Hubbell Electric Heater Company J manual Control Board, Relief Valve

Page 27

CONTROL BOARD

1.Disconnect power from unit.

2.Disconnect display cable, probe cable (J3), leak detection wire (J2), ground wire (J7), and terminal block (J5) from the control board. NOTE: The terminal block (J5) is removable from the control board. Grasp the terminal block on the ends and pull straight away from the board.

Ground Wire (J7)

Display Cable

Leak Detection Wire (J2)

Probe Cable (J3)

Power Wire (Common, White)

Connector (J5)

Power Wire (Black)

Wire to #1 Contactor (yellow)

 

Wire to #2 Contactor (red)

3.Remove four (4) screws securing control board to panel.

4.Remove and replace control board.

5.Reconnect wires disconnected in step 2. NOTE: When reconnecting the ribbon cable be sure to have the key on the cable align with the slot in the connector.

6.Connect power to unit.

RELIEF VALVE

1.Disconnect power from unit.

2.Shut off incoming water supply.

3.Attach hose to drain connection.

4.Lift manual release lever on relief valve to let air into system or break union on outgoing water line.

5.Drain water from tank.

6.Disconnect overflow piping.

7.Unscrew relief valve, remove assembly and replace with new one.

8.Connect overflow piping.

9.Turn on incoming water supply and check for leaks.

10.Connect power to unit.

27

Image 27
Contents Operating and Maintenance Manual for Electric Booster Heater STRATFORD, CT Hubbell Electric Heater Company Seymour StreetTable of Contents Section Title Capacity Section I General Description and ConstructionPage Heating Element Power Circuit BreakersConstruction Tank Tank ConnectionsDial Temperature and Pressure Gauge Pressure Reducing ValveOptional Equipment Section II Installation and START-UP Water Heater PlacementSlide Brackets for Hanging Support Mounting Manual Release Lever Electrical Installation Optional XB1 LOW Temperature InterlockFilling the Heater Common no Optional Remote Alarm ContactsFinal Checks For Remote ON/OFF ControlWiring Chart Diagram 1WT 1NT WT L1 L2 L3 13 NT NCB L1 L2 L3 Page Controller Operation Section III Scheduled Maintenance and OperationMaintenance and Operation FreezingQuarterly Inspection Err, No, H2O Section IV Troubleshooting Error MessagesMiscellaneous Contactor CareOK? Troubleshooting Flow ChartsContinuous No Display Is the circuit Breaker tripped at Source? Section V Servicing & Replacement of Parts Relief Valve Control BoardSensor Probe Category Description Volts Ohms Hubbell P/N Section VI Service Parts ListSection VII Torque Values Part Wire Size Torque inlbs Torque ftlbsSuch Warranties do not Cover Section Viii Warranty Information Limited Warranty