | 3.50 | 3.42 | 3.24 | 3.05 | 2.82 | 2.67 | 2.51 | 2.40 | 2.34 | 2.15 | 1.95 | 1.74 | 1.53 | 1.28 |
EER | 14.0 | 13.5 | 13.0 | 12.4 | 11.9 | 11.7 | 11.1 | 10.4 | 9.6 | 9.1 | 8.6 | 8.2 | 8.0 | 7.3 | 6.7 | 6.0 | 5.2 | 4.4 |
HI PR | 416 | 399 | 383 | 367 | 358 | 351 | 338 | 324 | 310 | 296 | 285 | 278 | 273 | 262 | 252 | 242 | 233 | 225 |
LO PR | 133 | 123 | 115 | 106 | 100 | 96 | 89 | 79 | 71 | 64 | 56 | 52 | 50 | 42 | 37 | 31 | 27 | 21 |
MODEL: GSZ130604A* /AR*F486016** |
|
|
|
|
|
|
|
|
| HEATING OPERATION | ||||||||
|
|
|
|
|
|
| Outdoor Ambient Temperature |
|
|
|
|
|
|
| ||||
| 65 | 60 | 55 | 50 | 47 | 45 | 40 | 35 | 30 | 25 | 20 | 17 | 15 | 10 | 5 | 0 | ||
MBh | 72.9 | 69.0 | 65.0 | 60.7 | 58.0 | 56.2 | 52.2 | 48.1 | 44.9 | 41.4 | 38.1 | 36.0 | 34.7 | 31.1 | 27.6 | 24.0 | 20.5 | 16.8 |
DT | 37.5 | 35.5 | 33.4 | 31.2 | 29.8 | 28.9 | 26.9 | 24.8 | 23.1 | 21.3 | 19.6 | 18.5 | 17.8 | 16.0 | 14.2 | 12.4 | 10.6 | 8.6 |
KW | 5.21 | 5.11 | 5.01 | 4.91 | 4.86 | 4.81 | 4.72 | 4.62 | 4.65 | 4.55 | 4.45 | 4.39 | 4.34 | 4.24 | 4.14 | 4.04 | 3.94 | 3.84 |
AMPS | 6.5 | 6.1 | 5.7 | 5.4 | 5.2 | 5.1 | 4.8 | 4.6 | 4.4 | 4.2 | 4.1 | 4.0 | 3.9 | 3.7 | 3.5 | 3.3 | 3.1 | 2.8 |
COP | 4.10 | 3.95 | 3.79 | 3.62 | 3.50 | 3.42 | 3.24 | 3.05 | 2.82 | 2.67 | 2.51 | 2.40 | 2.34 | 2.15 | 1.95 | 1.74 | 1.53 | 1.28 |
EER | 14.0 | 13.5 | 13.0 | 12.4 | 11.9 | 11.7 | 11.1 | 10.4 | 9.6 | 9.1 | 8.6 | 8.2 | 8.0 | 7.3 | 6.7 | 6.0 | 5.2 | 4.4 |
HI PR | 416 | 399 | 383 | 367 | 358 | 351 | 338 | 324 | 310 | 296 | 285 | 278 | 273 | 262 | 252 | 242 | 233 | 225 |
LO PR | 133 | 123 | 115 | 106 | 100 | 96 | 89 | 79 | 71 | 64 | 56 | 52 | 50 | 42 | 37 | 31 | 27 | 21 |
High pressure is measured at the liquid service valve (the smaller valve). Low pressure is measured at the gauge port connection.
Calculations are based on nominal CFM and 70 °F indoor dry bulb.
AMPS = Outdoor unit amps (comp.+fan) KW = Total system power
*Note: Shaded area is AHRI Rating Conditions at 47° outdoor ambient temberature