Hubbell Electric Heater Company J manual Section III Scheduled Maintenance and Operation, Freezing

Page 19

SECTION III - SCHEDULED MAINTENANCE AND OPERATION

WARNING / CAUTION

Before performing any maintenance procedure, make certain the power supply is turned OFF and cannot accidentally be turned on.

MAINTENANCE AND OPERATION

The water heater is automatic in its operation. It will maintain a full tank of water at the temperature setting of the controller. The water heater should not be turned on without first making sure that the tank is full of water and that all air has been released.

FREEZING

The tank should be fully drained in the event the electricity has been turned off and if there is danger of freezing.

CONTROLLER OPERATION

NOTE: All controller variables come preset from the factory to include a preset temperature of 185°F.

1.To turn unit on or off:

a.Press the ON/OFF button on the display module.

b.Note that the controller will resume its last mode of operation if power is disconnected.

2.To change setpoint temperature (the temperature is fully adjustable from 32° to 194°F (0°-90°C):

a.Press the UP and DOWN arrows simultaneously to enter setpoint change mode.

b.Press the UP or DOWN button to change the setpoint temperature.

c.Pressing and holding the UP or DOWN button will scroll through the setpoint temperature.

d.To leave setpoint change mode

i.Wait 5 seconds without pushing any buttons or press the UP and DOWN buttons simultaneously.

3.To view the number of operational hours (the number of hours when a contactor is pulled in) and software version:

a.Press the UP and DOWN arrows simultaneously to enter setpoint change mode.

b.Press the ON/OFF button.

c.Display will flash the software version (e.g. R14), HRS, followed by the hours in thousands of hours, followed by the hours.

i.Example: r14, HrS, 123, 456; indicates software version R1.4 and 123,456 hours.

d.To leave operational hours mode

i.Wait 5 seconds without pushing any buttons or press the UP and DOWN buttons simultaneously.

4.Configuration Menu. (NOTE: Configuration menu change should only be made by qualified personnel).

a.To enter the configuration menu, press and hold the UP, DOWN, and ON/OFF buttons simultaneously for 5 seconds.

b.To scroll through menu settings, press the ON/OFF button.

c.To make a change to a menu setting use either the UP or DOWN arrow.

d.Settings:

i.Relays – sets the number of magnetic contactors used in the heater.

1.r##, where ## is the number of magnetic contactors (01 or 02).

19

Image 19
Contents Operating and Maintenance Manual for Electric Booster Heater STRATFORD, CT Hubbell Electric Heater Company Seymour StreetTable of Contents Section Title Capacity Section I General Description and ConstructionPage Heating Element Power Circuit BreakersConstruction Tank Tank ConnectionsPressure Reducing Valve Dial Temperature and Pressure GaugeOptional Equipment Water Heater Placement Section II Installation and START-UPSlide Brackets for Hanging Support Mounting Manual Release Lever Optional XB1 LOW Temperature Interlock Electrical InstallationFilling the Heater Common no Optional Remote Alarm ContactsFinal Checks For Remote ON/OFF ControlWiring Chart Diagram 1WT 1NT WT L1 L2 L3 13 NT NCB L1 L2 L3 Page Controller Operation Section III Scheduled Maintenance and OperationMaintenance and Operation FreezingQuarterly Inspection Err, No, H2O Section IV Troubleshooting Error MessagesMiscellaneous Contactor CareOK? Troubleshooting Flow ChartsContinuous No Display Is the circuit Breaker tripped at Source? Section V Servicing & Replacement of Parts Relief Valve Control BoardSensor Probe Category Description Volts Ohms Hubbell P/N Section VI Service Parts ListSection VII Torque Values Part Wire Size Torque inlbs Torque ftlbsSuch Warranties do not Cover Section Viii Warranty Information Limited Warranty