Monessen Hearth LX32DV Rear Wall Vent installation, Do not recess vent termination into any

Page 17

VENTING INSTALLATION

Rear Wall Vent installation

When installed as a rear vent unit this appliance may be vented directly to a termination located on the rear outside termination behind the appliance

45° elbows may only be attached to rear when used to direct the flue skyward (to achieve additional rise). Do not attach 45° elbows to rear of appliance in which the flue turns either left or right and terminates horizontal.

The maximum horizontal distance between the rear of the appliance and the outside face of the outside termination is 20" (508 m). Figure 15

LX Series Direct Vent Gas Fireplace

2.Rigid vent pipes and fittings have special twist-lock connections. Assemble the desired combination of pipe and elbows to the appliance adaptor with pipe seams oriented towards the wall or floor.

Twist-lock Procedure: The female ends of the pipes and fittings have three locking lugs (indentations). These lugs will slide straight into matching slots on the male end of adjacent pipes and fittings. Push the pipe sections together and twist one section clockwise approximately one-quarter turn until the sections are fully locked. Figure 16

20"(508 mm)

Maximum

Figure 14 -

DVR584

Rear Vent Application,

 

Maximum Horizontal Distance

 

1.Locate and cut the vent opening in the wall. For com- bustible walls first frame in opening. Figure 15

NOTE: Horizontal runs of vent must be supported every 3' (914 mm). Use wall straps for this purpose.

Figure 16 -

Rigid Vent Pipe Connections

Female

Locking Lugs

Male Slots

FP1953

Combustible Walls: Cut a 11Z\x"H x 9Z\x" W (292 x 24

mm)hole through the exterior wall and frame as shown. Figure 15

Noncombustible Walls: Hole opening should be 7Z\x" (190 mm) in diameter.

Vent Opening for Combustible Walls

3. Attach vent pipe assembly to the fireplace. Set fireplace

in front of its permanent location to insure minimum

clearances. Mark the wall for a 11Z\x"H x 9Z\x"W (292 x 24

mm) rectangle hole (for noncombustible material such

as masonry block or concrete, a 7Z\x" [190 mm] diameter

hole is acceptable). Figure 15. The center of the hole

should line up with the center line of the horizontal rigid

9Z\x"

(241 mm)

11Z\x"

(292 mm)

Fireplace Hearth

Framing Detail

vent pipe end. Be sure to allow for minimum rise. Cut

a 11Z\x" x 9Z\x" (292 X 241 mm) rectangle hole through

combustible exterior wall (7Z\x" [190 mm] diameter hole

if noncombustible). Frame as necessary. Allow 1/4"

minimum rise per foot. Figure 15

4. Apply a bead of non-hardening mastic around the

outside edge of vent cap. Position the vent cap in the

center of hole on the exterior wall with the word “UP”

on the vent cap facing up. Insure proper clearance of

1" to combustibles is maintained. Attach the vent cap

with four wood screws supplied. Figure 17

Vent Opening for Noncombustible Wall

NOTE: Replace the wood screws with appropriate fasteners for stucco, brick, concrete, or other types of siding.

7Z\x"

(190 mm)

Figure 15 -Fireplace Hearth

Locate Vent Opening on Wall

VO584-100

 

WARNING

Do not recess vent termination into any

 

 

 

 

wall. This will cause a fire hazard.

 

 

 

