Field Controls MPL-B, WML-C manual Cfm, Power, Speed

Page 15

Table A-6 Direct Drive Blower Set-Up

Furnace

 

 

 

 

 

 

 

 

 

Blower Set-Up

 

 

 

 

 

Cooling Capacity

 

 

Blower

 

 

 

 

0.20 in. w.c.

 

0.50 in. w.c.

 

 

 

 

 

 

 

 

Model

 

 

 

 

 

 

 

 

Tons

 

 

Power

 

CFM Range

 

 

 

 

 

Speed

 

Motor

 

Speed

Motor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WML-60C

 

GT10 DD

 

 

 

Low

 

½ HP

 

Med-Low

½ HP

 

 

3

 

 

½ HP

 

763 – 1505

WML-80C

 

GT10 DD

 

 

Med-Low

 

½ HP

 

Med-High

½ HP

 

 

3

 

 

½ HP

 

763 – 1505

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WML-90C

 

GT10 DD

 

 

Med-High

 

½ HP

 

High

½ HP

 

 

3

 

 

½ HP

 

763 – 1505

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MPL-90B

 

GT12-10DD

 

 

Low

 

¾ HP

 

Med-High

¾ HP

 

 

3

 

 

¾ HP

 

1185 – 1553

MPL-100B

 

GT12-10DD

 

Med-High

 

¾ HP

 

High

¾ HP

 

 

3

 

 

¾ HP

 

1185 – 1553

MPL-120B

 

GT12-10DD

 

 

High

 

¾ HP

 

High

¾ HP

 

 

3

 

 

¾ HP

 

1185 – 1553

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MPL-130B

 

GT12-10DD

 

 

High

 

¾ HP

 

High

¾ HP

 

 

3

 

 

¾ HP

 

1185 – 1553

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table A-8 Direct Drive Blower Characteristics

 

 

 

 

 

Furnace

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CFM

 

 

Blower

 

Motor HP

 

Motor FLA

∆T

 

Speed

 

 

External Static Pressure – Inches w.c.

 

Model

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.20

 

0.30

 

0.40

 

0.50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LOW

 

813

 

813

 

797

 

763

WML-C

 

GT10

 

 

½ HP

 

7.0

 

45-75°F

 

MED-LOW

 

1170

 

1144

 

1118

 

1063

60 - 90

 

 

 

 

 

 

MED-HIGH

 

1423

 

1381

 

1291

 

1220

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HIGH

 

1505

 

1444

 

1359

 

1291

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LOW

 

1334

 

1286

 

1239

 

1185

MPL-B

GT12-10DD

 

 

¾ HP

 

12.5

 

50-80°F

 

MED-LOW

 

1389

 

1332

 

1287

 

1236

90-130

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MED-HIGH

 

1423

 

1373

 

1326

 

1289

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HIGH

 

1553

 

1491

 

1449

 

1331

TIP:

These Formulae will assist with the design of the ductwork and the determination of airflow delivery:

CFM =

Bonnet Output

SystemTemperature Rise=

Bonnet Output

(1085.x SystemTemperature Rise)

(1085.x CFM )

15

30318 R4 9/9/2005

Image 15
Contents WML-C and MPL-B Table of Contents Location of Unit DOWN-FLOW InstallationIntroduction Heat LossAIR Conditioning Suspended InstallationChimney Venting Combustion AIRCommon Chimney Problems Electrical Connections Piping InstallationOptional Side Wall Venting OIL TankCirculating AIR Blower FAN Timer Board and Limit ControlHoneywell ST9103 Dip Switch Blower Off Delay Position Time Dip Switch Blower Delay Position Times Off Seconds MinutesOIL Burner HumidifierChecking Over-Fire Draft Furnace Installation SET- UPMaintenance and Service Routine Maintenance By Home OwnerAnnual Service By Contractor To Shut Down Unit Operating Instructions Before Lighting To Light UnitAF76YB Appendix A- WML-C and MPL-B Burner SET UPOIL Burner AIR Adjustment Burner ElectrodesStart UP Power CFMSpeed 20 x 20 x Size WeightModel 55-1/4 19 x 18 xAppendix B Wiring Diagrams Beckett Afii Burner Wiring Diagram Riello 40F3 and F5 Burner Wiring Diagram Riello 40BF3 Burner Wiring Diagram Operation of OIL Burner Thermostat calls for heat 30318 R4 9/9/2005 Operation Returns to Idle State Recycle Timer StartsHeat Mode Action System ResponseR7184 LED Diagnostic Light TroubleshootingElectrical Shock Hazard Corrective Action Table C-3 R7184 TroubleshootingRemount control onto burner housing. Go to step Problem Possible Cause Remedy Table C4 System and General TroubleshootingTiming Final Check OUT Parts Listing Counterflow Horizontal Model WML C Parts Listing Vestibule KIT WML C 30318 R4 9/9/2005 Parts Listing Counterflow Horizontal Model MPL Flame Retention Head MPL 30318 R4 9/9/2005 If Different from Installation Contractor HOMEOWNER’S Reference TableFuel Supplier 30318 R4 9/9/2005 Tel 716 Fax 716