Heat & Glo LifeStyle 6000G-LP Install Attic Insulation Shield, Flat Ceiling Installation

Page 24

D. Install Attic Insulation Shield

WARNING! Fire Risk. DO NOT allow loose materials or insulation to touch vent. Hearth & Home Technologies Inc. requires the use of an attic shield.

The National Fuel Gas Code ANSI Z223.1 and NFPA 54 requires an attic shield constructed of 26 gauge minimum metal that extends at least 2 in. (51 mm) above insulation.

Attic shields must meet specified clearance and be se- cured in place.

Flat Ceiling Installation

• Remove one shield from box.

NOTICE: Cut previously installed batt insulation to make room for the attic insulation shield.

Wrap shield around pipe if pipe is already installed in area to be insulated.

Match the three holes in each side and fasten with three screws to form a tube.

Bend three tabs on the bottom of the shield outward to allow attachment to the ceiling firestop.

Bend the remaining bottom tabs inward 90° to maintain the air space between the pipe and the shield. Set the shield on the ceiling firestop and attach to the firestop.

Bend all tabs inward 90° around the top of the shield. These tabs must be used to prevent blown insulation from getting between the shield and vent pipe, and to maintain air space clearance.

Vaulted Ceiling Installation

The attic insulation shield has been laser-etched with cut lines and ceiling pitches to make field trimming easier.

Remove one shield from box.

NOTICE: Cut previously installed batt insulation to make room for the attic insulation shield.

Cut the attic insulation shield (if application is for vaulted ceiling) using a laser-etched cut line, to fit your ceiling pitch. Snip cut edge to recreate 1 in. bend tabs all the way around the bottom.

Wrap shield around pipe if pipe is already installed in area to be insulated.

Match the three holes in each side and fasten with three screws to form a tube.

Bend three tabs on the bottom of the shield outward to allow attachment to the ceiling firestop.

Bend the remaining bottom tabs inward 90° to maintain the air space between the pipe and the shield. Set the shield on the ceiling firestop and attach to the firestop.

Bend all tabs inward 90° around the top of the shield. These tabs must be used to prevent blown insulation from getting between the shield and vent pipe, and to maintain air space clearance.

