Desa HDVF3018N, HDVF3018P installation manual Ventilation AIR, Ventilation Air From Inside Building

Page 7

AIR FOR COMBUSTION

AND VENTILATION

Continued

Example:

 

40,000

 

Gas water heater

_

Btu/Hr

Vent-free fireplace

+_

39,000

Btu/Hr

the two spaces (see options 1 and 2, Figure 2). You can also remove door into adjoining room (see option 3, Figure 2). Follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

Total

=_

79,000

Btu/Hr

4.Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

__________ Btu/Hr (maximum the space can support)

__________ Btu/Hr (actual amount of Btu/Hr used) Example: 51,200 Btu/Hr (maximum the space

can support)

79,000 Btu/Hr (actual amount of Btu/Hr used)

Ventilation

 

Grills

 

Into Adjoining

Or

Room,

Remove

Option 1

Door into

 

 

Adjoining

 

Room,

 

Option

 

3

12"

Ventilation Grills

Into Adjoining Room,

Option 2

The space in the example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support. You must provide ad- ditional fresh air. Your options are as follows:

A.Rework worksheet, adding the space of an adjoin- ing room. If the extra space provides an unconfined space, remove door to adjoining room or add ventilation grills between rooms. See Ventilation Air From Inside Building.

B.Vent room directly to the outdoors. See Ventila- tion Air From Outdoors.

C.Install a lower Btu/Hr fireplace, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an un- confined space. You will need no additional fresh air ventilation.

WARNING: If the area in which the heater may be oper- ated is smaller than that defined as an unconfined space or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of the methods described in the National Fuel Gas Code, ANSI Z223.1/NFPA54 Section 5.3 or applicable local codes.

VENTILATION AIR

Ventilation Air From Inside Building

This fresh air would come from an adjoining un- confined space. When ventilating to an adjoining unconfined space, you must provide two perma- nent openings: one within 12" of the ceiling and one within 12" of the floor on the wall connecting

12"

Figure 2 - Ventilation Air from Inside

Building

Ventilation Air From Outdoors

Provide extra fresh air by using ventilation grills or ducts. You must provide two permanent openings: one within 12" of the ceiling and one within 12" of the floor. Connect these items directly to the outdoors or spaces open to the outdoors. These spaces include attics and crawl spaces. Follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

IMPORTANT: Do not provide openings for inlet or outlet air into attic if attic has a thermostat- controlled power vent. Heated air entering the attic will activate the power vent.

 

Outlet

Ventilated

 

Attic

 

Air

 

 

Outlet

 

 

Air

 

To Attic

 

 

 

 

To

 

 

Crawl

Inlet

 

Space

 

 

Air

 

 

 

Inlet Air

Ventilated

 

Crawl Space

 

 

Figure 3 - Ventilation Air from Outdoors

119421-01Awww.desatech.com

Image 7
Contents Variable Manually Controlled Models Also Design-Certified As Vented Decorative AppliancesSafety Information Table of ContentsSafety Information Local Codes Air for Combustion Ventilation Product FeaturesProduct Identification UnpackingProviding Adequate Ventilation AIR for Combustion VentilationDetermining FRESH-AIR Flow for Heater Location Ventilation Air From Inside Building Ventilation AIRVentilation Air From Outdoors Check GAS Type InstallationInstallation and Clearances InstallationVent-Free Operation Only Marble, Tile, etc. Above Fireplace Mantel ClearancesFloor Clearances Installing Damper Clamp Accessory for Vented OperationArea of Various Standard Round Flues Installing Heater Base AssemblyInstallation Items Needed Chimney Minimum PermanentAttaching Base Assembly to Fireplace Floor Dual Burner Model Connecting to GAS SupplyPropane/LP Checking GAS ConnectionsNatural Pressure Testing Heater Gas Connections Installing LogsTest Pressures Equal To or Less Than Psig 3.5 kPa Installing Front Log #1 Operating Heater For Your Safety Read Before LIGHTING  LIGHTING INSTRUCTIONS   TO Turn OFF GAS to APPLIANCE   MANUAL Lighting ProcedureOperating Heater  VARIABLE Control OperationBurner Primary AIR Holes Cleaning MaintenanceInspecting Burners Pilot Flame PatternBlow air into the primary air holes on the injector holder LogsObserved Problem Possible Cause Remedy TroubleshootingMaintenance, TroubleshootingStatement above Gas leak. See WarningReplacement Parts SpecificationsTechnical Service Service HintsEquipment Shutoff Valve GA5010 AccessoriesFireplace Hood Variable Manually-Controlled Models HDVF3018P and HDVF3018N Illustrated Parts BreakdownParts List Keep this Warranty Warranty InformationLimited Warranty VENT-FREE GAS LOG Heaters

HDVF3018N, HDVF3018P specifications

The Desa HDVF3018P and HDVF3018N are advanced heating solutions that exemplify innovation and efficiency in the heating appliance market. They are designed to provide reliable and effective heating for residential and commercial spaces, ensuring comfort during colder months while also prioritizing energy efficiency.

One of the standout features of the HDVF3018 series is its powerful heat output. With an impressive BTU rating, these units are capable of efficiently warming large areas, making them ideal for both homes and businesses. This makes them a popular choice for those looking to maintain a comfortable environment during winter.

In terms of design, the HDVF3018P and HDVF3018N boast sleek, modern aesthetics that allow them to blend seamlessly with various interior styles. Their compact footprints make them suitable for smaller spaces without sacrificing performance. Additionally, these units are equipped with advanced safety features, including automatic shut-off mechanisms that ensure reliable operation without compromising user safety.

The HDVF3018 series incorporates cutting-edge technology to optimize heating efficiency. For instance, they utilize a variable speed blower, which not only enhances heat distribution but also reduces energy consumption. This feature helps residents and businesses save on heating costs while decreasing their environmental impact.

Another notable characteristic of these units is their user-friendly controls. The HDVF3018P and HDVF3018N come with intuitive interfaces that allow users to easily adjust temperature settings and programming schedules. This ensures that the heating systems operate at desired levels without needing constant manual adjustments.

In terms of fuel options, the HDVF3018 series is versatile, catering to various preferences and needs. Whether using propane, natural gas, or other fuel types, these units provide flexibility for users to choose the best option for their specific heating requirements.

Furthermore, both models are engineered with durability in mind. High-quality materials contribute to their longevity, making them a worthwhile investment for those seeking dependable heating solutions.

In summary, the Desa HDVF3018P and HDVF3018N deliver a powerful combination of reliable performance, modern design, and advanced technology. Their ability to efficiently heat spaces while providing user-friendly operation and safety make them excellent choices for anyone in need of a high-quality heating appliance.