Oakleaf Woodburning Stove

B. Clearances To Combustibles

CLEARANCE TO COMBUSTIBLES: Vertical Venting Configuration

Location

AUnit to Side Wall

B Unit to Back Wall

C Vent Pipe to Side Wall

D*

Vent Pipe to Back Wall

17" / 432 mm 14" / 356 mm 26.75" / 679 mm *17.5" / 444 mm

Pipe clearance may be reduced using double wall or insulated connector pipe, provided that you adhere to the specified clearances from the stove itself. Follow pipe manufacturer's guidelines.

C

A

D*

B

*NFPA 211 specifies 18" clearance to single wall connector pipe. This lower clearance is based on actual safety test conditions.

For clearance reduction methods, refer to NFPA 211 or Local Codes

CLEARANCE TO COMBUSTIBLES: Vertical Vent, Horizontal Exit

 

Location

 

A

Unit to Side Wall

16" / 407 mm

B

Unit to Back Wall

13" / 330 mm

C

Vent Pipe to Side Wall

25.25" / 641 mm

D*

Vent Pipe to Back Wall

*17" / 432 mm

E*

Vent Pipe to Ceiling

*16" / 407 mm

F

Minimum Vertical

0" / 0 mm

Pipe clearance may be reduced using double wall or insulated connector pipe, provided that you adhere to the specified clearances from the stove itself. Follow pipe manufacturer's guidelines.

*NFPA 211 specifies 18" clearance to single wall connector pipe. This lower clearance is based on actual safety test conditions.

 

E

F

C

 

A

C

A

E

D

B

10 Dry Seasoned Wood Only!

3-90-798

Save These Instructions

Image 10
Contents Installation and Operation ModelOakleaf Woodburning Stove Table of Contents 1Listing and Code Approvals This appliance is also approved for installation in a shopMobile Home Approved If the alarm sounds 2Special Warnings and Notes3Getting Started Design, Installation & Location ConsiderationsFire Safety Appliance LocationComponent Locations Flue Direction ConversionPre- Use Check List Fire Risk4Dimensions & Clearances Appliance DimensionsClearances To Combustibles 17 / 432 mm 14 / 356 mm 26.75 / 679 mm *17.5 / 444 mmClearance to Combustibles Requirements Floor Protection RequirementsFloor Protection Floor Protection RequirementsDraft Chimney ConnectorsChimneys and Venting Wall Pass-thrusAN Approved Canadian Wall PASS-THROUGH ChimneyVenting to a Masonry Chimney Installing to a Prefabricated ChimneyExisting Masonry Chimneys Venting to a Masonry Fireplace ChimneyChimney Cap Storm Collar Sections Roof Flashing Airtight insulated Clean-out Stainless Steel Chimney Connector Must Extend to Flue Liner Full Relining Fireplace Conversion Freestanding Appliance Chimney Breach Fireplace Conversion with Combustible Wall Mobile Home Installation 6Mobile HomeOutside Air Attachment Leveling the Appliance Appliance Set-UpOptional Cooking Grill Optional Rear-vent Rear Shield Optional Blower InstallationOptional Bottom Heat Shield 8Operating Instructions Fuel SpecificationsAlways wear fire retardant Gloves when operating the stove General Operating InformationDoors Or change the configuration of this grate systemCombustion Process GratesBefore Your First Fire User ControlsBuilding and Maintaining a Fire Oakleaf Woodburning Stove Seasonal cleaning 9Service & MaintenanceCreosote- Formation and Need For Removal By User Wear Leather Gloves To Prevent Skin Burns General Maintenance ProceduresAsh Removal Door GlassFirebox Chimney ConnectorBlower- If installed ChimneyOakleaf Optional Blower Kit #1-00-797032 Wiring Diagram 10Reference MaterialsService Parts OakleafStocked At depotStocked at depot Grams Per Hour 50% 60% 70% 80% 90% 100%Limited Lifetime Warranty Hearth & Home Technologies IncWarranty Conditions This warranty is void ifService & Maintenance Log Page Proudly Printed On 100% Recycled Paper