Oakleaf Woodburning Stove
| |
| side only. If two covers are |
Hole with a minimum | used, each must be mounted |
clearance of 18" (450 mm) | on |
between connector and wall. | at least 7/8" (21mm) away |
| from the wall. |
1" (25mm) Clearance
AN APPROVED CANADIAN
WALL PASS-THROUGH
Closest | Minimum 2" (50mm) | |
Combustible | ||
Material | Clearance to Brick | |
| Liner | Minimum 12" |
| (300mm) to Brick | |
|
| |
| Flue | Fire Clay |
| Thimble | |
|
| |
| Chimney | Chimney |
|
|
Connector
Masonry Chimney Built to
NFPA 211 Specifications.
Minimum 12" (300mm) to Combustibles
AN APPROVED U.S.
WALL
D. The Chimney
This unit must be installed into a chimney approved for use with
In Canada, this unit is listed for use with prefabricated chimneys tested and listed to the high temperature (650 degrees C) chimney standard, ULC
Do not connect this unit to a chimney flue servicing another appliance.
NOTE: The restriction of not venting more than one appliance to the same flue applies to the U.S. specifically. While it is not recommended that you use the same chimney for more than one appliance, in Canada certain exceptions may be made. Be sure to contact your building code inspection official to see if this option is allowed in your area, and to find out the specific requirements for such an installation.
For mobile homes, (US only) it must only be installed with a factory built stainless steel chimney. The chimney system should include all required installation compo- nents, such as vapor barriers and roof flashing, as tested for use in mobile homes.
The minimum recommended height for any chimney is 16 ft. (4.8 m) above flue collar height. For
Codes require that
m) above the highest point at which they exit from the |
roof. Then, the chimney must extend 2 ft. (0.6 m) above |
More Than 10 ft. (3m)
10 ft. (3m)
2 ft. (0.6m) min.
Ridge
Chimney
Height Necessary Above Any Roof Sur- face Within 10ft. (3m)
3ft. (0.9m) minimum above exit
point
the highest point within a 10 ft (3 m) radius. Thus, the 3 |
foot, 2 foot, 10 foot rule: |
3ft. - Above roof exit point |
2ft. - Higher than anything within- |
10ft. of the chimney. |
The 3-foot, 2-foot, 10 foot rule
14 Dry Seasoned Wood Only! | Save These Instructions |