LX Series Direct Vent Gas Fireplace

VENTING INSTALLATION

 

 

installation planning

There are two basic types of direct-vent installation:

Horizontal Termination

Vertical Termination

It is important to select the proper length of vent pipe for the type of termination you choose. It is also important to note the wall thickness.

WARNING

Never run the vent pipe level or downward. This may cause excessive temperatures which could cause a fire.

for horizontal termination

Select the amount of vertical rise desired. All horizontal run of venting must have minimum 1/4" rise for every 12" of run towards the termination.

You may use up to three 90° elbows in this vent configuration. Refer to Horizontal (Through the Wall) Termination Configurations on Page 18.

For vertical termination

Measure the distance from the fireplace floor to the ceiling. Add the ceiling thickness, the vertical rise in an attic or second story, and allow for sufficient vent height above the roof line.

NOTE: You may use two 45° elbows in place of a 90° elbow. You must follow rise to run ratios when using 45° elbows. The appliance is approved for use with three 90° elbows maximum or a combina- tion of 90° and 45° elbows up to a maximum of 270°.

For two-story applications, firestops are required at each floor level. If an offset is needed in the attic, additional pipe and elbows will be required.

You may use a chase with a vent termination with exposed pipe on the exterior of the house. See Installing Vent System in a Chase below. If pipe is enclosed in chase, it is not exposed.

It is very important that the venting system maintain its balance between the combustion air intake and the flue gas exhaust. Certain limitations apply to vent configurations and must be strictly followed.

Installing a vent system in an outside chase

A chase is a vertical boxlike structure built to enclose venting that runs along the outside of a build- ing. A chase is required for such venting.

NOTICE

Treatment of firestops and construction of the chase may vary from building type to building type. These instructions are not substitutes for the requirements of local building codes. You must follow all local building codes.

NOTICE

When installing in a chase, you should insulate the chase as you would the outside walls of your home. This is especially important in cold climates. Insulation should be considered a combustible material. Maintain proper clearances to all combustible materials.

WARNING

Always maintain minimum clearances around vent systems. The minimum clearances to combustibles for horizontal vent pipe are 3" at the top and 1" at the sides and bottom of the vent system until the pipe penetrates the nearest vertical wall. A 1" minimum clearance all around the pipe must be maintained. Do not pack the open air spaces with insulation or other materials. This could cause high temperatures and may present a fire hazard.

14

51D0528

Image 14
Contents Lexington Direct Vent Gas Fireplace What to do if YOU Smell GASContents CongratulationsOwner Important Safety InformationInstaller Please leave these instructions with the appliancePlease Read the Following Carefully Important Safety InformationCode Approval High Elevations Product SpecificationsGas Specifications & Orifice Size GAS pressuresFireplace and Framing Dimensions LX32 Fireplace & Framing DimensionsFireplace Framing Installation InformationBefore You Start Installation Information Fireplace LocationMantel clearances Hearth requirements ClearancesClearances to combustibles For the exact width of the faceSecure Fireplace to floor or framing Finishing Material4 102 mm flue pipe should be After conversion to top vent configurationOptional top vent application Concentric within the 6B\, 175 mm outerFailure to follow these instructions will void the warranty Installation precautionsVenting Installation Venting Installation Combustible Clearances for Vent PipeFor horizontal termination Installation planningInstalling a vent system in an outside chase For vertical terminationVenting Installation General Venting Information Termination LocationVent Graph should be read in conjunction with How To Use The Vent GraphFollowing vent installation instructions to determine SystemWall. This will cause a fire hazard Rear Wall Vent installationDo not recess vent termination into any Horizontal through the wall ter- mination configurations Elbow Total Angular Variation 270 Example According to the vent graph Page 16Maximum horizontal vent length in a system with a Below Grade Installations Vertical through-the-roof applica- tionsInstallation for Vertical TERMINA- Tion Flat Ceiling InstallationFirestop. Be sure pipe and elbow connections are Assemble the desired lengths of pipe and elbows necEssary to reach from the burner system flue up through Fully twist-locked. Page 17, FigureInstalling gas piping to fireplace location Check gas typeNatural Gas Propane/LPElectrical Wiring Heater 110V circuit Remote Wall mounted SwitchDo not connect wall switch to Glass Frame Removal Final InstallationReinstalling clamps, keep fingers clear Each clamp has a quick spring force. WhenLogs supplied with the unit LOG PlacementInstalL logs and rock wool ember material in firebox Personal injuryRear Log #1 Place top left log #4 on two pins on left mid log. Figure Center Log #8 Air Space Under Rear Log 20 to 50% 30 to AIR Restrictor Adjustment100% Factory Setting Facing Installation Install FacingOperating Instructions Leak testing Never use an open flame to check for gas leaksInitial lighting Approved leak testing method Operating InstructionsPilot position Main burner switchLighting the burner Firebox Cleaning Cleaning and maintenanceCleaning glass Venting systemWiring Diagram for Blower BlowerTroubleshooting Observed Problem Possible Cause RemedyReplacement Parts Replacement Parts Optional Accessories Nantucket Decorative ArchOptional Accessories LX Series Direct Vent Gas Fireplace LX Series Direct Vent Gas Fireplace Carbon Monoxide Detector Requirements Basic Warranty Lifetime WarrantyFive Year Warranty If Warranty Service is NeededMhsc Model EnerGuide Ratings

LX36DV, LX32DV specifications

The Monessen Hearth LX36DV and LX32DV are premium direct vent gas fireplaces designed to provide warmth and ambiance in any living space. Both models showcase innovative engineering and elegant designs, making them a popular choice for homeowners seeking efficient heating solutions.

One of the main features of the LX36DV and LX32DV is their versatile design. Both units are available in various configurations, allowing them to seamlessly integrate into a range of architectural styles, from contemporary to traditional. Their clean face design and beveled edges contribute to a sleek, attractive appearance that enhances any room's aesthetic.

Efficiency is another standout characteristic of these fireplaces. Equipped with advanced gas burner technology, the LX36DV and LX32DV deliver an impressive heat output while maintaining a high efficiency rating. The direct vent system ensures that combustion gases are safely expelled outside, making it a safe alternative to traditional wood-burning fireplaces. This feature not only improves indoor air quality but also contributes to overall energy conservation.

The LX36DV and LX32DV also offer customizable options to enhance user experience. Customers can choose from various front styles, finishes, and media options, allowing for personalization that matches individual tastes. The addition of decorative glass or colorful crushed fireglass can transform the look of the fireplace, creating a unique focal point in the room.

In terms of technology, both models are equipped with remote control capabilities, allowing users to adjust flame height and heat settings from anywhere in the room. This convenience ensures optimal comfort while eliminating the need for manual adjustments. Additionally, these fireplaces come with innovative electronic ignition systems that provide reliable startup every time.

Safety features are prioritized in the design of the LX36DV and LX32DV. Each unit comes with safety screen options and can be modified to include childproof doors, making them a practical choice for families. The advanced flame sensing technology provides peace of mind as it automatically adjusts in response to room conditions.

In conclusion, the Monessen Hearth LX36DV and LX32DV are exemplary gas fireplaces that combine style, efficiency, and safety. With their customizable design, advanced technologies, and user-friendly features, these models stand out in the market, offering unrivaled warmth and elegance to any home. Whether you are heating a cozy family room or making a statement in a grand living area, these fireplaces provide both functionality and charm.