51D0528

17

Image 17
Contents What to do if YOU Smell GAS Lexington Direct Vent Gas FireplaceCongratulations ContentsInstaller Important Safety InformationOwner Please leave these instructions with the appliancePlease Read the Following Carefully Important Safety InformationCode Approval Gas Specifications & Orifice Size Product SpecificationsHigh Elevations GAS pressuresLX32 Fireplace & Framing Dimensions Fireplace and Framing DimensionsFireplace Framing Installation InformationBefore You Start Fireplace Location Installation InformationClearances to combustibles ClearancesMantel clearances Hearth requirements For the exact width of the faceFinishing Material Secure Fireplace to floor or framingOptional top vent application After conversion to top vent configuration4 102 mm flue pipe should be Concentric within the 6B\, 175 mm outerFailure to follow these instructions will void the warranty Installation precautionsVenting Installation Combustible Clearances for Vent Pipe Venting InstallationInstalling a vent system in an outside chase Installation planningFor horizontal termination For vertical terminationGeneral Venting Information Termination Location Venting InstallationFollowing vent installation instructions to determine How To Use The Vent GraphVent Graph should be read in conjunction with SystemWall. This will cause a fire hazard Rear Wall Vent installationDo not recess vent termination into any Horizontal through the wall ter- mination configurations Elbow Total Angular Variation 270 Example According to the vent graph Page 16Maximum horizontal vent length in a system with a Vertical through-the-roof applica- tions Below Grade InstallationsFlat Ceiling Installation Installation for Vertical TERMINA- TionEssary to reach from the burner system flue up through Assemble the desired lengths of pipe and elbows necFirestop. Be sure pipe and elbow connections are Fully twist-locked. Page 17, FigureCheck gas type Installing gas piping to fireplace locationPropane/LP Natural GasElectrical Wiring Heater 110V circuit Remote Wall mounted SwitchDo not connect wall switch to Reinstalling clamps, keep fingers clear Final InstallationGlass Frame Removal Each clamp has a quick spring force. WhenInstalL logs and rock wool ember material in firebox LOG PlacementLogs supplied with the unit Personal injuryRear Log #1 Place top left log #4 on two pins on left mid log. Figure Center Log #8 Air Space Under Rear Log 20 to 50% 30 to AIR Restrictor Adjustment100% Factory Setting Install Facing Facing InstallationOperating Instructions Leak testing Never use an open flame to check for gas leaksInitial lighting Operating Instructions Approved leak testing methodPilot position Main burner switchLighting the burner Cleaning glass Cleaning and maintenanceFirebox Cleaning Venting systemBlower Wiring Diagram for BlowerObserved Problem Possible Cause Remedy TroubleshootingReplacement Parts Replacement Parts Nantucket Decorative Arch Optional AccessoriesOptional Accessories LX Series Direct Vent Gas Fireplace LX Series Direct Vent Gas Fireplace Carbon Monoxide Detector Requirements Five Year Warranty Lifetime WarrantyBasic Warranty If Warranty Service is NeededModel EnerGuide Ratings Mhsc

LX36DV, LX32DV specifications

The Monessen Hearth LX36DV and LX32DV are premium direct vent gas fireplaces designed to provide warmth and ambiance in any living space. Both models showcase innovative engineering and elegant designs, making them a popular choice for homeowners seeking efficient heating solutions.

One of the main features of the LX36DV and LX32DV is their versatile design. Both units are available in various configurations, allowing them to seamlessly integrate into a range of architectural styles, from contemporary to traditional. Their clean face design and beveled edges contribute to a sleek, attractive appearance that enhances any room's aesthetic.

Efficiency is another standout characteristic of these fireplaces. Equipped with advanced gas burner technology, the LX36DV and LX32DV deliver an impressive heat output while maintaining a high efficiency rating. The direct vent system ensures that combustion gases are safely expelled outside, making it a safe alternative to traditional wood-burning fireplaces. This feature not only improves indoor air quality but also contributes to overall energy conservation.

The LX36DV and LX32DV also offer customizable options to enhance user experience. Customers can choose from various front styles, finishes, and media options, allowing for personalization that matches individual tastes. The addition of decorative glass or colorful crushed fireglass can transform the look of the fireplace, creating a unique focal point in the room.

In terms of technology, both models are equipped with remote control capabilities, allowing users to adjust flame height and heat settings from anywhere in the room. This convenience ensures optimal comfort while eliminating the need for manual adjustments. Additionally, these fireplaces come with innovative electronic ignition systems that provide reliable startup every time.

Safety features are prioritized in the design of the LX36DV and LX32DV. Each unit comes with safety screen options and can be modified to include childproof doors, making them a practical choice for families. The advanced flame sensing technology provides peace of mind as it automatically adjusts in response to room conditions.

In conclusion, the Monessen Hearth LX36DV and LX32DV are exemplary gas fireplaces that combine style, efficiency, and safety. With their customizable design, advanced technologies, and user-friendly features, these models stand out in the market, offering unrivaled warmth and elegance to any home. Whether you are heating a cozy family room or making a statement in a grand living area, these fireplaces provide both functionality and charm.