Hubbell Electric Heater Company J manual Diagram

Page 14

 

 

 

Unit

Branch

Phase-Phase

Min. Feed

Internal

Element

Copper Power

Conduit

 

kW

Volt

Ph

Amp

Resistance

Breaker or

Power Wire

Jumper

Diagram

Amp Draw

Feed Wire Size

Size

 

 

 

Draw

(Ohms)

Fuse Size

Size

Wire Size

 

 

 

 

 

 

 

 

 

208

1

115.4

38.5

1.8

145

10

12

1/0

1¼"

3A

 

208

3

66.6

66.6

3.6

85

8

10

4

1"

13(NT)

24

240

1

100.0

33.3

2.4

130

12

12

1

1¼"

3A

240

3

57.7

57.7

4.8

75

8

10

4

1"

13(NT)

 

 

480

3

28.9

28.9

19.2

40

12

12

8

½"

13(WT)

 

600

3

22.6

22.6

30.6

30

12

12

10

½"

15

 

208

1

130.0

43.3

1.6

165

10

12

2/0

1½"

6A

 

208

3

74.9

37.5

3.2

95

10

12

3

1"

12(NCB)

27

240

1

112.5

37.5

2.1

145

10

12

1/0

1¼"

3A

240

3

65.0

65.0

4.3

85

8

10

4

1"

13(NT)

 

 

480

3

32.5

32.5

17.1

45

12

12

8

½"

13(WT)

 

600

3

27.2

27.2

25.5

35

12

12

8

½"

15

 

208

1

144.2

48.1

1.4

185

8

10

3/0

1½"

6A

 

208

3

83.3

41.6

2.9

105

10

12

2

1"

12(NCB)

30

240

1

125.0

41.7

1.9

160

10

12

2/0

1½"

6A

240

3

72.2

36.1

3.8

95

10

12

3

1"

12(NCB)

 

 

480

3

36.1

36.1

15.4

50

10

12

8

½"

13(WT)

 

600

3

29.4

29.4

23.6

40

12

12

8

½"

15

 

208

1

173.1

57.7

1.2

220

8

10

4/0

2"

6A

 

208

3

99.9

50.0

2.4

125

8

10

1

1¼"

12(NCB)

36

240

1

150.0

50.0

1.6

190

8

10

3/0

1½"

6A

240

3

86.6

43.3

3.2

110

10

12

2

1"

12(NCB)

 

 

480

3

43.3

43.3

12.8

55

10

12

6

¾"

13(WT)

 

600

3

36.2

36.2

19.1

50

10

12

8

½"

15

 

208

1

187.5

62.5

1.1

235

8

10

250

2"

6A

 

208

3

108.3

54.1

2.2

140

8

10

1/0

1¼"

12(NCB)

39

240

1

162.5

54.2

1.5

205

8

10

4/0

1½"

6A

240

3

93.8

46.9

3.0

120

10

12

1

1"

12(NCB)

 

 

480

3

46.9

46.9

11.8

60

8

10

6

¾"

13(WT)

 

600

3

36.2

36.2

19.1

50

10

12

8

¾"

15

 

208

1

195.0

65.0

1.1

245

8

10

250

2"

6A

 

208

3

112.6

56.3

2.1

145

8

10

1/0

1¼"

12(NCB)

40.5

240

1

168.8

56.3

1.4

215

8

10

250

1½"

6A

240

3

97.4

48.7

2.8

125

10

12

1

1"

12(NCB)

 

 

480

3

48.7

48.7

11.4

65

8

10

4

¾"

13(WT)

 

600

3

36.2

36.2

19.1

50

10

12

8

¾"

15

 

208

3

119.1

59.5

1.9

150

8

10

2/0

1¼"

12(NCB)

45

240

1

187.5

62.5

1.3

235

8

10

250

2"

6A

240

3

108.3

54.1

2.6

140

8

10

1/0

1¼"

12(NCB)

 

480

3

54.1

54.1

10.2

70

8

10

4

¾"

13(WT)

 

600

3

42.2

42.2

16.4

55

10

12

6

¾"

15

 

208

3

149.9

74.9

1.6

190

6

8

3/0

1½"

12

54

240

3

129.9

65.0

2.1

165

8

10

2/0

1½"

12

480

3

65.0

65.0

8.5

85

8

10

4

1"

13(WT)

 

 

600

3

54.3

54.3

12.8

70

8

10

4

1"

15

 

208

3

159.9

79.9

1.5

200

6

8

4/0

1½"

12

58.5

240

3

140.7

70.4

2.0

180

6

8

2/0

1½"

12

480

3

70.4

35.2

7.9

90

12

12

3

1"

12(WT)

 

 

600

3

54.3

54.3

12.8

70

8

10

4

1"

15

Notes:

1.Power feed wire sizing is based on using 75°C Cu THHN wire with feeder branch protection rated at 125%.

2.Internal wire sizing is based on using 200°C SEW-2 or PTFE wiring in a raceway with an ambient temperature up to 60°C.

3.For information on 380V, 415V, or 440V models reference the supplied drawing or contact the factory.

4.Normal phase-to-phase resistance tolerance is ±5%.

5.480-volt and 600-volt phase-to-phase resistance values are shown with the transformer disconnected.

6.For 575V models, multiply the kW rating of the 600V model by a de-rating factor of 0.92 to get the actual rating for 575V.

7.For models manufactured prior to June 24, 2005, that utilize wiring diagrams 3, 5, 6, 7(NT), 7(WT), or 11 please contact the factory for wiring diagrams.

14

Image 14
Contents Operating and Maintenance Manual for Electric Booster Heater Hubbell Electric Heater Company Seymour Street STRATFORD, CTTable of Contents Section Title Section I General Description and Construction CapacityPage Tank Connections Power Circuit BreakersConstruction Tank Heating ElementOptional Equipment Dial Temperature and Pressure GaugePressure Reducing Valve Slide Brackets for Hanging Support Mounting Section II Installation and START-UPWater Heater Placement Manual Release Lever Filling the Heater Electrical InstallationOptional XB1 LOW Temperature Interlock Optional Remote Alarm Contacts Common noFor Remote ON/OFF Control Final ChecksWiring Chart Diagram 1WT 1NT WT L1 L2 L3 13 NT NCB L1 L2 L3 Page Freezing Section III Scheduled Maintenance and OperationMaintenance and Operation Controller OperationQuarterly Inspection Section IV Troubleshooting Error Messages Err, No, H2OContactor Care MiscellaneousTroubleshooting Flow Charts OK?Continuous No Display Is the circuit Breaker tripped at Source? Section V Servicing & Replacement of Parts Control Board Relief ValveSensor Probe Section VI Service Parts List Category Description Volts Ohms Hubbell P/NPart Wire Size Torque inlbs Torque ftlbs Section VII Torque ValuesSection Viii Warranty Information Limited Warranty Such Warranties do not Cover