BEND ALL TABS INWARD 90°

TO MAINTAIN CLEARANCE

AND PREVENT INSULATION

FROM FALLING INSIDE

LASER-ETCHED

INSERT 3 CUT LINES

SCREWS

BEND 3 TABS

OUTWARD TO

FASTEN TO CEILING

FIRESTOP-BEND

REMAINING TABS

INWARD 90 DEGREES

TO MAINTAIN

CLEARANCE

Figure 6.5 Attic Insulation Shield

24

Heat & Glo • 6000G, 6000G-IPI2103-900 Rev. M • 9/08

Image 24
Contents What to do if you smell gas Hot glass will cause burnsCongratulations Homeowner Reference InformationTable of Contents Listing and Code Approvals Installation of Carbon Monoxide Detectors Requirements for the Commonwealth of MassachusettsInstallation to ensure maximum safety and benefit Getting StartedTools and Supplies Needed Framing and Clearances Selecting Appliance LocationConstructing the Appliance Chase ClearancesClearance to Combustibles Mantel Projections To CeilingTermination Locations Vent Termination Minimum ClearancesSee .4 for specific clearances Alcove Applications Vent Information and Diagrams Vent Table KeyUse of Elbows Measuring StandardsVent Diagrams Top Vent Horizontal Termination One ElbowMinimum Maximum V1 Minimum H1 + H2 MaximumTop Vent Horizontal Termination Three Elbows Min Max V2 Min H2 MaxFlue Restrictor Instructions E a K R EMaximum + V 2 Min Top Vent Vertical Termination H1+ H2 V1 + V2 Minimum H1+ H2 MaximumRear Vent Horizontal Termination H1 = 16 in mm MaximumH1 Maximum V1 Minimum H1+ H2 Maximum H1 Maximum V1 Minimum H2+ H3 H1+ H2+ H3 MaxRear Vent Vertical Termination H1+ H2 Maximum V1 MinimumMaximum Minimum + H 2 Maximum V1 Minimum H1+ H2+ H3 Maximum 10 ftVent Clearances and Framing Pipe Clearances to CombustiblesWall Penetration Framing Combustible Wall PenetrationVertical Penetration Framing Pipe DVP SLPInstall Attic Insulation Shield Flat Ceiling InstallationVaulted Ceiling Installation Appliance Preparation Top VentProceed to . C Installing the Non-combustible Board Securing and Leveling the ApplianceInstall the Optional HEAT-ZONE-GAS Kit Installing Vent Pipe DVP and SLP Pipe Attach Vent to the Firebox AssemblyAssemble Vent Sections DVP Pipe Only Assemble Pipe Sections DVP Pipe OnlyAssemble Vent Sections SLP Pipe Only Assemble Slip SectionsSecure the Vent Sections Disassemble Vent SectionsInstall Decorative Ceiling Components SLP only Install Metal Roof Flashing Assemble and Install Storm CollarInstall RF4-8 SLP-FSInstall Vertical Termination Cap Install Decorative Wall Components SLP onlyHeat Shield Requirements for Horizontal Termination Install Horizontal Termination Cap DVP and SLP Pipe Ansi Z223.1 and CAN/CGA-B149 installation codesRefer to of this manual Gas Information Fuel Conversions Gas ConnectionGas Pressures Pressure Natural Gas PropaneHigh Altitude Installations Recommendation for Wire Intellifire Ignition System WiringConnecting to the Appliance Optional Accessories RequirementsStanding Pilot Ignition System Wiring Intellifire Pilot Ignition IPI Wiring DiagramJunction Box Installation Wall Switch Installation for Fan OptionalVAC to wall switch Finishing Facing MaterialFinishing Material Finish Door FIT Material See Maximum ThicknessAppliance Setup Clean the ApplianceAccessories Ember PlacementPositioning the Logs Log #1 SRV2103-10712 Front View Glass Assembly Air Shutter SettingScreen Mesh Grilles and TrimOperating Instructions Before Lighting ApplianceTurn off all electric power to the appliance Lighting Instructions IPIFinal inspection by For Your Safety Read Before Lighting Lighting Instructions Standing Pilot IgnitionFrequently Asked Questions Initial Break-in ProcedureAfter Appliance is Lit Troubleshooting Symptom Possible Causes Corrective ActionStanding Pilot Ignition System Troubleshooting Symptom Possible Cause Corrective ActionIntellifire Ignition System flame has been lit, flame Maintenance Tasks Maintaining and Servicing ApplianceInspect Maintenance Tasks Doors, SurroundsAppliance Dimension Diagram Reference MaterialsLocation Inches Millimeters Vent Components Diagrams P 4 5 4 5 E lb o wHorizontal Termination Cap DVP vent components787 mm 13-1/4 367 mm 24-5/8 625 mm 27-1/2 Roof Flashing Multi-pak 13-3/4 11-7/8 349 mm302 mm 13-3/4 13-7/8 352 mm 349 mmDVP-TVHW DVP-HRC-SS DVP-HRC-ZC-SS Horizontal Termination CAP Elbow Wall Shield FirestopRF4-8 Roof Flashing Ceiling Firestop SupportSnorkel Support Box-BlackPVK-80 AdapterLog Set Assembly Service PartsPart number list on following Service Parts List 6000G, 6000G-IPI At DepotStanding Pilot IPI IgnitionStanding Pilot Valve Assembly StockedIPI Valve Assembly 6000G-IPICONDITIONS, Exclusions & Limitation of Liability Limited Lifetime Warranty Contact Information

6000G-IPILP, 6000G-IPI, 6000G, 6000G-LP specifications

The Heat & Glo LifeStyle 6000 series offers a sophisticated solution for homeowners seeking both performance and style in their heating options. With models such as the 6000G, 6000G-IPILP, 6000G-IPI, and 6000G-LP, this series combines innovative technologies with elegant design, making it a preferred choice for many.

One of the standout features of the LifeStyle 6000 series is its advanced heating technology. The units utilize Direct Vent technology, which ensures efficient combustion by drawing air from the outside for combustion and venting exhaust air outdoors. This not only enhances efficiency but also maintains a safe and comfortable indoor environment. Additionally, these models are designed with advanced burner systems that provide realistic flame effects and a warm ambiance, making them perfect for any living space.

The aesthetic appeal of the LifeStyle 6000 series cannot be overlooked. These fireplaces boast a contemporary design that seamlessly integrates into various architectural styles. With customizable options like different front styles and finishes, homeowners can truly make the fireplace their own. The impressive viewing area, thanks to large glass doors, amplifies the beauty of the flames while also allowing for maximum heat output.

Thermal efficiency is a key characteristic of the LifeStyle 6000 series. With an impressive heating capacity, these units can effectively warm large spaces. Furthermore, they feature a range of BTU outputs, allowing users to select the model that best suits their heating needs. Models equipped with the IntelliFire Ignition system further enhance usability, providing reliable startup with the convenience of remote control operation.

Safety is also paramount in the design of the LifeStyle 6000 series. Each model comes with built-in safety features such as a glass safety barrier and optional automatic shut-off systems, ensuring peace of mind for users.

In summary, the Heat & Glo LifeStyle 6000 series, including the 6000G, 6000G-IPILP, 6000G-IPI, and 6000G-LP, stands out in the market for its combination of modern aesthetics, innovative heating technologies, and robust safety features. Whether enhancing a cozy living room or providing warmth in a spacious area, these fireplaces offer a stylish and efficient heating solution for contemporary homes.